@prefix rdf: . @prefix rdfs: . @prefix xsd: . @prefix owl: . @prefix ph: . @prefix phScience: . @prefix phIoT: . ph:hasTag a owl:ObjectProperty ; rdfs:range ph:marker . _:b-0000 a phIoT:site ; ph:hasTag phIoT:site ; rdfs:label "Bravo" ; phIoT:area 78000 ; ph:dis "Bravo" ; ph:geoAddr "123 Some Rd, Fort Wayne, IN 46900" ; ph:geoCity "Fort Wayne" ; ph:geoCountry "US" ; ph:geoCounty "US" ; ph:geoPostalCode "46900" ; ph:geoState "IN" ; ph:geoStreet "123 Some Rd" ; phIoT:primaryFunction "Hospital (General Medical & Surgical)" ; ph:tz "Chicago" ; phIoT:weatherStationRef _:b-042f ; phIoT:yearBuilt 2000 ; _:custom _:0aa7c726-ad69-4180-5197-f23c91a70cca . _:0aa7c726-ad69-4180-5197-f23c91a70cca rdfs:label "" ; _:elecFreq 60 . _:b-0001 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:chilledWaterCooling, phIoT:equip, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo BCU-1" ; ph:dis "Bravo BCU-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; _:custom _:0aa7c726-ad78-83c0-5198-f23c91a70cca . _:0aa7c726-ad78-83c0-5198-f23c91a70cca rdfs:label "" . _:b-0002 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo BCU-1 Cooling Valve Output" ; ph:dis "Bravo BCU-1 Cooling Valve Output" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-ad78-83c1-5199-f23c91a70cca . _:0aa7c726-ad78-83c1-5199-f23c91a70cca rdfs:label "" ; _:predictionConf 0.31259757180034364 ; _:sourcePointName "ChwVlvOR_value" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0003 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:mixed, phIoT:point ; rdfs:label "Bravo BCU-1 Mixed Air Damper Output" ; ph:dis "Bravo BCU-1 Mixed Air Damper Output" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-ad78-83c2-519a-f23c91a70cca . _:0aa7c726-ad78-83c2-519a-f23c91a70cca rdfs:label "" ; _:predictionConf 0.28394372966813813 ; _:sourcePointName "MadOR_value" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0004 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo BCU-1 Supply Air Temperature" ; ph:dis "Bravo BCU-1 Supply Air Temperature" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ad78-83c3-519b-f23c91a70cca . _:0aa7c726-ad78-83c3-519b-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7893816782198223 ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0005 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo BCU-1 Zone Temperature" ; ph:dis "Bravo BCU-1 Zone Temperature" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ad78-83c4-519c-f23c91a70cca . _:0aa7c726-ad78-83c4-519c-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6720981954640639 ; _:sourcePointName "SpaceTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0006 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo BCU-1 Zone Temperature Setpoint" ; ph:dis "Bravo BCU-1 Zone Temperature Setpoint" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ad78-83c5-519d-f23c91a70cca . _:0aa7c726-ad78-83c5-519d-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0007 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:chilledWaterCooling, phIoT:equip, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo BCU-2" ; ph:dis "Bravo BCU-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; _:custom _:0aa7c726-ad78-83c6-519e-f23c91a70cca . _:0aa7c726-ad78-83c6-519e-f23c91a70cca rdfs:label "" . _:b-0008 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo BCU-2 Cooling Valve Output" ; ph:dis "Bravo BCU-2 Cooling Valve Output" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-ad78-83c7-519f-f23c91a70cca . _:0aa7c726-ad78-83c7-519f-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlvOR_value" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0009 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:mixed, phIoT:point ; rdfs:label "Bravo BCU-2 Mixed Air Damper Output" ; ph:dis "Bravo BCU-2 Mixed Air Damper Output" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-ad78-83c8-51a0-f23c91a70cca . _:0aa7c726-ad78-83c8-51a0-f23c91a70cca rdfs:label "" ; _:sourcePointName "MadOR_value" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-000a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo BCU-2 Supply Air Temperature" ; ph:dis "Bravo BCU-2 Supply Air Temperature" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ad78-83c9-51a1-f23c91a70cca . _:0aa7c726-ad78-83c9-51a1-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-000b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo BCU-2 Zone Temperature" ; ph:dis "Bravo BCU-2 Zone Temperature" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ad78-83ca-51a2-f23c91a70cca . _:0aa7c726-ad78-83ca-51a2-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpaceTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-000c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo BCU-2 Zone Temperature Setpoint" ; ph:dis "Bravo BCU-2 Zone Temperature Setpoint" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ad78-83cb-51a3-f23c91a70cca . _:0aa7c726-ad78-83cb-51a3-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-000d a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo BCUs" ; ph:dis "Bravo BCUs" ; phIoT:siteRef _:b-0000 ; _:custom _:0aa7c726-ad78-83cc-51a4-f23c91a70cca . _:0aa7c726-ad78-83cc-51a4-f23c91a70cca rdfs:label "" . _:b-000e a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Boiler 1" ; ph:dis "Bravo Boiler 1" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; _:custom _:0aa7c726-ad78-83cd-51a5-f23c91a70cca . _:0aa7c726-ad78-83cd-51a5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterPower 4200 ; _:designMake "Bryan Boiler" ; _:designModel "RV-500W" . _:b-000f a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Boiler 1 Boiler Status" ; ph:dis "Bravo Boiler 1 Boiler Status" ; phIoT:equipRef _:b-000e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0aa7c726-ad78-83ce-51a6-f23c91a70cca . _:0aa7c726-ad78-83ce-51a6-f23c91a70cca rdfs:label "" ; _:sourcePointName "HwBlr1Sts" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0010 a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Boiler 2" ; ph:dis "Bravo Boiler 2" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; _:custom _:0aa7c726-ad78-83cf-51a7-f23c91a70cca . _:0aa7c726-ad78-83cf-51a7-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterPower 4200 ; _:designMake "Bryan Boiler" ; _:designModel "RV-500W" . _:b-0011 a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Boiler 2 Boiler Status" ; ph:dis "Bravo Boiler 2 Boiler Status" ; phIoT:equipRef _:b-0010 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0aa7c726-ad78-83d0-51a8-f23c91a70cca . _:0aa7c726-ad78-83d0-51a8-f23c91a70cca rdfs:label "" ; _:sourcePointName "HwBlr2Sts" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0012 a phIoT:hot-water-plant ; ph:hasTag phIoT:equip, phIoT:hot, phIoT:hvac, phIoT:plant, phScience:water ; rdfs:label "Bravo Boiler Plant" ; ph:dis "Bravo Boiler Plant" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab . _:b-0013 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:domestic, phIoT:his, phIoT:hot, phIoT:leaving, phIoT:point, phIoT:sp, phScience:temp, phScience:water ; rdfs:label "Bravo Boiler Plant Domestic Hot Water Leaving Temperature Setpoint" ; ph:dis "Bravo Boiler Plant Domestic Hot Water Leaving Temperature Setpoint" ; phIoT:equipRef _:b-0012 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ad87-c600-51a9-f23c91a70cca . _:0aa7c726-ad87-c600-51a9-f23c91a70cca rdfs:label "" ; _:sourcePointName "HwSp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0014 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:delta, phIoT:his, phIoT:hot, phIoT:point, phScience:pressure, phIoT:sp, phScience:water ; rdfs:label "Bravo Boiler Plant Heating Hot Water Differential Pressure Setpoint" ; ph:dis "Bravo Boiler Plant Heating Hot Water Differential Pressure Setpoint" ; phIoT:equipRef _:b-0012 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; ph:unit "psi" ; _:custom _:0aa7c726-ad87-c601-51aa-f23c91a70cca . _:0aa7c726-ad87-c601-51aa-f23c91a70cca rdfs:label "" ; _:sourcePointName "HWDifSP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0015 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heating, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Boiler Plant Heating Hot Water Return Temperature" ; ph:dis "Bravo Boiler Plant Heating Hot Water Return Temperature" ; phIoT:equipRef _:b-0012 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ad87-c602-51ab-f23c91a70cca . _:0aa7c726-ad87-c602-51ab-f23c91a70cca rdfs:label "" ; _:sourcePointName "HWRTEMP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0016 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:leaving, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Boiler Plant Heating Hot Water Supply Temperature" ; ph:dis "Bravo Boiler Plant Heating Hot Water Supply Temperature" ; phIoT:equipRef _:b-0012 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ad87-c603-51ac-f23c91a70cca . _:0aa7c726-ad87-c603-51ac-f23c91a70cca rdfs:label "" ; _:sourcePointName "HWSTEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0017 a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo CHW System" ; ph:dis "Bravo CHW System" ; phIoT:siteRef _:b-0000 ; _:custom _:0aa7c726-ad87-c604-51ad-f23c91a70cca . _:0aa7c726-ad87-c604-51ad-f23c91a70cca rdfs:label "" . _:b-0018 a phIoT:equip ; ph:hasTag phIoT:chilled, phIoT:equip, phIoT:hvac, phIoT:pump, phScience:water ; rdfs:label "Bravo CHWP-1" ; ph:dis "Bravo CHWP-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 . _:b-0019 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:pump, phIoT:sensor, phScience:water ; rdfs:label "Bravo CHWP-1 Chilled Water Pump Enable" ; ph:dis "Bravo CHWP-1 Chilled Water Pump Enable" ; ph:enum "Stop,Running" ; phIoT:equipRef _:b-0018 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ad87-c605-51ae-f23c91a70cca . _:0aa7c726-ad87-c605-51ae-f23c91a70cca rdfs:label "" ; _:poinTags "point and chilled and water and cmd and pump" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-001a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:pump, phIoT:sensor, phScience:speed, phScience:water ; rdfs:label "Bravo CHWP-1 Chilled Water Pump VFD Speed" ; ph:dis "Bravo CHWP-1 Chilled Water Pump VFD Speed" ; phIoT:equipRef _:b-0018 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-ad87-c606-51af-f23c91a70cca . _:0aa7c726-ad87-c606-51af-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-07-14T01:00:03.512-04:00"^^xsd:dateTime ; _:precision 2 ; _:dataSyncType "error" . _:b-001b a phIoT:equip ; ph:hasTag phIoT:chilled, phIoT:equip, phIoT:hvac, phIoT:pump, phScience:water ; rdfs:label "Bravo CHWP-2" ; ph:dis "Bravo CHWP-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 . _:b-001c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:pump, phIoT:sensor, phScience:water ; rdfs:label "Bravo CHWP-2 Chilled Water Pump Enable" ; ph:dis "Bravo CHWP-2 Chilled Water Pump Enable" ; ph:enum "Stop,Running" ; phIoT:equipRef _:b-001b ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ad87-c607-51b0-f23c91a70cca . _:0aa7c726-ad87-c607-51b0-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-001d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:pump, phIoT:sensor, phScience:speed, phScience:water ; rdfs:label "Bravo CHWP-2 Chilled Water Pump VFD Speed" ; ph:dis "Bravo CHWP-2 Chilled Water Pump VFD Speed" ; phIoT:equipRef _:b-001b ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-ad87-c608-51b1-f23c91a70cca . _:0aa7c726-ad87-c608-51b1-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-001e a phIoT:chilled-water-plant ; ph:hasTag phIoT:chilled, phIoT:equip, phIoT:hvac, phIoT:plant, phScience:water ; rdfs:label "Bravo Chilled Water Plant" ; ph:dis "Bravo Chilled Water Plant" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 . _:b-001f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cooling, phIoT:cur, phIoT:enable, phIoT:his, phIoT:point ; rdfs:label "Bravo Chilled Water Plant AHU Cooling Enable" ; ph:dis "Bravo Chilled Water Plant AHU Cooling Enable" ; phIoT:equipRef _:b-001e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ad87-c609-51b2-f23c91a70cca . _:0aa7c726-ad87-c609-51b2-f23c91a70cca rdfs:label "" ; _:sourcePointName "AHUClgEnable" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0020 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:heating, phIoT:his, phIoT:point ; rdfs:label "Bravo Chilled Water Plant AHU Heating Enable" ; ph:dis "Bravo Chilled Water Plant AHU Heating Enable" ; phIoT:equipRef _:b-001e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ad87-c60a-51b3-f23c91a70cca . _:0aa7c726-ad87-c60a-51b3-f23c91a70cca rdfs:label "" ; _:sourcePointName "AHUHtgEnable" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0021 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo Chilled Water Plant CV-1 Valve Signal (HHW)" ; ph:dis "Bravo Chilled Water Plant CV-1 Valve Signal (HHW)" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; ph:maxVal 100 ; ph:minVal 0 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-ad87-c60b-51b4-f23c91a70cca . _:0aa7c726-ad87-c60b-51b4-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0022 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:bypass, phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo Chilled Water Plant CV-2 Valve Signal (Bypass Valve)" ; ph:dis "Bravo Chilled Water Plant CV-2 Valve Signal (Bypass Valve)" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; ph:maxVal 100 ; ph:minVal 0 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-ad87-c60c-51b5-f23c91a70cca . _:0aa7c726-ad87-c60c-51b5-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0023 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo Chilled Water Plant CV-3 Valve Signal" ; ph:dis "Bravo Chilled Water Plant CV-3 Valve Signal" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; ph:maxVal 100 ; ph:minVal 0 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-ad87-c60d-51b6-f23c91a70cca . _:0aa7c726-ad87-c60d-51b6-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0024 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo Chilled Water Plant CV-4 Valve Signal" ; ph:dis "Bravo Chilled Water Plant CV-4 Valve Signal" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; ph:maxVal 100 ; ph:minVal 0 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-ad97-0840-51b7-f23c91a70cca . _:0aa7c726-ad97-0840-51b7-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0025 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:delta, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor, phScience:water ; rdfs:label "Bravo Chilled Water Plant Chilled Water Differential Pressure" ; ph:dis "Bravo Chilled Water Plant Chilled Water Differential Pressure" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "psi" ; _:custom _:0aa7c726-ad97-0841-51b8-f23c91a70cca . _:0aa7c726-ad97-0841-51b8-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0026 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:delta, phIoT:his, phIoT:primaryLoop, phIoT:point, phScience:pressure, phIoT:sensor, phScience:water ; rdfs:label "Bravo Chilled Water Plant Chilled Water Differential Pressure Setpoint" ; ph:dis "Bravo Chilled Water Plant Chilled Water Differential Pressure Setpoint" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "psi" ; _:custom _:0aa7c726-ad97-0842-51b9-f23c91a70cca . _:0aa7c726-ad97-0842-51b9-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3397244142906628 ; _:sourcePointName "ChwDifSP" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0027 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:entering, phIoT:his, phIoT:primaryLoop, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chilled Water Plant Chilled Water Entering Temperature" ; ph:dis "Bravo Chilled Water Plant Chilled Water Entering Temperature" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ad97-0843-51ba-f23c91a70cca . _:0aa7c726-ad97-0843-51ba-f23c91a70cca rdfs:label "" ; _:predictionConf 0.787900067809321 ; _:sourcePointName "CHWRTEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0028 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:primaryLoop, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chilled Water Plant Chilled Water Leaving Temperature" ; ph:dis "Bravo Chilled Water Plant Chilled Water Leaving Temperature" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ad97-0844-51bb-f23c91a70cca . _:0aa7c726-ad97-0844-51bb-f23c91a70cca rdfs:label "" ; _:predictionConf 0.787900067809321 ; _:sourcePointName "ChwsTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0029 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo Chilled Water Plant Chilled Water dT (Auto-computed)" ; ph:dis "Bravo Chilled Water Plant Chilled Water dT (Auto-computed)" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ad97-0845-51bc-f23c91a70cca . _:0aa7c726-ad97-0845-51bc-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-002a a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Chilled Water Plant Chiller Status" ; ph:dis "Bravo Chilled Water Plant Chiller Status" ; phIoT:equipRef _:b-001e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ad97-0846-51bd-f23c91a70cca . _:0aa7c726-ad97-0846-51bd-f23c91a70cca rdfs:label "" ; _:predictionConf 0.15013386549340826 ; _:sourcePointName "RunSTATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-002b a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo Chilled Water Plant Efficiency (Auto-computed)" ; ph:dis "Bravo Chilled Water Plant Efficiency (Auto-computed)" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "kW/ton" ; _:custom _:0aa7c726-ad97-0847-51be-f23c91a70cca . _:0aa7c726-ad97-0847-51be-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-002c a phIoT:chiller ; ph:hasTag phIoT:airCooling, phIoT:chiller, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Chiller 1" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo Chiller 1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; _:custom _:0aa7c726-ad97-0848-51bf-f23c91a70cca . _:0aa7c726-ad97-0848-51bf-f23c91a70cca rdfs:label "" ; _:designElecPower 180 ; _:designEfficiency 10.6 ; _:designSource "Drawings" ; _:designChilledWaterPower 160 ; _:designChilledWaterLeavingTemp 44 ; _:designMake "Mcquay" ; _:designChilledWaterEnteringTemp 58 ; _:designChilledWaterDeltaPressure 18.61 ; _:designModel "AGS-160C" ; _:designChilledWaterFlow 275 . _:b-002d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:entering, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 1 Chilled Water Entering Temperature" ; ph:dis "Bravo Chiller 1 Chilled Water Entering Temperature" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ad97-0849-51c0-f23c91a70cca . _:0aa7c726-ad97-0849-51c0-f23c91a70cca rdfs:label "" ; _:predictionConf 0.38428817764444545 ; _:sourcePointName "CH1_EntChwTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-002e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 1 Chilled Water Leaving Temperature" ; ph:dis "Bravo Chiller 1 Chilled Water Leaving Temperature" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ad97-084a-51c1-f23c91a70cca . _:0aa7c726-ad97-084a-51c1-f23c91a70cca rdfs:label "" ; _:predictionConf 0.34916172794461753 ; _:sourcePointName "CH1_LeavChwTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-002f a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo Chiller 1 Chilled Water dT (Auto-computed)" ; ph:dis "Bravo Chiller 1 Chilled Water dT (Auto-computed)" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ad97-084b-51c2-f23c91a70cca . _:0aa7c726-ad97-084b-51c2-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0030 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:chiller, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sp, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 1 Chiller 1 Setpoint" ; ph:dis "Bravo Chiller 1 Chiller 1 Setpoint" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ad97-084c-51c3-f23c91a70cca . _:0aa7c726-ad97-084c-51c3-f23c91a70cca rdfs:label "" ; _:predictionConf 0.42372423437084655 ; _:sourcePointName "CH1_CHW_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0031 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo Chiller 1 Chiller Act. Capacity" ; ph:dis "Bravo Chiller 1 Chiller Act. Capacity" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-ad97-084d-51c4-f23c91a70cca . _:0aa7c726-ad97-084d-51c4-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0032 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cmd, phIoT:cur, phIoT:his, phIoT:point, phIoT:run ; rdfs:label "Bravo Chiller 1 Chiller Enable" ; ph:dis "Bravo Chiller 1 Chiller Enable" ; phIoT:equipRef _:b-002c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ad97-084e-51c5-f23c91a70cca . _:0aa7c726-ad97-084e-51c5-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2769995097894551 ; _:sourcePointName "CH1_Clr1Cmd" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0033 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Chiller 1 Chiller Status" ; ph:dis "Bravo Chiller 1 Chiller Status" ; phIoT:equipRef _:b-002c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ad97-084f-51c6-f23c91a70cca . _:0aa7c726-ad97-084f-51c6-f23c91a70cca rdfs:label "" ; _:predictionConf 0.33026119584467384 ; _:sourcePointName "CH1_ChlrSts" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0034 a phIoT:chiller ; ph:hasTag phIoT:airCooling, phIoT:chiller, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Chiller 2" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo Chiller 2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; _:custom _:0aa7c726-ada6-4a80-51c7-f23c91a70cca . _:0aa7c726-ada6-4a80-51c7-f23c91a70cca rdfs:label "" ; _:designElecPower 180 ; _:designEfficiency 10.6 ; _:designSource "Drawings" ; _:designChilledWaterPower 160 ; _:designChilledWaterLeavingTemp 44 ; _:designMake "Mcquay" ; _:designChilledWaterEnteringTemp 58 ; _:designChilledWaterDeltaPressure 18.61 ; _:designModel "AGS-160C" ; _:designChilledWaterFlow 275 . _:b-0035 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:entering, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 2 Chilled Water Entering Temperature" ; ph:dis "Bravo Chiller 2 Chilled Water Entering Temperature" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ada6-4a81-51c8-f23c91a70cca . _:0aa7c726-ada6-4a81-51c8-f23c91a70cca rdfs:label "" ; _:predictionConf 0.38428817764444545 ; _:sourcePointName "CH2_EntChwTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0036 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 2 Chilled Water Leaving Temperature" ; ph:dis "Bravo Chiller 2 Chilled Water Leaving Temperature" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ada6-4a82-51c9-f23c91a70cca . _:0aa7c726-ada6-4a82-51c9-f23c91a70cca rdfs:label "" ; _:predictionConf 0.34916172794461753 ; _:sourcePointName "CH2_LeavChwTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0037 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo Chiller 2 Chilled Water dT (Auto-computed)" ; ph:dis "Bravo Chiller 2 Chilled Water dT (Auto-computed)" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ada6-4a83-51ca-f23c91a70cca . _:0aa7c726-ada6-4a83-51ca-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0038 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:chiller, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sp, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 2 Chiller 2 Setpoint" ; ph:dis "Bravo Chiller 2 Chiller 2 Setpoint" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-ada6-4a84-51cb-f23c91a70cca . _:0aa7c726-ada6-4a84-51cb-f23c91a70cca rdfs:label "" ; _:predictionConf 0.42372423437084655 ; _:sourcePointName "CH2_CHW_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0039 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo Chiller 2 Chiller Act. Capacity" ; ph:dis "Bravo Chiller 2 Chiller Act. Capacity" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-ada6-4a85-51cc-f23c91a70cca . _:0aa7c726-ada6-4a85-51cc-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-003a a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cmd, phIoT:cur, phIoT:his, phIoT:point, phIoT:run ; rdfs:label "Bravo Chiller 2 Chiller Enable" ; ph:dis "Bravo Chiller 2 Chiller Enable" ; phIoT:equipRef _:b-0034 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ada6-4a86-51cd-f23c91a70cca . _:0aa7c726-ada6-4a86-51cd-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2769995097894551 ; _:sourcePointName "CH2_Clr1Cmd" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-003b a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Chiller 2 Chiller Status" ; ph:dis "Bravo Chiller 2 Chiller Status" ; phIoT:equipRef _:b-0034 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ada6-4a87-51ce-f23c91a70cca . _:0aa7c726-ada6-4a87-51ce-f23c91a70cca rdfs:label "" ; _:predictionConf 0.33026119584467384 ; _:sourcePointName "CH2_ChlrSts" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-003c a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-1" ; ph:dis "Bravo EF-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-003d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-1 Exhaust Fan Enable" ; ph:dis "Bravo EF-1 Exhaust Fan Enable" ; phIoT:equipRef _:b-003c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ada6-4a88-51cf-f23c91a70cca . _:0aa7c726-ada6-4a88-51cf-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-003e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-1 Exhaust Fan Status" ; ph:dis "Bravo EF-1 Exhaust Fan Status" ; phIoT:equipRef _:b-003c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae11-1a40-51d0-f23c91a70cca . _:0aa7c726-ae11-1a40-51d0-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" ; _:pointType "" . _:b-003f a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-10" ; ph:dis "Bravo EF-10" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0040 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-10 Exhaust Fan Enable" ; ph:dis "Bravo EF-10 Exhaust Fan Enable" ; phIoT:equipRef _:b-003f ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae11-1a41-51d1-f23c91a70cca . _:0aa7c726-ae11-1a41-51d1-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0041 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-10 Exhaust Fan Status" ; ph:dis "Bravo EF-10 Exhaust Fan Status" ; phIoT:equipRef _:b-003f ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae11-1a42-51d2-f23c91a70cca . _:0aa7c726-ae11-1a42-51d2-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-06-23T01:00:04.326-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0042 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-11" ; ph:dis "Bravo EF-11" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0043 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-11 Exhaust Fan Enable" ; ph:dis "Bravo EF-11 Exhaust Fan Enable" ; phIoT:equipRef _:b-0042 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae11-1a43-51d3-f23c91a70cca . _:0aa7c726-ae11-1a43-51d3-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0044 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-11 Exhaust Fan Status" ; ph:dis "Bravo EF-11 Exhaust Fan Status" ; phIoT:equipRef _:b-0042 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae11-1a44-51d4-f23c91a70cca . _:0aa7c726-ae11-1a44-51d4-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0045 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-12" ; ph:dis "Bravo EF-12" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0046 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-12 Exhaust Fan Enable" ; ph:dis "Bravo EF-12 Exhaust Fan Enable" ; phIoT:equipRef _:b-0045 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae11-1a45-51d5-f23c91a70cca . _:0aa7c726-ae11-1a45-51d5-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0047 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-12 Exhaust Fan Status" ; ph:dis "Bravo EF-12 Exhaust Fan Status" ; phIoT:equipRef _:b-0045 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae11-1a46-51d6-f23c91a70cca . _:0aa7c726-ae11-1a46-51d6-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0048 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-13" ; ph:dis "Bravo EF-13" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0049 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-13 Exhaust Fan Enable" ; ph:dis "Bravo EF-13 Exhaust Fan Enable" ; phIoT:equipRef _:b-0048 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae11-1a47-51d7-f23c91a70cca . _:0aa7c726-ae11-1a47-51d7-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-004a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-13 Exhaust Fan Status" ; ph:dis "Bravo EF-13 Exhaust Fan Status" ; phIoT:equipRef _:b-0048 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae11-1a48-51d8-f23c91a70cca . _:0aa7c726-ae11-1a48-51d8-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-004b a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-14" ; ph:dis "Bravo EF-14" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-004c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-14 Exhaust Fan Enable" ; ph:dis "Bravo EF-14 Exhaust Fan Enable" ; phIoT:equipRef _:b-004b ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae11-1a49-51d9-f23c91a70cca . _:0aa7c726-ae11-1a49-51d9-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-004d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-14 Exhaust Fan Status" ; ph:dis "Bravo EF-14 Exhaust Fan Status" ; phIoT:equipRef _:b-004b ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae20-5c80-51da-f23c91a70cca . _:0aa7c726-ae20-5c80-51da-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-004e a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-15" ; ph:dis "Bravo EF-15" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-004f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-15 Exhaust Fan Enable" ; ph:dis "Bravo EF-15 Exhaust Fan Enable" ; phIoT:equipRef _:b-004e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae20-5c81-51db-f23c91a70cca . _:0aa7c726-ae20-5c81-51db-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0050 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-15 Exhaust Fan Status" ; ph:dis "Bravo EF-15 Exhaust Fan Status" ; phIoT:equipRef _:b-004e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae20-5c82-51dc-f23c91a70cca . _:0aa7c726-ae20-5c82-51dc-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0051 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-16" ; ph:dis "Bravo EF-16" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0052 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-16 Exhaust Fan Enable" ; ph:dis "Bravo EF-16 Exhaust Fan Enable" ; phIoT:equipRef _:b-0051 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae20-5c83-51dd-f23c91a70cca . _:0aa7c726-ae20-5c83-51dd-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0053 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-16 Exhaust Fan Status" ; ph:dis "Bravo EF-16 Exhaust Fan Status" ; phIoT:equipRef _:b-0051 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae20-5c84-51de-f23c91a70cca . _:0aa7c726-ae20-5c84-51de-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0054 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-17" ; ph:dis "Bravo EF-17" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0055 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-17 Exhaust Fan Enable" ; ph:dis "Bravo EF-17 Exhaust Fan Enable" ; phIoT:equipRef _:b-0054 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae20-5c85-51df-f23c91a70cca . _:0aa7c726-ae20-5c85-51df-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0056 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-17 Exhaust Fan Status" ; ph:dis "Bravo EF-17 Exhaust Fan Status" ; phIoT:equipRef _:b-0054 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae20-5c86-51e0-f23c91a70cca . _:0aa7c726-ae20-5c86-51e0-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0057 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-18" ; ph:dis "Bravo EF-18" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0058 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-18 Exhaust Fan Enable" ; ph:dis "Bravo EF-18 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-0057 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae20-5c87-51e1-f23c91a70cca . _:0aa7c726-ae20-5c87-51e1-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0059 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-18 Exhaust Fan Status" ; ph:dis "Bravo EF-18 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-0057 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae20-5c88-51e2-f23c91a70cca . _:0aa7c726-ae20-5c88-51e2-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-005a a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-19" ; ph:dis "Bravo EF-19" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-005b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-19 Exhaust Fan Enable" ; ph:dis "Bravo EF-19 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-005a ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae20-5c89-51e3-f23c91a70cca . _:0aa7c726-ae20-5c89-51e3-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-005c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-19 Exhaust Fan Status" ; ph:dis "Bravo EF-19 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-005a ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae20-5c8a-51e4-f23c91a70cca . _:0aa7c726-ae20-5c8a-51e4-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-005d a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-2" ; ph:dis "Bravo EF-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-005e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-2 Exhaust Fan Enable" ; ph:dis "Bravo EF-2 Exhaust Fan Enable" ; phIoT:equipRef _:b-005d ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae20-5c8b-51e5-f23c91a70cca . _:0aa7c726-ae20-5c8b-51e5-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-005f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-2 Exhaust Fan Status" ; ph:dis "Bravo EF-2 Exhaust Fan Status" ; phIoT:equipRef _:b-005d ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae20-5c8c-51e6-f23c91a70cca . _:0aa7c726-ae20-5c8c-51e6-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0060 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-20" ; ph:dis "Bravo EF-20" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0061 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-20 Exhaust Fan Enable" ; ph:dis "Bravo EF-20 Exhaust Fan Enable" ; phIoT:equipRef _:b-0060 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ec0-51e7-f23c91a70cca . _:0aa7c726-ae2f-9ec0-51e7-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0062 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-20 Exhaust Fan Status" ; ph:dis "Bravo EF-20 Exhaust Fan Status" ; phIoT:equipRef _:b-0060 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ec1-51e8-f23c91a70cca . _:0aa7c726-ae2f-9ec1-51e8-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0063 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-21" ; ph:dis "Bravo EF-21" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0064 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-21 Exhaust Fan Enable" ; ph:dis "Bravo EF-21 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-0063 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ec2-51e9-f23c91a70cca . _:0aa7c726-ae2f-9ec2-51e9-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0065 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-21 Exhaust Fan Status" ; ph:dis "Bravo EF-21 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-0063 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ec3-51ea-f23c91a70cca . _:0aa7c726-ae2f-9ec3-51ea-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0066 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-22" ; ph:dis "Bravo EF-22" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0067 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-22 Exhaust Fan Enable" ; ph:dis "Bravo EF-22 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-0066 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ec4-51eb-f23c91a70cca . _:0aa7c726-ae2f-9ec4-51eb-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0068 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-22 Exhaust Fan Status" ; ph:dis "Bravo EF-22 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-0066 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ec5-51ec-f23c91a70cca . _:0aa7c726-ae2f-9ec5-51ec-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0069 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-23" ; ph:dis "Bravo EF-23" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-006a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-23 Exhaust Fan Enable" ; ph:dis "Bravo EF-23 Exhaust Fan Enable" ; phIoT:equipRef _:b-0069 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ec6-51ed-f23c91a70cca . _:0aa7c726-ae2f-9ec6-51ed-f23c91a70cca rdfs:label "" ; _:sourcePointName "EF23SS" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-006b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-23 Exhaust Fan Status" ; ph:dis "Bravo EF-23 Exhaust Fan Status" ; phIoT:equipRef _:b-0069 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ec7-51ee-f23c91a70cca . _:0aa7c726-ae2f-9ec7-51ee-f23c91a70cca rdfs:label "" ; _:sourcePointName "EF23Status" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-006c a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-24" ; ph:dis "Bravo EF-24" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-006d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-24 Exhaust Fan Enable" ; ph:dis "Bravo EF-24 Exhaust Fan Enable" ; phIoT:equipRef _:b-006c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ec8-51ef-f23c91a70cca . _:0aa7c726-ae2f-9ec8-51ef-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-006e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-24 Exhaust Fan Status" ; ph:dis "Bravo EF-24 Exhaust Fan Status" ; phIoT:equipRef _:b-006c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ec9-51f0-f23c91a70cca . _:0aa7c726-ae2f-9ec9-51f0-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-006f a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-25" ; ph:dis "Bravo EF-25" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0070 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-25 Exhaust Fan Enable" ; ph:dis "Bravo EF-25 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-006f ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9eca-51f1-f23c91a70cca . _:0aa7c726-ae2f-9eca-51f1-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0071 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-25 Exhaust Fan Status" ; ph:dis "Bravo EF-25 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-006f ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ecb-51f2-f23c91a70cca . _:0aa7c726-ae2f-9ecb-51f2-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0072 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-26" ; ph:dis "Bravo EF-26" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0073 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-26 Exhaust Fan Enable" ; ph:dis "Bravo EF-26 Exhaust Fan Enable" ; phIoT:equipRef _:b-0072 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ecc-51f3-f23c91a70cca . _:0aa7c726-ae2f-9ecc-51f3-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0074 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-26 Exhaust Fan Status" ; ph:dis "Bravo EF-26 Exhaust Fan Status" ; phIoT:equipRef _:b-0072 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ecd-51f4-f23c91a70cca . _:0aa7c726-ae2f-9ecd-51f4-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFStatus" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0075 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-27" ; ph:dis "Bravo EF-27" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0076 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-27 Exhaust Fan Enable" ; ph:dis "Bravo EF-27 Exhaust Fan Enable" ; phIoT:equipRef _:b-0075 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ece-51f5-f23c91a70cca . _:0aa7c726-ae2f-9ece-51f5-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0077 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-27 Exhaust Fan Status" ; ph:dis "Bravo EF-27 Exhaust Fan Status" ; phIoT:equipRef _:b-0075 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ecf-51f6-f23c91a70cca . _:0aa7c726-ae2f-9ecf-51f6-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFStatus" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0078 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-28" ; ph:dis "Bravo EF-28" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0079 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-28 Exhaust Fan Status" ; ph:dis "Bravo EF-28 Exhaust Fan Status" ; phIoT:equipRef _:b-0078 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae2f-9ed0-51f7-f23c91a70cca . _:0aa7c726-ae2f-9ed0-51f7-f23c91a70cca rdfs:label "" ; _:sourcePointName "EF28Status" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-007a a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-3" ; ph:dis "Bravo EF-3" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-007b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-3 Exhaust Fan Enable" ; ph:dis "Bravo EF-3 Exhaust Fan Enable" ; phIoT:equipRef _:b-007a ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae3e-e100-51f8-f23c91a70cca . _:0aa7c726-ae3e-e100-51f8-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-007c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-3 Exhaust Fan Status" ; ph:dis "Bravo EF-3 Exhaust Fan Status" ; phIoT:equipRef _:b-007a ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae3e-e101-51f9-f23c91a70cca . _:0aa7c726-ae3e-e101-51f9-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFStatus" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-007d a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-4" ; ph:dis "Bravo EF-4" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-007e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-4 Exhaust Fan Enable" ; ph:dis "Bravo EF-4 Exhaust Fan Enable" ; phIoT:equipRef _:b-007d ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae3e-e102-51fa-f23c91a70cca . _:0aa7c726-ae3e-e102-51fa-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-007f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-4 Exhaust Fan Status" ; ph:dis "Bravo EF-4 Exhaust Fan Status" ; phIoT:equipRef _:b-007d ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae3e-e103-51fb-f23c91a70cca . _:0aa7c726-ae3e-e103-51fb-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0080 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-5" ; ph:dis "Bravo EF-5" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0081 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-5 Exhaust Fan Enable" ; ph:dis "Bravo EF-5 Exhaust Fan Enable" ; phIoT:equipRef _:b-0080 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae3e-e104-51fc-f23c91a70cca . _:0aa7c726-ae3e-e104-51fc-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0082 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-5 Exhaust Fan Status" ; ph:dis "Bravo EF-5 Exhaust Fan Status" ; phIoT:equipRef _:b-0080 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae3e-e105-51fd-f23c91a70cca . _:0aa7c726-ae3e-e105-51fd-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0083 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-6" ; ph:dis "Bravo EF-6" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0084 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-6 Exhaust Fan Enable" ; ph:dis "Bravo EF-6 Exhaust Fan Enable" ; phIoT:equipRef _:b-0083 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae3e-e106-51fe-f23c91a70cca . _:0aa7c726-ae3e-e106-51fe-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0085 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-6 Exhaust Fan Status" ; ph:dis "Bravo EF-6 Exhaust Fan Status" ; phIoT:equipRef _:b-0083 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae3e-e107-51ff-f23c91a70cca . _:0aa7c726-ae3e-e107-51ff-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-05-28T01:00:09.102-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0086 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-7" ; ph:dis "Bravo EF-7" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0087 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-7 Exhaust Fan Enable" ; ph:dis "Bravo EF-7 Exhaust Fan Enable" ; phIoT:equipRef _:b-0086 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-ae3e-e108-5200-f23c91a70cca . _:0aa7c726-ae3e-e108-5200-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0088 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-7 Exhaust Fan Status" ; ph:dis "Bravo EF-7 Exhaust Fan Status" ; phIoT:equipRef _:b-0086 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aea9-b0c0-5201-f23c91a70cca . _:0aa7c726-aea9-b0c0-5201-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0089 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-8" ; ph:dis "Bravo EF-8" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-008a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-8 Exhaust Fan Enable" ; ph:dis "Bravo EF-8 Exhaust Fan Enable" ; phIoT:equipRef _:b-0089 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aea9-b0c1-5202-f23c91a70cca . _:0aa7c726-aea9-b0c1-5202-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-008b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-8 Exhaust Fan Status" ; ph:dis "Bravo EF-8 Exhaust Fan Status" ; phIoT:equipRef _:b-0089 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aea9-b0c2-5203-f23c91a70cca . _:0aa7c726-aea9-b0c2-5203-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-008c a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-9" ; ph:dis "Bravo EF-9" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-008d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-9 Exhaust Fan Enable" ; ph:dis "Bravo EF-9 Exhaust Fan Enable" ; phIoT:equipRef _:b-008c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aea9-b0c3-5204-f23c91a70cca . _:0aa7c726-aea9-b0c3-5204-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-008e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-9 Exhaust Fan Status" ; ph:dis "Bravo EF-9 Exhaust Fan Status" ; phIoT:equipRef _:b-008c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aea9-b0c4-5205-f23c91a70cca . _:0aa7c726-aea9-b0c4-5205-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-07-02T01:00:04.305-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" ; _:pointType "" . _:b-008f a phIoT:fcu, phIoT:thermostat ; ph:hasTag phIoT:chilledWaterCooling, phIoT:directZone, phIoT:elecHeating, phIoT:equip, phIoT:fcu, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:zone ; rdfs:label "Bravo FCU-1" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo FCU-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 . _:b-0090 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo FCU-1 Cooling Valve Output" ; ph:dis "Bravo FCU-1 Cooling Valve Output" ; phIoT:equipRef _:b-008f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aea9-b0c5-5206-f23c91a70cca . _:0aa7c726-aea9-b0c5-5206-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlv" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0091 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heat, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve ; rdfs:label "Bravo FCU-1 Heating Valve Output" ; ph:dis "Bravo FCU-1 Heating Valve Output" ; phIoT:equipRef _:b-008f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aea9-b0c6-5207-f23c91a70cca . _:0aa7c726-aea9-b0c6-5207-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0092 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-1 Zone Temperature" ; ph:dis "Bravo FCU-1 Zone Temperature" ; phIoT:equipRef _:b-008f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aea9-b0c7-5208-f23c91a70cca . _:0aa7c726-aea9-b0c7-5208-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpcTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0093 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-1 Zone Temperature Setpoint" ; ph:dis "Bravo FCU-1 Zone Temperature Setpoint" ; phIoT:equipRef _:b-008f ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aea9-b0c8-5209-f23c91a70cca . _:0aa7c726-aea9-b0c8-5209-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0094 a phIoT:fcu, phIoT:thermostat ; ph:hasTag phIoT:chilledWaterCooling, phIoT:directZone, phIoT:elecHeating, phIoT:equip, phIoT:fcu, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:zone ; rdfs:label "Bravo FCU-2" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo FCU-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 . _:b-0095 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo FCU-2 Cooling Valve Output" ; ph:dis "Bravo FCU-2 Cooling Valve Output" ; phIoT:equipRef _:b-0094 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aeb8-f300-520a-f23c91a70cca . _:0aa7c726-aeb8-f300-520a-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlv" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0096 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heat, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve ; rdfs:label "Bravo FCU-2 Heating Valve Output" ; ph:dis "Bravo FCU-2 Heating Valve Output" ; phIoT:equipRef _:b-0094 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aeb8-f301-520b-f23c91a70cca . _:0aa7c726-aeb8-f301-520b-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0097 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-2 Zone Temperature" ; ph:dis "Bravo FCU-2 Zone Temperature" ; phIoT:equipRef _:b-0094 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aeb8-f302-520c-f23c91a70cca . _:0aa7c726-aeb8-f302-520c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpcTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0098 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-2 Zone Temperature Setpoint" ; ph:dis "Bravo FCU-2 Zone Temperature Setpoint" ; phIoT:equipRef _:b-0094 ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aeb8-f303-520d-f23c91a70cca . _:0aa7c726-aeb8-f303-520d-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0099 a phIoT:fcu, phIoT:thermostat ; ph:hasTag phIoT:chilledWaterCooling, phIoT:directZone, phIoT:elecHeating, phIoT:equip, phIoT:fcu, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:zone ; rdfs:label "Bravo FCU-3" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo FCU-3" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 . _:b-009a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo FCU-3 Cooling Valve Output" ; ph:dis "Bravo FCU-3 Cooling Valve Output" ; phIoT:equipRef _:b-0099 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aeb8-f304-520e-f23c91a70cca . _:0aa7c726-aeb8-f304-520e-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlv" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-009b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heat, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve ; rdfs:label "Bravo FCU-3 Heating Valve Output" ; ph:dis "Bravo FCU-3 Heating Valve Output" ; phIoT:equipRef _:b-0099 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aeb8-f305-520f-f23c91a70cca . _:0aa7c726-aeb8-f305-520f-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-009c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-3 Zone Temperature" ; ph:dis "Bravo FCU-3 Zone Temperature" ; phIoT:equipRef _:b-0099 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aeb8-f306-5210-f23c91a70cca . _:0aa7c726-aeb8-f306-5210-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpcTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-009d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-3 Zone Temperature Setpoint" ; ph:dis "Bravo FCU-3 Zone Temperature Setpoint" ; phIoT:equipRef _:b-0099 ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aeb8-f307-5211-f23c91a70cca . _:0aa7c726-aeb8-f307-5211-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-009e a phIoT:fcu, phIoT:thermostat ; ph:hasTag phIoT:chilledWaterCooling, phIoT:directZone, phIoT:elecHeating, phIoT:equip, phIoT:fcu, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:zone ; rdfs:label "Bravo FCU-4" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo FCU-4" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 . _:b-009f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo FCU-4 Cooling Valve Output" ; ph:dis "Bravo FCU-4 Cooling Valve Output" ; phIoT:equipRef _:b-009e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aeb8-f308-5212-f23c91a70cca . _:0aa7c726-aeb8-f308-5212-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlv" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00a0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heat, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve ; rdfs:label "Bravo FCU-4 Heating Valve Output" ; ph:dis "Bravo FCU-4 Heating Valve Output" ; phIoT:equipRef _:b-009e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aeb8-f309-5213-f23c91a70cca . _:0aa7c726-aeb8-f309-5213-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00a1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-4 Zone Temperature" ; ph:dis "Bravo FCU-4 Zone Temperature" ; phIoT:equipRef _:b-009e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aeb8-f30a-5214-f23c91a70cca . _:0aa7c726-aeb8-f30a-5214-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpcTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00a2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-4 Zone Temperature Setpoint" ; ph:dis "Bravo FCU-4 Zone Temperature Setpoint" ; phIoT:equipRef _:b-009e ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aeb8-f30b-5215-f23c91a70cca . _:0aa7c726-aeb8-f30b-5215-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00a3 a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo FCUs" ; ph:dis "Bravo FCUs" ; phIoT:siteRef _:b-0000 ; _:custom _:0aa7c726-aeb8-f30c-5216-f23c91a70cca . _:0aa7c726-aeb8-f30c-5216-f23c91a70cca rdfs:label "" . _:b-00a4 a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo Fans" ; ph:dis "Bravo Fans" ; phIoT:siteRef _:b-0000 ; _:custom _:0aa7c726-aeb8-f30d-5217-f23c91a70cca . _:0aa7c726-aeb8-f30d-5217-f23c91a70cca rdfs:label "" . _:b-00a5 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:hot, phIoT:hvac, phIoT:pump, phScience:water ; rdfs:label "Bravo HHW Pump 1" ; ph:dis "Bravo HHW Pump 1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab . _:b-00a6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:pump, phIoT:sensor, phScience:water ; rdfs:label "Bravo HHW Pump 1 HHW Pump Status" ; ph:dis "Bravo HHW Pump 1 HHW Pump Status" ; ph:enum "false,true" ; phIoT:equipRef _:b-00a5 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0aa7c726-aeb8-f30e-5218-f23c91a70cca . _:0aa7c726-aeb8-f30e-5218-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-00a7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:pump, phIoT:sensor, phScience:speed, phScience:water ; rdfs:label "Bravo HHW Pump 1 HHW Pump VFD Speed" ; ph:dis "Bravo HHW Pump 1 HHW Pump VFD Speed" ; phIoT:equipRef _:b-00a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0aa7c726-aeb8-f30f-5219-f23c91a70cca . _:0aa7c726-aeb8-f30f-5219-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-00a8 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:hot, phIoT:hvac, phIoT:pump, phScience:water ; rdfs:label "Bravo HHW Pump 2" ; ph:dis "Bravo HHW Pump 2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab . _:b-00a9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:pump, phIoT:sensor, phScience:water ; rdfs:label "Bravo HHW Pump 2 HHW Pump Status" ; ph:dis "Bravo HHW Pump 2 HHW Pump Status" ; ph:enum "false,true" ; phIoT:equipRef _:b-00a8 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0aa7c726-aeb8-f310-521a-f23c91a70cca . _:0aa7c726-aeb8-f310-521a-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00aa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:pump, phIoT:sensor, phScience:speed, phScience:water ; rdfs:label "Bravo HHW Pump 2 HHW Pump VFD Speed" ; ph:dis "Bravo HHW Pump 2 HHW Pump VFD Speed" ; phIoT:equipRef _:b-00a8 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0aa7c726-aec8-3540-521b-f23c91a70cca . _:0aa7c726-aec8-3540-521b-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00ab a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo HW System" ; ph:dis "Bravo HW System" ; phIoT:siteRef _:b-0000 ; _:custom _:0aa7c726-aec8-3541-521c-f23c91a70cca . _:0aa7c726-aec8-3541-521c-f23c91a70cca rdfs:label "" . _:b-00ac a phIoT:rtu ; ph:hasTag phIoT:ahu, phIoT:chilledWaterCooling, phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:rtu, phIoT:singleDuct, phIoT:vavZone ; rdfs:label "Bravo RTU-1" ; ph:dis "Bravo RTU-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; _:custom _:0aa7c726-aec8-3542-521d-f23c91a70cca . _:0aa7c726-aec8-3542-521d-f23c91a70cca rdfs:label "" ; _:designDischargeAirFlow 15300 ; _:designHotWaterLeavingTemp 65 ; _:designHotWaterPower 145 ; _:designOutsideAirFlowMin 3500 ; _:designDischargeFanAirDeltaPressure 7.04 ; _:designSource "Drawings" ; _:designChilledWaterLeavingTemp 59 ; _:designChilledWaterPower 722.3 ; _:designHotWaterFlow 24.1 ; _:designChilledWaterFlow 96.4 ; _:designReturnAirFlow 15300 ; _:designHotWaterEnteringTemp 75 ; _:designOutsideAirFlow 15300 ; _:designReturnFanPower 15 ; _:designChilledWaterEnteringTemp 44 ; _:designDischargeFanPower 40 ; _:designReturnFanAirDeltaPressure 1.66 . _:b-00ad a phIoT:his-point ; ph:hasTag ph:computed, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 AHU Operation Mode" ; ph:dis "Bravo RTU-1 AHU Operation Mode" ; phIoT:equipRef _:b-00ac ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aec8-3543-521e-f23c91a70cca . _:0aa7c726-aec8-3543-521e-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00ae a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cmd, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo RTU-1 Cooling Valve Output" ; ph:dis "Bravo RTU-1 Cooling Valve Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aec8-3544-521f-f23c91a70cca . _:0aa7c726-aec8-3544-521f-f23c91a70cca rdfs:label "" ; _:sourcePointName "CWV" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-00af a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:exhaust, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Exhaust Air Damper Output" ; ph:dis "Bravo RTU-1 Exhaust Air Damper Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aec8-3545-5220-f23c91a70cca . _:0aa7c726-aec8-3545-5220-f23c91a70cca rdfs:label "" ; _:sourcePointName "EAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00b0 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Fan Power (Auto-computed)" ; ph:dis "Bravo RTU-1 Fan Power (Auto-computed)" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aec8-3546-5221-f23c91a70cca . _:0aa7c726-aec8-3546-5221-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00b1 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Heating/Cooling Load (Auto-computed)" ; ph:dis "Bravo RTU-1 Heating/Cooling Load (Auto-computed)" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "BTU/h" ; _:custom _:0aa7c726-aec8-3547-5222-f23c91a70cca . _:0aa7c726-aec8-3547-5222-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00b2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:his, phIoT:humidifier, phIoT:point ; rdfs:label "Bravo RTU-1 Humidifier Enable" ; ph:dis "Bravo RTU-1 Humidifier Enable" ; phIoT:equipRef _:b-00ac ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aec8-3548-5223-f23c91a70cca . _:0aa7c726-aec8-3548-5223-f23c91a70cca rdfs:label "" ; _:sourcePointName "HUM_ENABLE" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00b3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:his, phIoT:humidifier, phIoT:point, phScience:steam, phIoT:valve ; rdfs:label "Bravo RTU-1 Humidifier Output" ; ph:dis "Bravo RTU-1 Humidifier Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aec8-3549-5224-f23c91a70cca . _:0aa7c726-aec8-3549-5224-f23c91a70cca rdfs:label "" ; _:sourcePointName "HUM VLV" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-00b4 a phIoT:his-point ; ph:hasTag phIoT:cmd, ph:computed, phIoT:damper, phIoT:his, phIoT:point ; rdfs:label "Bravo RTU-1 Max Damper Position" ; ph:dis "Bravo RTU-1 Max Damper Position" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aec8-354a-5225-f23c91a70cca . _:0aa7c726-aec8-354a-5225-f23c91a70cca ph:hasTag ph:max ; rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00b5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Min Outdoor Air Flow Setpoint" ; ph:dis "Bravo RTU-1 Min Outdoor Air Flow Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aec8-354b-5226-f23c91a70cca . _:0aa7c726-aec8-354b-5226-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:sourcePointName "MinOA_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime ; _:pointType "" . _:b-00b6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Min Outdoor Air Flow/10" ; ph:dis "Bravo RTU-1 Min Outdoor Air Flow/10" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-aec8-354c-5227-f23c91a70cca . _:0aa7c726-aec8-354c-5227-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:sourcePointName "MIN OA CFM / 10" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00b7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Minimum Outside Air Damper Output" ; ph:dis "Bravo RTU-1 Minimum Outside Air Damper Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aec8-354d-5228-f23c91a70cca . _:0aa7c726-aec8-354d-5228-f23c91a70cca rdfs:label "" ; _:sourcePointName "Min OAD" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-00b8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-1 Mixed Air Temperature" ; ph:dis "Bravo RTU-1 Mixed Air Temperature" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aec8-354e-5229-f23c91a70cca . _:0aa7c726-aec8-354e-5229-f23c91a70cca rdfs:label "" ; _:sourcePointName "MAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00b9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-1 Mixed Air Temperature Setpoint" ; ph:dis "Bravo RTU-1 Mixed Air Temperature Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aec8-354f-522a-f23c91a70cca . _:0aa7c726-aec8-354f-522a-f23c91a70cca rdfs:label "" ; _:sourcePointName "MAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00ba a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:outside, phIoT:point ; rdfs:label "Bravo RTU-1 Outside Air Damper Output" ; ph:dis "Bravo RTU-1 Outside Air Damper Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aec8-3550-522b-f23c91a70cca . _:0aa7c726-aec8-3550-522b-f23c91a70cca rdfs:label "" ; _:sourcePointName "OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-00bb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Outside Air Flow" ; ph:dis "Bravo RTU-1 Outside Air Flow" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-aec8-3551-522c-f23c91a70cca . _:0aa7c726-aec8-3551-522c-f23c91a70cca rdfs:label "" ; _:sourcePointName "OA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00bc a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Outside Air Percentage (Auto-computed)" ; ph:dis "Bravo RTU-1 Outside Air Percentage (Auto-computed)" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aec8-3552-522d-f23c91a70cca . _:0aa7c726-aec8-3552-522d-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.656-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00bd a phIoT:his-point ; ph:hasTag phScience:air, ph:computed, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-1 Percent Outside Air" ; ph:dis "Bravo RTU-1 Percent Outside Air" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aec8-3553-522e-f23c91a70cca . _:0aa7c726-aec8-3553-522e-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00be a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-1 Return Air Damper Output" ; ph:dis "Bravo RTU-1 Return Air Damper Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aed7-7780-522f-f23c91a70cca . _:0aa7c726-aed7-7780-522f-f23c91a70cca rdfs:label "" ; _:sourcePointName "RET/REL DAMPER" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-00bf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-1 Return Air Flow" ; ph:dis "Bravo RTU-1 Return Air Flow" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-aed7-7781-5230-f23c91a70cca . _:0aa7c726-aed7-7781-5230-f23c91a70cca rdfs:label "" ; _:sourcePointName "RA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00c0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-1 Return Air Humidity" ; ph:dis "Bravo RTU-1 Return Air Humidity" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aed7-7782-5231-f23c91a70cca . _:0aa7c726-aed7-7782-5231-f23c91a70cca rdfs:label "" ; _:sourcePointName "RAH" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-00c1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-1 Return Air Temperature" ; ph:dis "Bravo RTU-1 Return Air Temperature" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aed7-7783-5232-f23c91a70cca . _:0aa7c726-aed7-7783-5232-f23c91a70cca rdfs:label "" ; _:sourcePointName "RAT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-00c2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-1 Return Fan Status" ; ph:dis "Bravo RTU-1 Return Fan Status" ; phIoT:equipRef _:b-00ac ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aed7-7784-5233-f23c91a70cca . _:0aa7c726-aed7-7784-5233-f23c91a70cca rdfs:label "" ; _:sourcePointName "RF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-00c3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-1 Return Fan VFD Speed" ; ph:dis "Bravo RTU-1 Return Fan VFD Speed" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aed7-7785-5234-f23c91a70cca . _:0aa7c726-aed7-7785-5234-f23c91a70cca rdfs:label "" ; _:sourcePointName "ACT_OUTPUT_SPEED" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-00c4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Supply Air Flow" ; ph:dis "Bravo RTU-1 Supply Air Flow" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-aed7-7786-5235-f23c91a70cca . _:0aa7c726-aed7-7786-5235-f23c91a70cca rdfs:label "" ; _:sourcePointName "SA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00c5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Supply Air Humidity" ; ph:dis "Bravo RTU-1 Supply Air Humidity" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aed7-7787-5236-f23c91a70cca . _:0aa7c726-aed7-7787-5236-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAH" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-00c6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Supply Air Humidity Setpoint" ; ph:dis "Bravo RTU-1 Supply Air Humidity Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:pointFunction phIoT:sp ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aed7-7788-5237-f23c91a70cca . _:0aa7c726-aed7-7788-5237-f23c91a70cca rdfs:label "" ; _:sourcePointName "Humidity SP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00c7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sp ; rdfs:label "Bravo RTU-1 Supply Air Pressure Setpoint" ; ph:dis "Bravo RTU-1 Supply Air Pressure Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0aa7c726-aed7-7789-5238-f23c91a70cca . _:0aa7c726-aed7-7789-5238-f23c91a70cca rdfs:label "" ; _:sourcePointName "Static Stpt" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-00c8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor ; rdfs:label "Bravo RTU-1 Supply Air Static Pressure" ; ph:dis "Bravo RTU-1 Supply Air Static Pressure" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0aa7c726-aed7-778a-5239-f23c91a70cca . _:0aa7c726-aed7-778a-5239-f23c91a70cca rdfs:label "" ; _:sourcePointName "DISCH STATIC" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-00c9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-1 Supply Air Temperature" ; ph:dis "Bravo RTU-1 Supply Air Temperature" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aed7-778b-523a-f23c91a70cca . _:0aa7c726-aed7-778b-523a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00ca a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-1 Supply Air Temperature Setpoint" ; ph:dis "Bravo RTU-1 Supply Air Temperature Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aed7-778c-523b-f23c91a70cca . _:0aa7c726-aed7-778c-523b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-00cb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-1 Supply Fan Status" ; ph:dis "Bravo RTU-1 Supply Fan Status" ; phIoT:equipRef _:b-00ac ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aed7-778d-523c-f23c91a70cca . _:0aa7c726-aed7-778d-523c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00cc a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 TU Air Flow (Auto-computed)" ; ph:dis "Bravo RTU-1 TU Air Flow (Auto-computed)" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-aed7-778e-523d-f23c91a70cca . _:0aa7c726-aed7-778e-523d-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00cd a phIoT:his-point ; ph:hasTag phScience:air, ph:computed, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 VAV Total Flow" ; ph:dis "Bravo RTU-1 VAV Total Flow" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-aed7-778f-523e-f23c91a70cca . _:0aa7c726-aed7-778f-523e-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00ce a phIoT:rtu ; ph:hasTag phIoT:ahu, phIoT:chilledWaterCooling, phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:rtu, phIoT:singleDuct, phIoT:vavZone ; rdfs:label "Bravo RTU-2" ; ph:dis "Bravo RTU-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; _:custom _:0aa7c726-aed7-7790-523f-f23c91a70cca . _:0aa7c726-aed7-7790-523f-f23c91a70cca rdfs:label "" ; _:designDischargeAirFlow 30000 ; _:designHotWaterLeavingTemp 65 ; _:designHotWaterPower 288 ; _:designOutsideAirFlowMin 6750 ; _:designDischargeFanAirDeltaPressure 6.4 ; _:designSource "Drawings" ; _:designChilledWaterLeavingTemp 59.2 ; _:designChilledWaterPower 1225.8 ; _:designHotWaterFlow 48 ; _:designChilledWaterFlow 160.9 ; _:designReturnAirFlow 30000 ; _:designHotWaterEnteringTemp 75 ; _:designOutsideAirFlow 30000 ; _:designReturnFanPower 25 ; _:designChilledWaterEnteringTemp 44 ; _:designDischargeFanPower 50 ; _:designReturnFanAirDeltaPressure 1.62 . _:b-00cf a phIoT:his-point ; ph:hasTag ph:computed, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 AHU Operation Mode" ; ph:dis "Bravo RTU-2 AHU Operation Mode" ; phIoT:equipRef _:b-00ce ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aed7-7791-5240-f23c91a70cca . _:0aa7c726-aed7-7791-5240-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00d0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Calculated Outdoor Air Flow Setpoint" ; ph:dis "Bravo RTU-2 Calculated Outdoor Air Flow Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aee6-b9c0-5241-f23c91a70cca . _:0aa7c726-aee6-b9c0-5241-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3970116854281743 ; _:sourcePointName "MinOA_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00d1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cmd, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo RTU-2 Cooling Valve Output" ; ph:dis "Bravo RTU-2 Cooling Valve Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aee6-b9c1-5242-f23c91a70cca . _:0aa7c726-aee6-b9c1-5242-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5846394026860828 ; _:sourcePointName "CWV" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-00d2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:exhaust, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Exhaust Air Damper Output" ; ph:dis "Bravo RTU-2 Exhaust Air Damper Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aee6-b9c2-5243-f23c91a70cca . _:0aa7c726-aee6-b9c2-5243-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6232903565384572 ; _:sourcePointName "EAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00d3 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Fan Power (Auto-computed)" ; ph:dis "Bravo RTU-2 Fan Power (Auto-computed)" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aee6-b9c3-5244-f23c91a70cca . _:0aa7c726-aee6-b9c3-5244-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00d4 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Heating/Cooling Load (Auto-computed)" ; ph:dis "Bravo RTU-2 Heating/Cooling Load (Auto-computed)" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "BTU/h" ; _:custom _:0aa7c726-aee6-b9c4-5245-f23c91a70cca . _:0aa7c726-aee6-b9c4-5245-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00d5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:his, phIoT:humidifier, phIoT:point ; rdfs:label "Bravo RTU-2 Humidifier Enable" ; ph:dis "Bravo RTU-2 Humidifier Enable" ; phIoT:equipRef _:b-00ce ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aee6-b9c5-5246-f23c91a70cca . _:0aa7c726-aee6-b9c5-5246-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2169429859073283 ; _:sourcePointName "HUM_ENABLE" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00d6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:his, phIoT:humidifier, phIoT:point, phScience:steam, phIoT:valve ; rdfs:label "Bravo RTU-2 Humidifier Output" ; ph:dis "Bravo RTU-2 Humidifier Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aee6-b9c6-5247-f23c91a70cca . _:0aa7c726-aee6-b9c6-5247-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7439557600414519 ; _:sourcePointName "HUM VLV" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00d7 a phIoT:his-point ; ph:hasTag phIoT:cmd, ph:computed, phIoT:damper, phIoT:his, phIoT:point ; rdfs:label "Bravo RTU-2 Max Damper Position" ; ph:dis "Bravo RTU-2 Max Damper Position" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aee6-b9c7-5248-f23c91a70cca . _:0aa7c726-aee6-b9c7-5248-f23c91a70cca ph:hasTag ph:max ; rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00d8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Min OA Flow Setpoint" ; ph:dis "Bravo RTU-2 Min OA Flow Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-aee6-b9c8-5249-f23c91a70cca . _:0aa7c726-aee6-b9c8-5249-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2305698711556413 ; _:sourcePointName "MINOASTPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00d9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Min Outdoor Air Flow" ; ph:dis "Bravo RTU-2 Min Outdoor Air Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-aee6-b9c9-524a-f23c91a70cca . _:0aa7c726-aee6-b9c9-524a-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:predictionConf 0.5591032698291575 ; _:sourcePointName "MIN OA CFM / 10" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-00da a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Minimum Outside Air Damper Output" ; ph:dis "Bravo RTU-2 Minimum Outside Air Damper Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aee6-b9ca-524b-f23c91a70cca . _:0aa7c726-aee6-b9ca-524b-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7226466689139898 ; _:sourcePointName "Min OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-00db a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-2 Mixed Air Temperature" ; ph:dis "Bravo RTU-2 Mixed Air Temperature" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aee6-b9cb-524c-f23c91a70cca . _:0aa7c726-aee6-b9cb-524c-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5092275130999935 ; _:sourcePointName "MAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00dc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-2 Mixed Air Temperature Setpoint" ; ph:dis "Bravo RTU-2 Mixed Air Temperature Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aee6-b9cc-524d-f23c91a70cca . _:0aa7c726-aee6-b9cc-524d-f23c91a70cca rdfs:label "" ; _:predictionConf 0.41409123546331406 ; _:sourcePointName "MAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00dd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:outside, phIoT:point ; rdfs:label "Bravo RTU-2 Outside Air Damper Output" ; ph:dis "Bravo RTU-2 Outside Air Damper Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aee6-b9cd-524e-f23c91a70cca . _:0aa7c726-aee6-b9cd-524e-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7395401248861597 ; _:sourcePointName "OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-00de a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Outside Air Flow" ; ph:dis "Bravo RTU-2 Outside Air Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-aee6-b9ce-524f-f23c91a70cca . _:0aa7c726-aee6-b9ce-524f-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7870789837941534 ; _:sourcePointName "OA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-00df a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Outside Air Percentage (Auto-computed)" ; ph:dis "Bravo RTU-2 Outside Air Percentage (Auto-computed)" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aee6-b9cf-5250-f23c91a70cca . _:0aa7c726-aee6-b9cf-5250-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00e0 a phIoT:his-point ; ph:hasTag phScience:air, ph:computed, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-2 Percent Outside Air" ; ph:dis "Bravo RTU-2 Percent Outside Air" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aee6-b9d0-5251-f23c91a70cca . _:0aa7c726-aee6-b9d0-5251-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00e1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-2 Return Air Damper Output" ; ph:dis "Bravo RTU-2 Return Air Damper Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aee6-b9d1-5252-f23c91a70cca . _:0aa7c726-aee6-b9d1-5252-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3561100767369028 ; _:sourcePointName "RET/REL DAMPER" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00e2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-2 Return Air Flow" ; ph:dis "Bravo RTU-2 Return Air Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-aef5-fc00-5253-f23c91a70cca . _:0aa7c726-aef5-fc00-5253-f23c91a70cca rdfs:label "" ; _:predictionConf 0.8263008623409421 ; _:sourcePointName "RA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00e3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-2 Return Air Humidity" ; ph:dis "Bravo RTU-2 Return Air Humidity" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aef5-fc01-5254-f23c91a70cca . _:0aa7c726-aef5-fc01-5254-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7016271134196499 ; _:sourcePointName "RAH" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00e4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-2 Return Air Temperature" ; ph:dis "Bravo RTU-2 Return Air Temperature" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aef5-fc02-5255-f23c91a70cca . _:0aa7c726-aef5-fc02-5255-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5745623242771728 ; _:sourcePointName "RAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-00e5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-2 Return Fan Status" ; ph:dis "Bravo RTU-2 Return Fan Status" ; phIoT:equipRef _:b-00ce ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aef5-fc03-5256-f23c91a70cca . _:0aa7c726-aef5-fc03-5256-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5721715629985896 ; _:sourcePointName "RF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-00e6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-2 Return Fan VFD Speed" ; ph:dis "Bravo RTU-2 Return Fan VFD Speed" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aef5-fc04-5257-f23c91a70cca . _:0aa7c726-aef5-fc04-5257-f23c91a70cca rdfs:label "" ; _:predictionConf 0.13813130060214382 ; _:sourcePointName "ACT_OUTPUT_SPEED" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-00e7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Supply Air Flow" ; ph:dis "Bravo RTU-2 Supply Air Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-aef5-fc05-5258-f23c91a70cca . _:0aa7c726-aef5-fc05-5258-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7841375570046363 ; _:sourcePointName "SA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00e8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Supply Air Humidity" ; ph:dis "Bravo RTU-2 Supply Air Humidity" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aef5-fc06-5259-f23c91a70cca . _:0aa7c726-aef5-fc06-5259-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7933659564917551 ; _:sourcePointName "DAH" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-00e9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Supply Air Humidity Setpoint" ; ph:dis "Bravo RTU-2 Supply Air Humidity Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:pointFunction phIoT:sp ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aef5-fc07-525a-f23c91a70cca . _:0aa7c726-aef5-fc07-525a-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7045004074770955 ; _:sourcePointName "Humidity SP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00ea a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor ; rdfs:label "Bravo RTU-2 Supply Air Static Pressure" ; ph:dis "Bravo RTU-2 Supply Air Static Pressure" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0aa7c726-aef5-fc08-525b-f23c91a70cca . _:0aa7c726-aef5-fc08-525b-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3539915786588711 ; _:sourcePointName "DISCH STATIC" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00eb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sp ; rdfs:label "Bravo RTU-2 Supply Air Static Pressure Setpoint" ; ph:dis "Bravo RTU-2 Supply Air Static Pressure Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0aa7c726-aef5-fc09-525c-f23c91a70cca . _:0aa7c726-aef5-fc09-525c-f23c91a70cca rdfs:label "" ; _:predictionConf 0.48636472322277824 ; _:sourcePointName "Static Stpt" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-00ec a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-2 Supply Air Temperature" ; ph:dis "Bravo RTU-2 Supply Air Temperature" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aef5-fc0a-525d-f23c91a70cca . _:0aa7c726-aef5-fc0a-525d-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5598774100147106 ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00ed a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-2 Supply Air Temperature Setpoint" ; ph:dis "Bravo RTU-2 Supply Air Temperature Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-aef5-fc0b-525e-f23c91a70cca . _:0aa7c726-aef5-fc0b-525e-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6936845307741977 ; _:sourcePointName "DAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-00ee a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-2 Supply Fan Status" ; ph:dis "Bravo RTU-2 Supply Fan Status" ; phIoT:equipRef _:b-00ce ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aef5-fc0c-525f-f23c91a70cca . _:0aa7c726-aef5-fc0c-525f-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6818756457191736 ; _:sourcePointName "SF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-00ef a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-2 Supply Fan VFD Speed" ; ph:dis "Bravo RTU-2 Supply Fan VFD Speed" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-aef5-fc0d-5260-f23c91a70cca . _:0aa7c726-aef5-fc0d-5260-f23c91a70cca rdfs:label "" ; _:predictionConf 0.13813130060214382 ; _:sourcePointName "ACT_OUTPUT_SPEED" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-00f0 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 TU Air Flow (Auto-computed)" ; ph:dis "Bravo RTU-2 TU Air Flow (Auto-computed)" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-aef5-fc0e-5261-f23c91a70cca . _:0aa7c726-aef5-fc0e-5261-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00f1 a phIoT:his-point ; ph:hasTag phScience:air, ph:computed, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 VAV Total Flow" ; ph:dis "Bravo RTU-2 VAV Total Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-aef5-fc0f-5262-f23c91a70cca . _:0aa7c726-aef5-fc0f-5262-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00f2 a phIoT:rtu ; ph:hasTag phIoT:ahu, phIoT:chilledWaterCooling, phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:rtu, phIoT:singleDuct, phIoT:vavZone ; rdfs:label "Bravo RTU-3" ; ph:dis "Bravo RTU-3" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; _:custom _:0aa7c726-aef5-fc10-5263-f23c91a70cca . _:0aa7c726-aef5-fc10-5263-f23c91a70cca rdfs:label "" ; _:designDischargeAirFlow 33600 ; _:designHotWaterLeavingTemp 65 ; _:designHotWaterPower 318 ; _:designOutsideAirFlowMin 7125 ; _:designDischargeFanAirDeltaPressure 6.7 ; _:designSource "Drawings" ; _:designChilledWaterLeavingTemp 58.9 ; _:designChilledWaterPower 1346.1 ; _:designHotWaterFlow 53 ; _:designChilledWaterFlow 180.2 ; _:designReturnAirFlow 33600 ; _:designHotWaterEnteringTemp 75 ; _:designOutsideAirFlow 33600 ; _:designReturnFanPower 25 ; _:designChilledWaterEnteringTemp 44 ; _:designDischargeFanPower 60 ; _:designReturnFanAirDeltaPressure 1.63 . _:b-00f3 a phIoT:his-point ; ph:hasTag ph:computed, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 AHU Operation Mode" ; ph:dis "Bravo RTU-3 AHU Operation Mode" ; phIoT:equipRef _:b-00f2 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-aef5-fc11-5264-f23c91a70cca . _:0aa7c726-aef5-fc11-5264-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00f4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cmd, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo RTU-3 Cooling Valve Output" ; ph:dis "Bravo RTU-3 Cooling Valve Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af05-3e40-5265-f23c91a70cca . _:0aa7c726-af05-3e40-5265-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5846394026860828 ; _:sourcePointName "CWV" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00f5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:exhaust, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Exhaust Air Damper Output" ; ph:dis "Bravo RTU-3 Exhaust Air Damper Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af05-3e41-5266-f23c91a70cca . _:0aa7c726-af05-3e41-5266-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6232903565384572 ; _:sourcePointName "EAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00f6 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 Fan Power (Auto-computed)" ; ph:dis "Bravo RTU-3 Fan Power (Auto-computed)" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0aa7c726-af05-3e42-5267-f23c91a70cca . _:0aa7c726-af05-3e42-5267-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00f7 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 Heating/Cooling Load (Auto-computed)" ; ph:dis "Bravo RTU-3 Heating/Cooling Load (Auto-computed)" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "BTU/h" ; _:custom _:0aa7c726-af05-3e43-5268-f23c91a70cca . _:0aa7c726-af05-3e43-5268-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00f8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:his, phIoT:humidifier, phIoT:point ; rdfs:label "Bravo RTU-3 Humidifier Enable" ; ph:dis "Bravo RTU-3 Humidifier Enable" ; phIoT:equipRef _:b-00f2 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-af05-3e44-5269-f23c91a70cca . _:0aa7c726-af05-3e44-5269-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2169429859073283 ; _:sourcePointName "HUM_ENABLE" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-00f9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:his, phIoT:humidifier, phIoT:point, phScience:steam, phIoT:valve ; rdfs:label "Bravo RTU-3 Humidifier Output" ; ph:dis "Bravo RTU-3 Humidifier Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af05-3e45-526a-f23c91a70cca . _:0aa7c726-af05-3e45-526a-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7439557600414519 ; _:sourcePointName "HUM VLV" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00fa a phIoT:his-point ; ph:hasTag phIoT:cmd, ph:computed, phIoT:damper, phIoT:his, phIoT:point ; rdfs:label "Bravo RTU-3 Max Damper Position" ; ph:dis "Bravo RTU-3 Max Damper Position" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af05-3e46-526b-f23c91a70cca . _:0aa7c726-af05-3e46-526b-f23c91a70cca ph:hasTag ph:max ; rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00fb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 Min OA Flow Setpoint" ; ph:dis "Bravo RTU-3 Min OA Flow Setpoint" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af05-3e47-526c-f23c91a70cca . _:0aa7c726-af05-3e47-526c-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2305698711556413 ; _:sourcePointName "MINOASTPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-00fc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Minimum Outside Air Damper Output" ; ph:dis "Bravo RTU-3 Minimum Outside Air Damper Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af05-3e48-526d-f23c91a70cca . _:0aa7c726-af05-3e48-526d-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7226466689139898 ; _:sourcePointName "Min OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00fd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-3 Mixed Air Temperature" ; ph:dis "Bravo RTU-3 Mixed Air Temperature" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-af05-3e49-526e-f23c91a70cca . _:0aa7c726-af05-3e49-526e-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5092275130999935 ; _:sourcePointName "MAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00fe a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-3 Mixed Air Temperature Setpoint" ; ph:dis "Bravo RTU-3 Mixed Air Temperature Setpoint" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-af05-3e4a-526f-f23c91a70cca . _:0aa7c726-af05-3e4a-526f-f23c91a70cca rdfs:label "" ; _:predictionConf 0.41409123546331406 ; _:sourcePointName "MAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-00ff a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:outside, phIoT:point ; rdfs:label "Bravo RTU-3 Outside Air Damper Output" ; ph:dis "Bravo RTU-3 Outside Air Damper Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af05-3e4b-5270-f23c91a70cca . _:0aa7c726-af05-3e4b-5270-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7395401248861597 ; _:sourcePointName "OAD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0100 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Outside Air Flow" ; ph:dis "Bravo RTU-3 Outside Air Flow" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af05-3e4c-5271-f23c91a70cca . _:0aa7c726-af05-3e4c-5271-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7870789837941534 ; _:sourcePointName "OA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0101 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 Outside Air Percentage (Auto-computed)" ; ph:dis "Bravo RTU-3 Outside Air Percentage (Auto-computed)" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-af05-3e4d-5272-f23c91a70cca . _:0aa7c726-af05-3e4d-5272-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0102 a phIoT:his-point ; ph:hasTag phScience:air, ph:computed, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-3 Percent Outside Air" ; ph:dis "Bravo RTU-3 Percent Outside Air" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af05-3e4e-5273-f23c91a70cca . _:0aa7c726-af05-3e4e-5273-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0103 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:return ; rdfs:label "Bravo RTU-3 Return Air Damper Output" ; ph:dis "Bravo RTU-3 Return Air Damper Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af05-3e4f-5274-f23c91a70cca . _:0aa7c726-af05-3e4f-5274-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3561100767369028 ; _:sourcePointName "RET/REL DAMPER" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0104 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-3 Return Air Flow" ; ph:dis "Bravo RTU-3 Return Air Flow" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af05-3e50-5275-f23c91a70cca . _:0aa7c726-af05-3e50-5275-f23c91a70cca rdfs:label "" ; _:predictionConf 0.8263008623409421 ; _:sourcePointName "RA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0105 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-3 Return Air Humidity" ; ph:dis "Bravo RTU-3 Return Air Humidity" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af05-3e51-5276-f23c91a70cca . _:0aa7c726-af05-3e51-5276-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7016271134196499 ; _:sourcePointName "RAH" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0106 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-3 Return Air Temperature" ; ph:dis "Bravo RTU-3 Return Air Temperature" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-af05-3e52-5277-f23c91a70cca . _:0aa7c726-af05-3e52-5277-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5745623242771728 ; _:sourcePointName "RAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0107 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-3 Return Fan Status" ; ph:dis "Bravo RTU-3 Return Fan Status" ; phIoT:equipRef _:b-00f2 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-af42-4740-5278-f23c91a70cca . _:0aa7c726-af42-4740-5278-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5721715629985896 ; _:sourcePointName "RF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0108 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-3 Return Fan VFD Speed" ; ph:dis "Bravo RTU-3 Return Fan VFD Speed" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af42-4741-5279-f23c91a70cca . _:0aa7c726-af42-4741-5279-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3324288739189246 ; _:sourcePointName "RTDrvSpd" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0109 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Supply Air Flow" ; ph:dis "Bravo RTU-3 Supply Air Flow" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af42-4742-527a-f23c91a70cca . _:0aa7c726-af42-4742-527a-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7841375570046363 ; _:sourcePointName "SA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-010a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Supply Air Humidity" ; ph:dis "Bravo RTU-3 Supply Air Humidity" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af42-4743-527b-f23c91a70cca . _:0aa7c726-af42-4743-527b-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7933659564917551 ; _:sourcePointName "DAH" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-010b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sp ; rdfs:label "Bravo RTU-3 Supply Air Pressure Setpoint" ; ph:dis "Bravo RTU-3 Supply Air Pressure Setpoint" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0aa7c726-af42-4744-527c-f23c91a70cca . _:0aa7c726-af42-4744-527c-f23c91a70cca rdfs:label "" ; _:predictionConf 0.48636472322277824 ; _:sourcePointName "Static Stpt" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-010c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor ; rdfs:label "Bravo RTU-3 Supply Air Static Pressure" ; ph:dis "Bravo RTU-3 Supply Air Static Pressure" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0aa7c726-af42-4745-527d-f23c91a70cca . _:0aa7c726-af42-4745-527d-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3539915786588711 ; _:sourcePointName "DISCH STATIC" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-010d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-3 Supply Air Temperature" ; ph:dis "Bravo RTU-3 Supply Air Temperature" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-af42-4746-527e-f23c91a70cca . _:0aa7c726-af42-4746-527e-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5598774100147106 ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-010e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-3 Supply Air Temperature Setpoint" ; ph:dis "Bravo RTU-3 Supply Air Temperature Setpoint" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-af42-4747-527f-f23c91a70cca . _:0aa7c726-af42-4747-527f-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6936845307741977 ; _:sourcePointName "DAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-010f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-3 Supply Fan Status" ; ph:dis "Bravo RTU-3 Supply Fan Status" ; phIoT:equipRef _:b-00f2 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-af42-4748-5280-f23c91a70cca . _:0aa7c726-af42-4748-5280-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6818756457191736 ; _:sourcePointName "SF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0110 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-3 Supply Fan VFD Speed" ; ph:dis "Bravo RTU-3 Supply Fan VFD Speed" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af42-4749-5281-f23c91a70cca . _:0aa7c726-af42-4749-5281-f23c91a70cca rdfs:label "" ; _:predictionConf 0.32036669663302475 ; _:sourcePointName "SPDrvSpd" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0111 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 TU Air Flow (Auto-computed)" ; ph:dis "Bravo RTU-3 TU Air Flow (Auto-computed)" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af42-474a-5282-f23c91a70cca . _:0aa7c726-af42-474a-5282-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0112 a phIoT:his-point ; ph:hasTag phScience:air, ph:computed, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 VAV Total Flow" ; ph:dis "Bravo RTU-3 VAV Total Flow" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af42-474b-5283-f23c91a70cca . _:0aa7c726-af42-474b-5283-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0113 a phIoT:rtu ; ph:hasTag phIoT:ahu, phIoT:chilledWaterCooling, phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:rtu, phIoT:singleDuct, phIoT:vavZone ; rdfs:label "Bravo RTU-4" ; ph:dis "Bravo RTU-4" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; _:custom _:0aa7c726-af51-8980-5284-f23c91a70cca . _:0aa7c726-af51-8980-5284-f23c91a70cca rdfs:label "" ; _:designDischargeAirFlow 15700 ; _:designHotWaterLeavingTemp 65 ; _:designHotWaterPower 243 ; _:designOutsideAirFlowMin 7125 ; _:designDischargeFanAirDeltaPressure 4.76 ; _:designSource "Drawings" ; _:designChilledWaterLeavingTemp 58.9 ; _:designChilledWaterPower 1028.7 ; _:designHotWaterFlow 41 ; _:designChilledWaterFlow 137.8 ; _:designReturnAirFlow 25700 ; _:designHotWaterEnteringTemp 75 ; _:designOutsideAirFlow 25700 ; _:designReturnFanPower 20 ; _:designChilledWaterEnteringTemp 44 ; _:designDischargeFanPower 40 ; _:designReturnFanAirDeltaPressure 1.64 . _:b-0114 a phIoT:his-point ; ph:hasTag ph:computed, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 AHU Operation Mode" ; ph:dis "Bravo RTU-4 AHU Operation Mode" ; phIoT:equipRef _:b-0113 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-af51-8981-5285-f23c91a70cca . _:0aa7c726-af51-8981-5285-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0115 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cmd, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo RTU-4 Cooling Valve Output" ; ph:dis "Bravo RTU-4 Cooling Valve Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af51-8982-5286-f23c91a70cca . _:0aa7c726-af51-8982-5286-f23c91a70cca rdfs:label "" ; _:sourcePointName "CWV" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0116 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:exhaust, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Exhaust Air Damper Output" ; ph:dis "Bravo RTU-4 Exhaust Air Damper Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af51-8983-5287-f23c91a70cca . _:0aa7c726-af51-8983-5287-f23c91a70cca rdfs:label "" ; _:sourcePointName "EAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0117 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Fan Power (Auto-computed)" ; ph:dis "Bravo RTU-4 Fan Power (Auto-computed)" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0aa7c726-af51-8984-5288-f23c91a70cca . _:0aa7c726-af51-8984-5288-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0118 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Heating/Cooling Load (Auto-computed)" ; ph:dis "Bravo RTU-4 Heating/Cooling Load (Auto-computed)" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "BTU/h" ; _:custom _:0aa7c726-af51-8985-5289-f23c91a70cca . _:0aa7c726-af51-8985-5289-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0119 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:his, phIoT:humidifier, phIoT:point ; rdfs:label "Bravo RTU-4 Humidifier Enable" ; ph:dis "Bravo RTU-4 Humidifier Enable" ; phIoT:equipRef _:b-0113 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-af51-8986-528a-f23c91a70cca . _:0aa7c726-af51-8986-528a-f23c91a70cca rdfs:label "" ; _:sourcePointName "HUM_ENABLE" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-011a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:his, phIoT:humidifier, phIoT:point, phScience:steam, phIoT:valve ; rdfs:label "Bravo RTU-4 Humidifier Output" ; ph:dis "Bravo RTU-4 Humidifier Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af51-8987-528b-f23c91a70cca . _:0aa7c726-af51-8987-528b-f23c91a70cca rdfs:label "" ; _:sourcePointName "HUM VLV" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-011b a phIoT:his-point ; ph:hasTag phIoT:cmd, ph:computed, phIoT:damper, phIoT:his, phIoT:point ; rdfs:label "Bravo RTU-4 Max Damper Position" ; ph:dis "Bravo RTU-4 Max Damper Position" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af51-8988-528c-f23c91a70cca . _:0aa7c726-af51-8988-528c-f23c91a70cca ph:hasTag ph:max ; rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-011c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Min Outdoor Air Flow Setpoint" ; ph:dis "Bravo RTU-4 Min Outdoor Air Flow Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af51-8989-528d-f23c91a70cca . _:0aa7c726-af51-8989-528d-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:sourcePointName "MinOA_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime ; _:pointType "" . _:b-011d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Min Outdoor Air Flow/10" ; ph:dis "Bravo RTU-4 Min Outdoor Air Flow/10" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af51-898a-528e-f23c91a70cca . _:0aa7c726-af51-898a-528e-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:sourcePointName "MIN OA CFM / 10" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-011e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Minimum Outside Air Damper Output" ; ph:dis "Bravo RTU-4 Minimum Outside Air Damper Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af51-898b-528f-f23c91a70cca . _:0aa7c726-af51-898b-528f-f23c91a70cca rdfs:label "" ; _:sourcePointName "Min OAD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-011f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-4 Mixed Air Temperature" ; ph:dis "Bravo RTU-4 Mixed Air Temperature" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-af51-898c-5290-f23c91a70cca . _:0aa7c726-af51-898c-5290-f23c91a70cca rdfs:label "" ; _:sourcePointName "MAT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0120 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-4 Mixed Air Temperature Setpoint" ; ph:dis "Bravo RTU-4 Mixed Air Temperature Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-af51-898d-5291-f23c91a70cca . _:0aa7c726-af51-898d-5291-f23c91a70cca rdfs:label "" ; _:sourcePointName "MAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0121 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:outside, phIoT:point ; rdfs:label "Bravo RTU-4 Outside Air Damper Output" ; ph:dis "Bravo RTU-4 Outside Air Damper Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af51-898e-5292-f23c91a70cca . _:0aa7c726-af51-898e-5292-f23c91a70cca rdfs:label "" ; _:sourcePointName "OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0122 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Outside Air Flow" ; ph:dis "Bravo RTU-4 Outside Air Flow" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af51-898f-5293-f23c91a70cca . _:0aa7c726-af51-898f-5293-f23c91a70cca rdfs:label "" ; _:sourcePointName "OA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0123 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Outside Air Percentage (Auto-computed)" ; ph:dis "Bravo RTU-4 Outside Air Percentage (Auto-computed)" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0aa7c726-af51-8990-5294-f23c91a70cca . _:0aa7c726-af51-8990-5294-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0124 a phIoT:his-point ; ph:hasTag phScience:air, ph:computed, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-4 Percent Outside Air" ; ph:dis "Bravo RTU-4 Percent Outside Air" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af51-8991-5295-f23c91a70cca . _:0aa7c726-af51-8991-5295-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0125 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-4 Return Air Damper Output" ; ph:dis "Bravo RTU-4 Return Air Damper Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af51-8992-5296-f23c91a70cca . _:0aa7c726-af51-8992-5296-f23c91a70cca rdfs:label "" ; _:sourcePointName "RET/REL DAMPER" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0126 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-4 Return Air Flow" ; ph:dis "Bravo RTU-4 Return Air Flow" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af51-8993-5297-f23c91a70cca . _:0aa7c726-af51-8993-5297-f23c91a70cca rdfs:label "" ; _:sourcePointName "RA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0127 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-4 Return Air Humidity" ; ph:dis "Bravo RTU-4 Return Air Humidity" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af51-8994-5298-f23c91a70cca . _:0aa7c726-af51-8994-5298-f23c91a70cca rdfs:label "" ; _:sourcePointName "RAH" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0128 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-4 Return Air Temperature" ; ph:dis "Bravo RTU-4 Return Air Temperature" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-af60-cbc0-5299-f23c91a70cca . _:0aa7c726-af60-cbc0-5299-f23c91a70cca rdfs:label "" ; _:sourcePointName "RAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0129 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-4 Return Fan Status" ; ph:dis "Bravo RTU-4 Return Fan Status" ; phIoT:equipRef _:b-0113 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-af60-cbc1-529a-f23c91a70cca . _:0aa7c726-af60-cbc1-529a-f23c91a70cca rdfs:label "" ; _:sourcePointName "RF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-012a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-4 Return Fan VFD Speed" ; ph:dis "Bravo RTU-4 Return Fan VFD Speed" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af60-cbc2-529b-f23c91a70cca . _:0aa7c726-af60-cbc2-529b-f23c91a70cca rdfs:label "" ; _:sourcePointName "ACT_OUTPUT_SPEED" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-012b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Supply Air Flow" ; ph:dis "Bravo RTU-4 Supply Air Flow" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af60-cbc3-529c-f23c91a70cca . _:0aa7c726-af60-cbc3-529c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-012c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Supply Air Humidity" ; ph:dis "Bravo RTU-4 Supply Air Humidity" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af60-cbc4-529d-f23c91a70cca . _:0aa7c726-af60-cbc4-529d-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAH" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-012d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Supply Air Humidity Setpoint" ; ph:dis "Bravo RTU-4 Supply Air Humidity Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sp ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af60-cbc5-529e-f23c91a70cca . _:0aa7c726-af60-cbc5-529e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Humidity SP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-012e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sp ; rdfs:label "Bravo RTU-4 Supply Air Pressure Setpoint" ; ph:dis "Bravo RTU-4 Supply Air Pressure Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0aa7c726-af60-cbc6-529f-f23c91a70cca . _:0aa7c726-af60-cbc6-529f-f23c91a70cca rdfs:label "" ; _:sourcePointName "Static Stpt" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-012f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor ; rdfs:label "Bravo RTU-4 Supply Air Static Pressure" ; ph:dis "Bravo RTU-4 Supply Air Static Pressure" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0aa7c726-af60-cbc7-52a0-f23c91a70cca . _:0aa7c726-af60-cbc7-52a0-f23c91a70cca rdfs:label "" ; _:sourcePointName "DISCH STATIC" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0130 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-4 Supply Air Temperature" ; ph:dis "Bravo RTU-4 Supply Air Temperature" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-af60-cbc8-52a1-f23c91a70cca . _:0aa7c726-af60-cbc8-52a1-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0131 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-4 Supply Air Temperature Setpoint" ; ph:dis "Bravo RTU-4 Supply Air Temperature Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-af60-cbc9-52a2-f23c91a70cca . _:0aa7c726-af60-cbc9-52a2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0132 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-4 Supply Fan Status" ; ph:dis "Bravo RTU-4 Supply Fan Status" ; phIoT:equipRef _:b-0113 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0aa7c726-af60-cbca-52a3-f23c91a70cca . _:0aa7c726-af60-cbca-52a3-f23c91a70cca rdfs:label "" ; _:sourcePointName "SF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0133 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 TU Air Flow (Auto-computed)" ; ph:dis "Bravo RTU-4 TU Air Flow (Auto-computed)" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af60-cbcb-52a4-f23c91a70cca . _:0aa7c726-af60-cbcb-52a4-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0134 a phIoT:his-point ; ph:hasTag phScience:air, ph:computed, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 VAV Total Flow" ; ph:dis "Bravo RTU-4 VAV Total Flow" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af60-cbcc-52a5-f23c91a70cca . _:0aa7c726-af60-cbcc-52a5-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0135 a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo RTUs" ; ph:dis "Bravo RTUs" ; phIoT:siteRef _:b-0000 ; _:custom _:0aa7c726-af60-cbcd-52a6-f23c91a70cca . _:0aa7c726-af60-cbcd-52a6-f23c91a70cca rdfs:label "" . _:b-0136 a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Steam Boiler A" ; ph:dis "Bravo Steam Boiler A" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; _:custom _:0aa7c726-af60-cbce-52a7-f23c91a70cca . _:0aa7c726-af60-cbce-52a7-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designMake "Lattner" ; _:designSteamPower 1350 ; _:designModel "WLF-40" . _:b-0137 a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Steam Boiler A Boiler Status" ; ph:dis "Bravo Steam Boiler A Boiler Status" ; phIoT:equipRef _:b-0136 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; ph:tz "Chicago" ; _:custom _:0aa7c726-af60-cbcf-52a8-f23c91a70cca . _:0aa7c726-af60-cbcf-52a8-f23c91a70cca rdfs:label "" ; _:sourcePointName "StmBlrAsts" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0138 a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Steam Boiler B" ; ph:dis "Bravo Steam Boiler B" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; _:custom _:0aa7c726-af60-cbd0-52a9-f23c91a70cca . _:0aa7c726-af60-cbd0-52a9-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designMake "Lattner" ; _:designSteamPower 1350 ; _:designModel "WLF-40" . _:b-0139 a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Steam Boiler B Boiler Status" ; ph:dis "Bravo Steam Boiler B Boiler Status" ; phIoT:equipRef _:b-0138 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; ph:tz "Chicago" ; _:custom _:0aa7c726-af60-cbd1-52aa-f23c91a70cca . _:0aa7c726-af60-cbd1-52aa-f23c91a70cca rdfs:label "" ; _:sourcePointName "StmBlrBsts" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-013a a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Steam Boiler C" ; ph:dis "Bravo Steam Boiler C" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; _:custom _:0aa7c726-af60-cbd2-52ab-f23c91a70cca . _:0aa7c726-af60-cbd2-52ab-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designMake "Lattner" ; _:designSteamPower 1350 ; _:designModel "WLF-40" . _:b-013b a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Steam Boiler C Boiler Status" ; ph:dis "Bravo Steam Boiler C Boiler Status" ; phIoT:equipRef _:b-013a ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; ph:tz "Chicago" ; _:custom _:0aa7c726-af60-cbd3-52ac-f23c91a70cca . _:0aa7c726-af60-cbd3-52ac-f23c91a70cca rdfs:label "" ; _:sourcePointName "StmBlrCsts" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-013c a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo Steam System" ; ph:dis "Bravo Steam System" ; phIoT:siteRef _:b-0000 ; _:custom _:0aa7c726-af70-0e00-52ad-f23c91a70cca . _:0aa7c726-af70-0e00-52ad-f23c91a70cca rdfs:label "" . _:b-013d a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-1" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-1" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-af70-0e01-52ae-f23c91a70cca . _:0aa7c726-af70-0e01-52ae-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 9.7 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-013e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-1 Damper Output" ; ph:dis "Bravo VAV 1-1 Damper Output" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af70-0e02-52af-f23c91a70cca . _:0aa7c726-af70-0e02-52af-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-013f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-1 Discharge Air Flow" ; ph:dis "Bravo VAV 1-1 Discharge Air Flow" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af70-0e03-52b0-f23c91a70cca . _:0aa7c726-af70-0e03-52b0-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0140 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-1 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-1 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af70-0e04-52b1-f23c91a70cca . _:0aa7c726-af70-0e04-52b1-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0141 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-1 Heating Valve Output" ; ph:dis "Bravo VAV 1-1 Heating Valve Output" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af70-0e05-52b2-f23c91a70cca . _:0aa7c726-af70-0e05-52b2-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0142 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-1 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-1 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-af70-0e06-52b3-f23c91a70cca . _:0aa7c726-af70-0e06-52b3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0143 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-1 Zone Temperature" ; ph:dis "Bravo VAV 1-1 Zone Temperature" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-af70-0e07-52b4-f23c91a70cca . _:0aa7c726-af70-0e07-52b4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0144 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-10" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-10" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-af70-0e08-52b5-f23c91a70cca . _:0aa7c726-af70-0e08-52b5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 6.5 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 375 . _:b-0145 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-10 Damper Output" ; ph:dis "Bravo VAV 1-10 Damper Output" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-af70-0e09-52b6-f23c91a70cca . _:0aa7c726-af70-0e09-52b6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0146 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-10 Discharge Air Flow" ; ph:dis "Bravo VAV 1-10 Discharge Air Flow" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-af70-0e0a-52b7-f23c91a70cca . _:0aa7c726-af70-0e0a-52b7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0147 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-10 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-10 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afad-1700-52b8-f23c91a70cca . _:0aa7c726-afad-1700-52b8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0148 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-10 Heating Valve Output" ; ph:dis "Bravo VAV 1-10 Heating Valve Output" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afad-1701-52b9-f23c91a70cca . _:0aa7c726-afad-1701-52b9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0149 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-10 Supply Air Temperature" ; ph:dis "Bravo VAV 1-10 Supply Air Temperature" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afad-1702-52ba-f23c91a70cca . _:0aa7c726-afad-1702-52ba-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-014a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-10 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-10 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afad-1703-52bb-f23c91a70cca . _:0aa7c726-afad-1703-52bb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-014b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-10 Zone Temperature" ; ph:dis "Bravo VAV 1-10 Zone Temperature" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afad-1704-52bc-f23c91a70cca . _:0aa7c726-afad-1704-52bc-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-014c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-11" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-11" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-afad-1705-52bd-f23c91a70cca . _:0aa7c726-afad-1705-52bd-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 300 . _:b-014d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-11 Damper Output" ; ph:dis "Bravo VAV 1-11 Damper Output" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afad-1706-52be-f23c91a70cca . _:0aa7c726-afad-1706-52be-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-014e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-11 Discharge Air Flow" ; ph:dis "Bravo VAV 1-11 Discharge Air Flow" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afad-1707-52bf-f23c91a70cca . _:0aa7c726-afad-1707-52bf-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-014f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-11 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-11 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afad-1708-52c0-f23c91a70cca . _:0aa7c726-afad-1708-52c0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0150 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-11 Heating Valve Output" ; ph:dis "Bravo VAV 1-11 Heating Valve Output" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afad-1709-52c1-f23c91a70cca . _:0aa7c726-afad-1709-52c1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0151 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-11 Supply Air Temperature" ; ph:dis "Bravo VAV 1-11 Supply Air Temperature" ; phIoT:equipRef _:b-014c ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afad-170a-52c2-f23c91a70cca . _:0aa7c726-afad-170a-52c2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0152 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-11 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-11 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afad-170b-52c3-f23c91a70cca . _:0aa7c726-afad-170b-52c3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0153 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-11 Zone Temperature" ; ph:dis "Bravo VAV 1-11 Zone Temperature" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afad-170c-52c4-f23c91a70cca . _:0aa7c726-afad-170c-52c4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0154 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-12" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-12" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-afad-170d-52c5-f23c91a70cca . _:0aa7c726-afad-170d-52c5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-0155 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-12 Damper Output" ; ph:dis "Bravo VAV 1-12 Damper Output" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afad-170e-52c6-f23c91a70cca . _:0aa7c726-afad-170e-52c6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0156 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-12 Discharge Air Flow" ; ph:dis "Bravo VAV 1-12 Discharge Air Flow" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afad-170f-52c7-f23c91a70cca . _:0aa7c726-afad-170f-52c7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0157 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-12 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-12 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afad-1710-52c8-f23c91a70cca . _:0aa7c726-afad-1710-52c8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0158 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-12 Heating Valve Output" ; ph:dis "Bravo VAV 1-12 Heating Valve Output" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afad-1711-52c9-f23c91a70cca . _:0aa7c726-afad-1711-52c9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0159 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-12 Supply Air Temperature" ; ph:dis "Bravo VAV 1-12 Supply Air Temperature" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afad-1712-52ca-f23c91a70cca . _:0aa7c726-afad-1712-52ca-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-015a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-12 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-12 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afbc-5940-52cb-f23c91a70cca . _:0aa7c726-afbc-5940-52cb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-015b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-12 Zone Temperature" ; ph:dis "Bravo VAV 1-12 Zone Temperature" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afbc-5941-52cc-f23c91a70cca . _:0aa7c726-afbc-5941-52cc-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-015c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-13" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-13" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-afbc-5942-52cd-f23c91a70cca . _:0aa7c726-afbc-5942-52cd-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 27 ; _:designHotWaterFlow 3 ; _:designAirFlow 1000 . _:b-015d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-13 Damper Output" ; ph:dis "Bravo VAV 1-13 Damper Output" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afbc-5943-52ce-f23c91a70cca . _:0aa7c726-afbc-5943-52ce-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-015e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-13 Discharge Air Flow" ; ph:dis "Bravo VAV 1-13 Discharge Air Flow" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afbc-5944-52cf-f23c91a70cca . _:0aa7c726-afbc-5944-52cf-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-015f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-13 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-13 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afbc-5945-52d0-f23c91a70cca . _:0aa7c726-afbc-5945-52d0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0160 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-13 Heating Valve" ; ph:dis "Bravo VAV 1-13 Heating Valve" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afbc-5946-52d1-f23c91a70cca . _:0aa7c726-afbc-5946-52d1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0161 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-13 Supply Air Temperature" ; ph:dis "Bravo VAV 1-13 Supply Air Temperature" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afbc-5947-52d2-f23c91a70cca . _:0aa7c726-afbc-5947-52d2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0162 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-13 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-13 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afbc-5948-52d3-f23c91a70cca . _:0aa7c726-afbc-5948-52d3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0163 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-13 Zone Temperature" ; ph:dis "Bravo VAV 1-13 Zone Temperature" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afbc-5949-52d4-f23c91a70cca . _:0aa7c726-afbc-5949-52d4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0164 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-14" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-14" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-afbc-594a-52d5-f23c91a70cca . _:0aa7c726-afbc-594a-52d5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 4.5 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 250 . _:b-0165 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-14 Damper Output" ; ph:dis "Bravo VAV 1-14 Damper Output" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afbc-594b-52d6-f23c91a70cca . _:0aa7c726-afbc-594b-52d6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0166 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-14 Discharge Air Flow" ; ph:dis "Bravo VAV 1-14 Discharge Air Flow" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afbc-594c-52d7-f23c91a70cca . _:0aa7c726-afbc-594c-52d7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0167 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-14 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-14 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afbc-594d-52d8-f23c91a70cca . _:0aa7c726-afbc-594d-52d8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0168 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-14 Heating Valve Output" ; ph:dis "Bravo VAV 1-14 Heating Valve Output" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afbc-594e-52d9-f23c91a70cca . _:0aa7c726-afbc-594e-52d9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0169 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-14 Supply Air Temperature" ; ph:dis "Bravo VAV 1-14 Supply Air Temperature" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afbc-594f-52da-f23c91a70cca . _:0aa7c726-afbc-594f-52da-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-016a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-14 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-14 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afbc-5950-52db-f23c91a70cca . _:0aa7c726-afbc-5950-52db-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-016b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-14 Zone Temperature" ; ph:dis "Bravo VAV 1-14 Zone Temperature" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afbc-5951-52dc-f23c91a70cca . _:0aa7c726-afbc-5951-52dc-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-016c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-15" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-15" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-afcb-9b80-52dd-f23c91a70cca . _:0aa7c726-afcb-9b80-52dd-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 6 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-016d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-15 Damper Output" ; ph:dis "Bravo VAV 1-15 Damper Output" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afcb-9b81-52de-f23c91a70cca . _:0aa7c726-afcb-9b81-52de-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-016e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-15 Discharge Air Flow" ; ph:dis "Bravo VAV 1-15 Discharge Air Flow" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afcb-9b82-52df-f23c91a70cca . _:0aa7c726-afcb-9b82-52df-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-016f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-15 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-15 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afcb-9b83-52e0-f23c91a70cca . _:0aa7c726-afcb-9b83-52e0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0170 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-15 Heating Valve Output" ; ph:dis "Bravo VAV 1-15 Heating Valve Output" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afcb-9b84-52e1-f23c91a70cca . _:0aa7c726-afcb-9b84-52e1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0171 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-15 Supply Air Temperature" ; ph:dis "Bravo VAV 1-15 Supply Air Temperature" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afcb-9b85-52e2-f23c91a70cca . _:0aa7c726-afcb-9b85-52e2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0172 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-15 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-15 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afcb-9b86-52e3-f23c91a70cca . _:0aa7c726-afcb-9b86-52e3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0173 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-15 Zone Temperature" ; ph:dis "Bravo VAV 1-15 Zone Temperature" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afcb-9b87-52e4-f23c91a70cca . _:0aa7c726-afcb-9b87-52e4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0174 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-16" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-16" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-afcb-9b88-52e5-f23c91a70cca . _:0aa7c726-afcb-9b88-52e5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 4.1 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0175 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-16 Damper Output" ; ph:dis "Bravo VAV 1-16 Damper Output" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afcb-9b89-52e6-f23c91a70cca . _:0aa7c726-afcb-9b89-52e6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0176 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-16 Discharge Air Flow" ; ph:dis "Bravo VAV 1-16 Discharge Air Flow" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afcb-9b8a-52e7-f23c91a70cca . _:0aa7c726-afcb-9b8a-52e7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0177 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-16 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-16 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afcb-9b8b-52e8-f23c91a70cca . _:0aa7c726-afcb-9b8b-52e8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0178 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-16 Heating Valve Output" ; ph:dis "Bravo VAV 1-16 Heating Valve Output" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afcb-9b8c-52e9-f23c91a70cca . _:0aa7c726-afcb-9b8c-52e9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0179 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-16 Supply Air Temperature" ; ph:dis "Bravo VAV 1-16 Supply Air Temperature" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afcb-9b8d-52ea-f23c91a70cca . _:0aa7c726-afcb-9b8d-52ea-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-017a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-16 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-16 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afcb-9b8e-52eb-f23c91a70cca . _:0aa7c726-afcb-9b8e-52eb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-017b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-16 Zone Temperature" ; ph:dis "Bravo VAV 1-16 Zone Temperature" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afcb-9b8f-52ec-f23c91a70cca . _:0aa7c726-afcb-9b8f-52ec-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-017c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-17" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-17" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-afcb-9b90-52ed-f23c91a70cca . _:0aa7c726-afcb-9b90-52ed-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 6 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-017d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-17 Damper Output" ; ph:dis "Bravo VAV 1-17 Damper Output" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afcb-9b91-52ee-f23c91a70cca . _:0aa7c726-afcb-9b91-52ee-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-017e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-17 Discharge Air Flow" ; ph:dis "Bravo VAV 1-17 Discharge Air Flow" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afcb-9b92-52ef-f23c91a70cca . _:0aa7c726-afcb-9b92-52ef-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-017f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-17 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-17 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-afda-ddc0-52f0-f23c91a70cca . _:0aa7c726-afda-ddc0-52f0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0180 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-17 Heating Valve Output" ; ph:dis "Bravo VAV 1-17 Heating Valve Output" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-afda-ddc1-52f1-f23c91a70cca . _:0aa7c726-afda-ddc1-52f1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0181 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-17 Supply Air Temperature" ; ph:dis "Bravo VAV 1-17 Supply Air Temperature" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afda-ddc2-52f2-f23c91a70cca . _:0aa7c726-afda-ddc2-52f2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0182 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-17 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-17 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afda-ddc3-52f3-f23c91a70cca . _:0aa7c726-afda-ddc3-52f3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0183 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-17 Zone Temperature" ; ph:dis "Bravo VAV 1-17 Zone Temperature" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-afda-ddc4-52f4-f23c91a70cca . _:0aa7c726-afda-ddc4-52f4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0184 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-18" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-18" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b008-a480-52f5-f23c91a70cca . _:0aa7c726-b008-a480-52f5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 4.1 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0185 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-18 Damper Output" ; ph:dis "Bravo VAV 1-18 Damper Output" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b008-a481-52f6-f23c91a70cca . _:0aa7c726-b008-a481-52f6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0186 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-18 Discharge Air Flow" ; ph:dis "Bravo VAV 1-18 Discharge Air Flow" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b008-a482-52f7-f23c91a70cca . _:0aa7c726-b008-a482-52f7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0187 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-18 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-18 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b008-a483-52f8-f23c91a70cca . _:0aa7c726-b008-a483-52f8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0188 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-18 Heating Valve Output" ; ph:dis "Bravo VAV 1-18 Heating Valve Output" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b008-a484-52f9-f23c91a70cca . _:0aa7c726-b008-a484-52f9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0189 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-18 Supply Air Temperature" ; ph:dis "Bravo VAV 1-18 Supply Air Temperature" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b008-a485-52fa-f23c91a70cca . _:0aa7c726-b008-a485-52fa-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-018a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-18 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-18 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b017-e6c0-52fb-f23c91a70cca . _:0aa7c726-b017-e6c0-52fb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-018b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-18 Zone Temperature" ; ph:dis "Bravo VAV 1-18 Zone Temperature" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b017-e6c1-52fc-f23c91a70cca . _:0aa7c726-b017-e6c1-52fc-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-018c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-19" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-19" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b017-e6c2-52fd-f23c91a70cca . _:0aa7c726-b017-e6c2-52fd-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 30.9 ; _:designHotWaterFlow 1.45 ; _:designAirFlow 2400 . _:b-018d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-19 Damper Output" ; ph:dis "Bravo VAV 1-19 Damper Output" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b017-e6c3-52fe-f23c91a70cca . _:0aa7c726-b017-e6c3-52fe-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-018e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-19 Discharge Air Flow" ; ph:dis "Bravo VAV 1-19 Discharge Air Flow" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b017-e6c4-52ff-f23c91a70cca . _:0aa7c726-b017-e6c4-52ff-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-018f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-19 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-19 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b017-e6c5-5300-f23c91a70cca . _:0aa7c726-b017-e6c5-5300-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0190 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-19 Heating Valve Output" ; ph:dis "Bravo VAV 1-19 Heating Valve Output" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b017-e6c6-5301-f23c91a70cca . _:0aa7c726-b017-e6c6-5301-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0191 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-19 Supply Air Temperature" ; ph:dis "Bravo VAV 1-19 Supply Air Temperature" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b017-e6c7-5302-f23c91a70cca . _:0aa7c726-b017-e6c7-5302-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0192 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor, phIoT:zone ; rdfs:label "Bravo VAV 1-19 Zone Air Humidity" ; ph:dis "Bravo VAV 1-19 Zone Air Humidity" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b017-e6c8-5303-f23c91a70cca . _:0aa7c726-b017-e6c8-5303-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6984488664169048 ; _:sourcePointName "Humidity" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0193 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-19 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-19 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b017-e6c9-5304-f23c91a70cca . _:0aa7c726-b017-e6c9-5304-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0194 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-19 Zone Temperature" ; ph:dis "Bravo VAV 1-19 Zone Temperature" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b017-e6ca-5305-f23c91a70cca . _:0aa7c726-b017-e6ca-5305-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0195 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-2" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-2" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b017-e6cb-5306-f23c91a70cca . _:0aa7c726-b017-e6cb-5306-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 17.5 ; _:designHotWaterFlow 2 ; _:designAirFlow 500 . _:b-0196 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-2 Damper Output" ; ph:dis "Bravo VAV 1-2 Damper Output" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b017-e6cc-5307-f23c91a70cca . _:0aa7c726-b017-e6cc-5307-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0197 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-2 Discharge Air Flow" ; ph:dis "Bravo VAV 1-2 Discharge Air Flow" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b017-e6cd-5308-f23c91a70cca . _:0aa7c726-b017-e6cd-5308-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0198 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-2 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-2 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b017-e6ce-5309-f23c91a70cca . _:0aa7c726-b017-e6ce-5309-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0199 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-2 Heating Valve Output" ; ph:dis "Bravo VAV 1-2 Heating Valve Output" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b017-e6cf-530a-f23c91a70cca . _:0aa7c726-b017-e6cf-530a-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-019a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-2 Supply Air Temperature" ; ph:dis "Bravo VAV 1-2 Supply Air Temperature" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b027-2900-530b-f23c91a70cca . _:0aa7c726-b027-2900-530b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-019b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-2 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-2 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b027-2901-530c-f23c91a70cca . _:0aa7c726-b027-2901-530c-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-019c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-2 Zone Temperature" ; ph:dis "Bravo VAV 1-2 Zone Temperature" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b027-2902-530d-f23c91a70cca . _:0aa7c726-b027-2902-530d-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-019d a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-20" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-20" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b027-2903-530e-f23c91a70cca . _:0aa7c726-b027-2903-530e-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 10.8 ; _:designHotWaterFlow 0.28 ; _:designAirFlow 800 . _:b-019e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-20 Damper Output" ; ph:dis "Bravo VAV 1-20 Damper Output" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b027-2904-530f-f23c91a70cca . _:0aa7c726-b027-2904-530f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-019f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-20 Discharge Air Flow" ; ph:dis "Bravo VAV 1-20 Discharge Air Flow" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b027-2905-5310-f23c91a70cca . _:0aa7c726-b027-2905-5310-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-01a0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-20 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-20 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b027-2906-5311-f23c91a70cca . _:0aa7c726-b027-2906-5311-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-01a1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-20 Heating Valve Output" ; ph:dis "Bravo VAV 1-20 Heating Valve Output" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b027-2907-5312-f23c91a70cca . _:0aa7c726-b027-2907-5312-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01a2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-20 Supply Air Temperature" ; ph:dis "Bravo VAV 1-20 Supply Air Temperature" ; phIoT:equipRef _:b-019d ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b027-2908-5313-f23c91a70cca . _:0aa7c726-b027-2908-5313-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01a3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-20 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-20 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b027-2909-5314-f23c91a70cca . _:0aa7c726-b027-2909-5314-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01a4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-20 Zone Temperature" ; ph:dis "Bravo VAV 1-20 Zone Temperature" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b027-290a-5315-f23c91a70cca . _:0aa7c726-b027-290a-5315-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-01a5 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-3" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-3" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b027-290b-5316-f23c91a70cca . _:0aa7c726-b027-290b-5316-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 83.5 ; _:designHotWaterFlow 12 ; _:designAirFlow 3000 . _:b-01a6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-3 Damper Output" ; ph:dis "Bravo VAV 1-3 Damper Output" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b027-290c-5317-f23c91a70cca . _:0aa7c726-b027-290c-5317-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01a7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-3 Discharge Air Flow" ; ph:dis "Bravo VAV 1-3 Discharge Air Flow" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b027-290d-5318-f23c91a70cca . _:0aa7c726-b027-290d-5318-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01a8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-3 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-3 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b027-290e-5319-f23c91a70cca . _:0aa7c726-b027-290e-5319-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-01a9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-3 Heating Valve Output" ; ph:dis "Bravo VAV 1-3 Heating Valve Output" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b027-290f-531a-f23c91a70cca . _:0aa7c726-b027-290f-531a-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-01aa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-3 Supply Air Humidity" ; ph:dis "Bravo VAV 1-3 Supply Air Humidity" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b027-2910-531b-f23c91a70cca . _:0aa7c726-b027-2910-531b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisChgrHumid" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01ab a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-3 Supply Air Temperature" ; ph:dis "Bravo VAV 1-3 Supply Air Temperature" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b027-2911-531c-f23c91a70cca . _:0aa7c726-b027-2911-531c-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01ac a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-3 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-3 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b027-2912-531d-f23c91a70cca . _:0aa7c726-b027-2912-531d-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01ad a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor, phIoT:zone ; rdfs:label "Bravo VAV 1-3 Zone Relative Humidity" ; ph:dis "Bravo VAV 1-3 Zone Relative Humidity" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b036-6b40-531e-f23c91a70cca . _:0aa7c726-b036-6b40-531e-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7237593125289187 ; _:sourcePointName "SpaceHum" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01ae a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-3 Zone Temperature" ; ph:dis "Bravo VAV 1-3 Zone Temperature" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b036-6b41-531f-f23c91a70cca . _:0aa7c726-b036-6b41-531f-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-01af a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-4" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-4" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b036-6b42-5320-f23c91a70cca . _:0aa7c726-b036-6b42-5320-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 3.8 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-01b0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-4 Damper Output" ; ph:dis "Bravo VAV 1-4 Damper Output" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b036-6b43-5321-f23c91a70cca . _:0aa7c726-b036-6b43-5321-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-01b1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-4 Discharge Air Flow" ; ph:dis "Bravo VAV 1-4 Discharge Air Flow" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b149-13c0-5322-f23c91a70cca . _:0aa7c726-b149-13c0-5322-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01b2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-4 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-4 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b149-13c1-5323-f23c91a70cca . _:0aa7c726-b149-13c1-5323-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01b3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-4 Heating Valve Output" ; ph:dis "Bravo VAV 1-4 Heating Valve Output" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b149-13c2-5324-f23c91a70cca . _:0aa7c726-b149-13c2-5324-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-01b4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-4 Supply Air Temperature" ; ph:dis "Bravo VAV 1-4 Supply Air Temperature" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b149-13c3-5325-f23c91a70cca . _:0aa7c726-b149-13c3-5325-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01b5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-4 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-4 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b149-13c4-5326-f23c91a70cca . _:0aa7c726-b149-13c4-5326-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-01b6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-4 Zone Temperature" ; ph:dis "Bravo VAV 1-4 Zone Temperature" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b149-13c5-5327-f23c91a70cca . _:0aa7c726-b149-13c5-5327-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-01b7 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-5" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-5" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b149-13c6-5328-f23c91a70cca . _:0aa7c726-b149-13c6-5328-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10.5 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 450 . _:b-01b8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-5 Damper Output" ; ph:dis "Bravo VAV 1-5 Damper Output" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b149-13c7-5329-f23c91a70cca . _:0aa7c726-b149-13c7-5329-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01b9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-5 Discharge Air Flow" ; ph:dis "Bravo VAV 1-5 Discharge Air Flow" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b149-13c8-532a-f23c91a70cca . _:0aa7c726-b149-13c8-532a-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01ba a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-5 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-5 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b149-13c9-532b-f23c91a70cca . _:0aa7c726-b149-13c9-532b-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01bb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-5 Heating Valve Output" ; ph:dis "Bravo VAV 1-5 Heating Valve Output" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b149-13ca-532c-f23c91a70cca . _:0aa7c726-b149-13ca-532c-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01bc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-5 Supply Air Temperature" ; ph:dis "Bravo VAV 1-5 Supply Air Temperature" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b149-13cb-532d-f23c91a70cca . _:0aa7c726-b149-13cb-532d-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01bd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-5 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-5 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b149-13cc-532e-f23c91a70cca . _:0aa7c726-b149-13cc-532e-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-01be a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-5 Zone Temperature" ; ph:dis "Bravo VAV 1-5 Zone Temperature" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b149-13cd-532f-f23c91a70cca . _:0aa7c726-b149-13cd-532f-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01bf a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-6" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-6" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b149-13ce-5330-f23c91a70cca . _:0aa7c726-b149-13ce-5330-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 83.5 ; _:designHotWaterFlow 12 ; _:designAirFlow 3000 . _:b-01c0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-6 Damper Output" ; ph:dis "Bravo VAV 1-6 Damper Output" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b158-5600-5331-f23c91a70cca . _:0aa7c726-b158-5600-5331-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01c1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-6 Discharge Air Flow" ; ph:dis "Bravo VAV 1-6 Discharge Air Flow" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b158-5601-5332-f23c91a70cca . _:0aa7c726-b158-5601-5332-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01c2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-6 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-6 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b158-5602-5333-f23c91a70cca . _:0aa7c726-b158-5602-5333-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-01c3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-6 Heating Valve Output" ; ph:dis "Bravo VAV 1-6 Heating Valve Output" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b158-5603-5334-f23c91a70cca . _:0aa7c726-b158-5603-5334-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01c4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-6 Supply Air Humidity" ; ph:dis "Bravo VAV 1-6 Supply Air Humidity" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b158-5604-5335-f23c91a70cca . _:0aa7c726-b158-5604-5335-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisChgrHumid" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01c5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-6 Supply Air Temperature" ; ph:dis "Bravo VAV 1-6 Supply Air Temperature" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b158-5605-5336-f23c91a70cca . _:0aa7c726-b158-5605-5336-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01c6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-6 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-6 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b158-5606-5337-f23c91a70cca . _:0aa7c726-b158-5606-5337-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-01c7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor, phIoT:zone ; rdfs:label "Bravo VAV 1-6 Zone Relative Humidity" ; ph:dis "Bravo VAV 1-6 Zone Relative Humidity" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b158-5607-5338-f23c91a70cca . _:0aa7c726-b158-5607-5338-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpaceHum" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-01c8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-6 Zone Temperature" ; ph:dis "Bravo VAV 1-6 Zone Temperature" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b158-5608-5339-f23c91a70cca . _:0aa7c726-b158-5608-5339-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01c9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-7" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-7" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b158-5609-533a-f23c91a70cca . _:0aa7c726-b158-5609-533a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 7.6 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 450 . _:b-01ca a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-7 Damper Output" ; ph:dis "Bravo VAV 1-7 Damper Output" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b158-560a-533b-f23c91a70cca . _:0aa7c726-b158-560a-533b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01cb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-7 Discharge Air Flow" ; ph:dis "Bravo VAV 1-7 Discharge Air Flow" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b158-560b-533c-f23c91a70cca . _:0aa7c726-b158-560b-533c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01cc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-7 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-7 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b158-560c-533d-f23c91a70cca . _:0aa7c726-b158-560c-533d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01cd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-7 Heating Valve Output" ; ph:dis "Bravo VAV 1-7 Heating Valve Output" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b158-560d-533e-f23c91a70cca . _:0aa7c726-b158-560d-533e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01ce a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-7 Supply Air Temperature" ; ph:dis "Bravo VAV 1-7 Supply Air Temperature" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b158-560e-533f-f23c91a70cca . _:0aa7c726-b158-560e-533f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01cf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-7 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-7 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b158-560f-5340-f23c91a70cca . _:0aa7c726-b158-560f-5340-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01d0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-7 Zone Temperature" ; ph:dis "Bravo VAV 1-7 Zone Temperature" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b158-5610-5341-f23c91a70cca . _:0aa7c726-b158-5610-5341-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01d1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-8" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-8" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b158-5611-5342-f23c91a70cca . _:0aa7c726-b158-5611-5342-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 4.8 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-01d2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-8 Damper Output" ; ph:dis "Bravo VAV 1-8 Damper Output" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b167-9840-5343-f23c91a70cca . _:0aa7c726-b167-9840-5343-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01d3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-8 Discharge Air Flow" ; ph:dis "Bravo VAV 1-8 Discharge Air Flow" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b167-9841-5344-f23c91a70cca . _:0aa7c726-b167-9841-5344-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01d4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-8 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-8 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b167-9842-5345-f23c91a70cca . _:0aa7c726-b167-9842-5345-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01d5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-8 Heating Valve Output" ; ph:dis "Bravo VAV 1-8 Heating Valve Output" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b167-9843-5346-f23c91a70cca . _:0aa7c726-b167-9843-5346-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01d6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-8 Supply Air Temperature" ; ph:dis "Bravo VAV 1-8 Supply Air Temperature" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b167-9844-5347-f23c91a70cca . _:0aa7c726-b167-9844-5347-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01d7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-8 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-8 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b167-9845-5348-f23c91a70cca . _:0aa7c726-b167-9845-5348-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01d8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-8 Zone Temperature" ; ph:dis "Bravo VAV 1-8 Zone Temperature" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b167-9846-5349-f23c91a70cca . _:0aa7c726-b167-9846-5349-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01d9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-9" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-9" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b167-9847-534a-f23c91a70cca . _:0aa7c726-b167-9847-534a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 15.3 ; _:designHotWaterFlow 1.75 ; _:designAirFlow 875 . _:b-01da a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-9 Damper Output" ; ph:dis "Bravo VAV 1-9 Damper Output" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b167-9848-534b-f23c91a70cca . _:0aa7c726-b167-9848-534b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01db a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-9 Discharge Air Flow" ; ph:dis "Bravo VAV 1-9 Discharge Air Flow" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b167-9849-534c-f23c91a70cca . _:0aa7c726-b167-9849-534c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01dc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-9 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-9 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b167-984a-534d-f23c91a70cca . _:0aa7c726-b167-984a-534d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01dd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-9 Heating Valve Output" ; ph:dis "Bravo VAV 1-9 Heating Valve Output" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b167-984b-534e-f23c91a70cca . _:0aa7c726-b167-984b-534e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-01de a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-9 Supply Air Temperature" ; ph:dis "Bravo VAV 1-9 Supply Air Temperature" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b167-984c-534f-f23c91a70cca . _:0aa7c726-b167-984c-534f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01df a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-9 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-9 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b167-984d-5350-f23c91a70cca . _:0aa7c726-b167-984d-5350-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01e0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-9 Zone Temperature" ; ph:dis "Bravo VAV 1-9 Zone Temperature" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b167-984e-5351-f23c91a70cca . _:0aa7c726-b167-984e-5351-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01e1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-1" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-1" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b167-984f-5352-f23c91a70cca . _:0aa7c726-b167-984f-5352-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-01e2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-1 Damper Output" ; ph:dis "Bravo VAV 2-1 Damper Output" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b167-9850-5353-f23c91a70cca . _:0aa7c726-b167-9850-5353-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01e3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-1 Discharge Air Flow" ; ph:dis "Bravo VAV 2-1 Discharge Air Flow" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b176-da80-5354-f23c91a70cca . _:0aa7c726-b176-da80-5354-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01e4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-1 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-1 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b176-da81-5355-f23c91a70cca . _:0aa7c726-b176-da81-5355-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01e5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-1 Heating Valve Output" ; ph:dis "Bravo VAV 2-1 Heating Valve Output" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b176-da82-5356-f23c91a70cca . _:0aa7c726-b176-da82-5356-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01e6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-1 Supply Air Temperature" ; ph:dis "Bravo VAV 2-1 Supply Air Temperature" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b176-da83-5357-f23c91a70cca . _:0aa7c726-b176-da83-5357-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01e7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-1 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-1 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b176-da84-5358-f23c91a70cca . _:0aa7c726-b176-da84-5358-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-01e8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-1 Zone Temperature" ; ph:dis "Bravo VAV 2-1 Zone Temperature" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b176-da85-5359-f23c91a70cca . _:0aa7c726-b176-da85-5359-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01e9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-10" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-10" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b176-da86-535a-f23c91a70cca . _:0aa7c726-b176-da86-535a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 4.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 175 . _:b-01ea a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-10 Damper Output" ; ph:dis "Bravo VAV 2-10 Damper Output" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b176-da87-535b-f23c91a70cca . _:0aa7c726-b176-da87-535b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01eb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-10 Discharge Air Flow" ; ph:dis "Bravo VAV 2-10 Discharge Air Flow" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b176-da88-535c-f23c91a70cca . _:0aa7c726-b176-da88-535c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-01ec a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-10 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-10 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b176-da89-535d-f23c91a70cca . _:0aa7c726-b176-da89-535d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-01ed a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-10 Heating Valve Output" ; ph:dis "Bravo VAV 2-10 Heating Valve Output" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b176-da8a-535e-f23c91a70cca . _:0aa7c726-b176-da8a-535e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-01ee a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-10 Supply Air Temperature" ; ph:dis "Bravo VAV 2-10 Supply Air Temperature" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b176-da8b-535f-f23c91a70cca . _:0aa7c726-b176-da8b-535f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01ef a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-10 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-10 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b176-da8c-5360-f23c91a70cca . _:0aa7c726-b176-da8c-5360-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-01f0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-10 Zone Temperature" ; ph:dis "Bravo VAV 2-10 Zone Temperature" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b176-da8d-5361-f23c91a70cca . _:0aa7c726-b176-da8d-5361-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01f1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-11" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-11" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b176-da8e-5362-f23c91a70cca . _:0aa7c726-b176-da8e-5362-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-01f2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-11 Damper Output" ; ph:dis "Bravo VAV 2-11 Damper Output" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b176-da8f-5363-f23c91a70cca . _:0aa7c726-b176-da8f-5363-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01f3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-11 Discharge Air Flow" ; ph:dis "Bravo VAV 2-11 Discharge Air Flow" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b176-da90-5364-f23c91a70cca . _:0aa7c726-b176-da90-5364-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01f4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-11 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-11 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b176-da91-5365-f23c91a70cca . _:0aa7c726-b176-da91-5365-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01f5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-11 Heating Valve Output" ; ph:dis "Bravo VAV 2-11 Heating Valve Output" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b176-da92-5366-f23c91a70cca . _:0aa7c726-b176-da92-5366-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01f6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-11 Supply Air Temperature" ; ph:dis "Bravo VAV 2-11 Supply Air Temperature" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b186-1cc0-5367-f23c91a70cca . _:0aa7c726-b186-1cc0-5367-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-01f7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-11 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-11 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b186-1cc1-5368-f23c91a70cca . _:0aa7c726-b186-1cc1-5368-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01f8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-11 Zone Temperature" ; ph:dis "Bravo VAV 2-11 Zone Temperature" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b186-1cc2-5369-f23c91a70cca . _:0aa7c726-b186-1cc2-5369-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01f9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-12" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-12" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b186-1cc3-536a-f23c91a70cca . _:0aa7c726-b186-1cc3-536a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 4.6 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 250 . _:b-01fa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-12 Damper Output" ; ph:dis "Bravo VAV 2-12 Damper Output" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b186-1cc4-536b-f23c91a70cca . _:0aa7c726-b186-1cc4-536b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01fb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-12 Discharge Air Flow" ; ph:dis "Bravo VAV 2-12 Discharge Air Flow" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b186-1cc5-536c-f23c91a70cca . _:0aa7c726-b186-1cc5-536c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01fc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-12 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-12 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b186-1cc6-536d-f23c91a70cca . _:0aa7c726-b186-1cc6-536d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01fd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-12 Heating Valve Output" ; ph:dis "Bravo VAV 2-12 Heating Valve Output" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b186-1cc7-536e-f23c91a70cca . _:0aa7c726-b186-1cc7-536e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01fe a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-12 Supply Air Temperature" ; ph:dis "Bravo VAV 2-12 Supply Air Temperature" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b186-1cc8-536f-f23c91a70cca . _:0aa7c726-b186-1cc8-536f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01ff a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-12 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-12 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b186-1cc9-5370-f23c91a70cca . _:0aa7c726-b186-1cc9-5370-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0200 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-12 Zone Temperature" ; ph:dis "Bravo VAV 2-12 Zone Temperature" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b186-1cca-5371-f23c91a70cca . _:0aa7c726-b186-1cca-5371-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0201 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-13" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-13" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b186-1ccb-5372-f23c91a70cca . _:0aa7c726-b186-1ccb-5372-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0202 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-13 Damper Output" ; ph:dis "Bravo VAV 2-13 Damper Output" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b186-1ccc-5373-f23c91a70cca . _:0aa7c726-b186-1ccc-5373-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0203 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-13 Discharge Air Flow" ; ph:dis "Bravo VAV 2-13 Discharge Air Flow" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b186-1ccd-5374-f23c91a70cca . _:0aa7c726-b186-1ccd-5374-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0204 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-13 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-13 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b186-1cce-5375-f23c91a70cca . _:0aa7c726-b186-1cce-5375-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0205 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-13 Heating Valve Output" ; ph:dis "Bravo VAV 2-13 Heating Valve Output" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b186-1ccf-5376-f23c91a70cca . _:0aa7c726-b186-1ccf-5376-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0206 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-13 Supply Air Temperature" ; ph:dis "Bravo VAV 2-13 Supply Air Temperature" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b186-1cd0-5377-f23c91a70cca . _:0aa7c726-b186-1cd0-5377-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0207 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-13 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-13 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b186-1cd1-5378-f23c91a70cca . _:0aa7c726-b186-1cd1-5378-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0208 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-13 Zone Temperature" ; ph:dis "Bravo VAV 2-13 Zone Temperature" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b186-1cd2-5379-f23c91a70cca . _:0aa7c726-b186-1cd2-5379-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0209 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-14" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-14" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b195-5f00-537a-f23c91a70cca . _:0aa7c726-b195-5f00-537a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 24.2 ; _:designHotWaterFlow 2.5 ; _:designAirFlow 1450 . _:b-020a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-14 Damper Output" ; ph:dis "Bravo VAV 2-14 Damper Output" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b195-5f01-537b-f23c91a70cca . _:0aa7c726-b195-5f01-537b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-020b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-14 Discharge Air Flow" ; ph:dis "Bravo VAV 2-14 Discharge Air Flow" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b195-5f02-537c-f23c91a70cca . _:0aa7c726-b195-5f02-537c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-020c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-14 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-14 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b195-5f03-537d-f23c91a70cca . _:0aa7c726-b195-5f03-537d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-020d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-14 Heating Valve Output" ; ph:dis "Bravo VAV 2-14 Heating Valve Output" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b195-5f04-537e-f23c91a70cca . _:0aa7c726-b195-5f04-537e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-020e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-14 Supply Air Temperature" ; ph:dis "Bravo VAV 2-14 Supply Air Temperature" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b195-5f05-537f-f23c91a70cca . _:0aa7c726-b195-5f05-537f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-020f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-14 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-14 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b195-5f06-5380-f23c91a70cca . _:0aa7c726-b195-5f06-5380-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0210 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-14 Zone Temperature" ; ph:dis "Bravo VAV 2-14 Zone Temperature" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b195-5f07-5381-f23c91a70cca . _:0aa7c726-b195-5f07-5381-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0211 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-15" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-15" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b195-5f08-5382-f23c91a70cca . _:0aa7c726-b195-5f08-5382-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.7 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-0212 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-15 Damper Output" ; ph:dis "Bravo VAV 2-15 Damper Output" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b195-5f09-5383-f23c91a70cca . _:0aa7c726-b195-5f09-5383-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0213 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-15 Discharge Air Flow" ; ph:dis "Bravo VAV 2-15 Discharge Air Flow" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b195-5f0a-5384-f23c91a70cca . _:0aa7c726-b195-5f0a-5384-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0214 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-15 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-15 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b195-5f0b-5385-f23c91a70cca . _:0aa7c726-b195-5f0b-5385-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0215 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-15 Heating Valve Output" ; ph:dis "Bravo VAV 2-15 Heating Valve Output" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b195-5f0c-5386-f23c91a70cca . _:0aa7c726-b195-5f0c-5386-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0216 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-15 Supply Air Temperature" ; ph:dis "Bravo VAV 2-15 Supply Air Temperature" ; phIoT:equipRef _:b-0211 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b195-5f0d-5387-f23c91a70cca . _:0aa7c726-b195-5f0d-5387-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0217 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-15 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-15 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b195-5f0e-5388-f23c91a70cca . _:0aa7c726-b195-5f0e-5388-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0218 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-15 Zone Temperature" ; ph:dis "Bravo VAV 2-15 Zone Temperature" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b195-5f0f-5389-f23c91a70cca . _:0aa7c726-b195-5f0f-5389-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0219 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-16" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-16" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b195-5f10-538a-f23c91a70cca . _:0aa7c726-b195-5f10-538a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-021a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-16 Damper Output" ; ph:dis "Bravo VAV 2-16 Damper Output" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b195-5f11-538b-f23c91a70cca . _:0aa7c726-b195-5f11-538b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-021b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-16 Discharge Air Flow" ; ph:dis "Bravo VAV 2-16 Discharge Air Flow" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b195-5f12-538c-f23c91a70cca . _:0aa7c726-b195-5f12-538c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-021c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-16 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-16 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b1a4-a140-538d-f23c91a70cca . _:0aa7c726-b1a4-a140-538d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-021d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-16 Heating Valve Output" ; ph:dis "Bravo VAV 2-16 Heating Valve Output" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b1a4-a141-538e-f23c91a70cca . _:0aa7c726-b1a4-a141-538e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-021e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-16 Supply Air Temperature" ; ph:dis "Bravo VAV 2-16 Supply Air Temperature" ; phIoT:equipRef _:b-0219 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1a4-a142-538f-f23c91a70cca . _:0aa7c726-b1a4-a142-538f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-021f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-16 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-16 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1a4-a143-5390-f23c91a70cca . _:0aa7c726-b1a4-a143-5390-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0220 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-16 Zone Temperature" ; ph:dis "Bravo VAV 2-16 Zone Temperature" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1a4-a144-5391-f23c91a70cca . _:0aa7c726-b1a4-a144-5391-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0221 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-17" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-17" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b1a4-a145-5392-f23c91a70cca . _:0aa7c726-b1a4-a145-5392-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-0222 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-17 Damper Output" ; ph:dis "Bravo VAV 2-17 Damper Output" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b1d2-6800-5393-f23c91a70cca . _:0aa7c726-b1d2-6800-5393-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0223 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-17 Discharge Air Flow" ; ph:dis "Bravo VAV 2-17 Discharge Air Flow" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b1d2-6801-5394-f23c91a70cca . _:0aa7c726-b1d2-6801-5394-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0224 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-17 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-17 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b1d2-6802-5395-f23c91a70cca . _:0aa7c726-b1d2-6802-5395-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0225 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-17 Heating Valve Output" ; ph:dis "Bravo VAV 2-17 Heating Valve Output" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b1d2-6803-5396-f23c91a70cca . _:0aa7c726-b1d2-6803-5396-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0226 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-17 Supply Air Temperature" ; ph:dis "Bravo VAV 2-17 Supply Air Temperature" ; phIoT:equipRef _:b-0221 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1e1-aa40-5397-f23c91a70cca . _:0aa7c726-b1e1-aa40-5397-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0227 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-17 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-17 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1e1-aa41-5398-f23c91a70cca . _:0aa7c726-b1e1-aa41-5398-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0228 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-17 Zone Temperature" ; ph:dis "Bravo VAV 2-17 Zone Temperature" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1e1-aa42-5399-f23c91a70cca . _:0aa7c726-b1e1-aa42-5399-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0229 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-18" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-18" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b1e1-aa43-539a-f23c91a70cca . _:0aa7c726-b1e1-aa43-539a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 15 ; _:designHotWaterFlow 1.75 ; _:designAirFlow 550 . _:b-022a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-18 Damper Output" ; ph:dis "Bravo VAV 2-18 Damper Output" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b1e1-aa44-539b-f23c91a70cca . _:0aa7c726-b1e1-aa44-539b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-022b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-18 Discharge Air Flow" ; ph:dis "Bravo VAV 2-18 Discharge Air Flow" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b1e1-aa45-539c-f23c91a70cca . _:0aa7c726-b1e1-aa45-539c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-022c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-18 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-18 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b1e1-aa46-539d-f23c91a70cca . _:0aa7c726-b1e1-aa46-539d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-022d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-18 Heating Valve Output" ; ph:dis "Bravo VAV 2-18 Heating Valve Output" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b1e1-aa47-539e-f23c91a70cca . _:0aa7c726-b1e1-aa47-539e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-022e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-18 Supply Air Temperature" ; ph:dis "Bravo VAV 2-18 Supply Air Temperature" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1e1-aa48-539f-f23c91a70cca . _:0aa7c726-b1e1-aa48-539f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-022f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-18 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-18 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1e1-aa49-53a0-f23c91a70cca . _:0aa7c726-b1e1-aa49-53a0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0230 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-18 Zone Temperature" ; ph:dis "Bravo VAV 2-18 Zone Temperature" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1e1-aa4a-53a1-f23c91a70cca . _:0aa7c726-b1e1-aa4a-53a1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0231 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-19" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-19" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b1e1-aa4b-53a2-f23c91a70cca . _:0aa7c726-b1e1-aa4b-53a2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6.2 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-0232 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-19 Damper Output" ; ph:dis "Bravo VAV 2-19 Damper Output" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b1e1-aa4c-53a3-f23c91a70cca . _:0aa7c726-b1e1-aa4c-53a3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0233 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-19 Discharge Air Flow" ; ph:dis "Bravo VAV 2-19 Discharge Air Flow" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b1e1-aa4d-53a4-f23c91a70cca . _:0aa7c726-b1e1-aa4d-53a4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0234 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-19 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-19 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b1e1-aa4e-53a5-f23c91a70cca . _:0aa7c726-b1e1-aa4e-53a5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0235 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-19 Heating Valve Output" ; ph:dis "Bravo VAV 2-19 Heating Valve Output" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b1e1-aa4f-53a6-f23c91a70cca . _:0aa7c726-b1e1-aa4f-53a6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0236 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-19 Supply Air Temperature" ; ph:dis "Bravo VAV 2-19 Supply Air Temperature" ; phIoT:equipRef _:b-0231 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1e1-aa50-53a7-f23c91a70cca . _:0aa7c726-b1e1-aa50-53a7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0237 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-19 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-19 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1e1-aa51-53a8-f23c91a70cca . _:0aa7c726-b1e1-aa51-53a8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0238 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-19 Zone Temperature" ; ph:dis "Bravo VAV 2-19 Zone Temperature" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1f0-ec80-53a9-f23c91a70cca . _:0aa7c726-b1f0-ec80-53a9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0239 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-2" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-2" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b1f0-ec81-53aa-f23c91a70cca . _:0aa7c726-b1f0-ec81-53aa-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.6 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 650 . _:b-023a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-2 Damper Output" ; ph:dis "Bravo VAV 2-2 Damper Output" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b1f0-ec82-53ab-f23c91a70cca . _:0aa7c726-b1f0-ec82-53ab-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-023b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-2 Discharge Air Flow" ; ph:dis "Bravo VAV 2-2 Discharge Air Flow" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b1f0-ec83-53ac-f23c91a70cca . _:0aa7c726-b1f0-ec83-53ac-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-023c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-2 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-2 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b1f0-ec84-53ad-f23c91a70cca . _:0aa7c726-b1f0-ec84-53ad-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-023d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-2 Heating Valve Output" ; ph:dis "Bravo VAV 2-2 Heating Valve Output" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b1f0-ec85-53ae-f23c91a70cca . _:0aa7c726-b1f0-ec85-53ae-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-023e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-2 Supply Air Temperature" ; ph:dis "Bravo VAV 2-2 Supply Air Temperature" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1f0-ec86-53af-f23c91a70cca . _:0aa7c726-b1f0-ec86-53af-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-023f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-2 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-2 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1f0-ec87-53b0-f23c91a70cca . _:0aa7c726-b1f0-ec87-53b0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0240 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-2 Zone Temperature" ; ph:dis "Bravo VAV 2-2 Zone Temperature" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1f0-ec88-53b1-f23c91a70cca . _:0aa7c726-b1f0-ec88-53b1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0241 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-20" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-20" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b1f0-ec89-53b2-f23c91a70cca . _:0aa7c726-b1f0-ec89-53b2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10.8 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 650 . _:b-0242 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-20 Damper Output" ; ph:dis "Bravo VAV 2-20 Damper Output" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b1f0-ec8a-53b3-f23c91a70cca . _:0aa7c726-b1f0-ec8a-53b3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0243 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-20 Discharge Air Flow" ; ph:dis "Bravo VAV 2-20 Discharge Air Flow" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b1f0-ec8b-53b4-f23c91a70cca . _:0aa7c726-b1f0-ec8b-53b4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0244 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-20 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-20 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b1f0-ec8c-53b5-f23c91a70cca . _:0aa7c726-b1f0-ec8c-53b5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0245 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-20 Heating Valve Output" ; ph:dis "Bravo VAV 2-20 Heating Valve Output" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b1f0-ec8d-53b6-f23c91a70cca . _:0aa7c726-b1f0-ec8d-53b6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0246 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-20 Supply Air Temperature" ; ph:dis "Bravo VAV 2-20 Supply Air Temperature" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1f0-ec8e-53b7-f23c91a70cca . _:0aa7c726-b1f0-ec8e-53b7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0247 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-20 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-20 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1f0-ec8f-53b8-f23c91a70cca . _:0aa7c726-b1f0-ec8f-53b8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0248 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-20 Zone Temperature" ; ph:dis "Bravo VAV 2-20 Zone Temperature" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b1f0-ec90-53b9-f23c91a70cca . _:0aa7c726-b1f0-ec90-53b9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0249 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-21" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-21" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b1f0-ec91-53ba-f23c91a70cca . _:0aa7c726-b1f0-ec91-53ba-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 10.4 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 650 . _:b-024a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-21 Damper Output" ; ph:dis "Bravo VAV 2-21 Damper Output" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b1f0-ec92-53bb-f23c91a70cca . _:0aa7c726-b1f0-ec92-53bb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-024b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-21 Discharge Air Flow" ; ph:dis "Bravo VAV 2-21 Discharge Air Flow" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b1f0-ec93-53bc-f23c91a70cca . _:0aa7c726-b1f0-ec93-53bc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-024c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-21 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-21 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b200-2ec0-53bd-f23c91a70cca . _:0aa7c726-b200-2ec0-53bd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-024d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-21 Heating Valve Output" ; ph:dis "Bravo VAV 2-21 Heating Valve Output" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b200-2ec1-53be-f23c91a70cca . _:0aa7c726-b200-2ec1-53be-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-024e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-21 Supply Air Temperature" ; ph:dis "Bravo VAV 2-21 Supply Air Temperature" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b200-2ec2-53bf-f23c91a70cca . _:0aa7c726-b200-2ec2-53bf-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-024f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-21 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-21 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b200-2ec3-53c0-f23c91a70cca . _:0aa7c726-b200-2ec3-53c0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0250 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-21 Zone Temperature" ; ph:dis "Bravo VAV 2-21 Zone Temperature" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b200-2ec4-53c1-f23c91a70cca . _:0aa7c726-b200-2ec4-53c1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0251 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-22" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-22" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b200-2ec5-53c2-f23c91a70cca . _:0aa7c726-b200-2ec5-53c2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0252 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-22 Damper Output" ; ph:dis "Bravo VAV 2-22 Damper Output" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b200-2ec6-53c3-f23c91a70cca . _:0aa7c726-b200-2ec6-53c3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0253 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-22 Discharge Air Flow" ; ph:dis "Bravo VAV 2-22 Discharge Air Flow" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b200-2ec7-53c4-f23c91a70cca . _:0aa7c726-b200-2ec7-53c4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0254 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-22 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-22 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b200-2ec8-53c5-f23c91a70cca . _:0aa7c726-b200-2ec8-53c5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0255 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-22 Heating Valve Output" ; ph:dis "Bravo VAV 2-22 Heating Valve Output" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b200-2ec9-53c6-f23c91a70cca . _:0aa7c726-b200-2ec9-53c6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0256 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-22 Supply Air Temperature" ; ph:dis "Bravo VAV 2-22 Supply Air Temperature" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b200-2eca-53c7-f23c91a70cca . _:0aa7c726-b200-2eca-53c7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0257 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-22 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-22 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b200-2ecb-53c8-f23c91a70cca . _:0aa7c726-b200-2ecb-53c8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0258 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-22 Zone Temperature" ; ph:dis "Bravo VAV 2-22 Zone Temperature" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b200-2ecc-53c9-f23c91a70cca . _:0aa7c726-b200-2ecc-53c9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0259 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-23" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-23" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b200-2ecd-53ca-f23c91a70cca . _:0aa7c726-b200-2ecd-53ca-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 6.2 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-025a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-23 Damper Output" ; ph:dis "Bravo VAV 2-23 Damper Output" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b200-2ece-53cb-f23c91a70cca . _:0aa7c726-b200-2ece-53cb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-025b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-23 Discharge Air Flow" ; ph:dis "Bravo VAV 2-23 Discharge Air Flow" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b200-2ecf-53cc-f23c91a70cca . _:0aa7c726-b200-2ecf-53cc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-025c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-23 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-23 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b200-2ed0-53cd-f23c91a70cca . _:0aa7c726-b200-2ed0-53cd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-025d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-23 Heating Valve Output" ; ph:dis "Bravo VAV 2-23 Heating Valve Output" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b200-2ed1-53ce-f23c91a70cca . _:0aa7c726-b200-2ed1-53ce-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-025e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-23 Supply Air Temperature" ; ph:dis "Bravo VAV 2-23 Supply Air Temperature" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b200-2ed2-53cf-f23c91a70cca . _:0aa7c726-b200-2ed2-53cf-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-025f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-23 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-23 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b23d-37c0-53d0-f23c91a70cca . _:0aa7c726-b23d-37c0-53d0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0260 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-23 Zone Temperature" ; ph:dis "Bravo VAV 2-23 Zone Temperature" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b23d-37c1-53d1-f23c91a70cca . _:0aa7c726-b23d-37c1-53d1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0261 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-24" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-24" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b23d-37c2-53d2-f23c91a70cca . _:0aa7c726-b23d-37c2-53d2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 15.4 ; _:designHotWaterFlow 2.5 ; _:designAirFlow 1600 . _:b-0262 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-24 Damper Output" ; ph:dis "Bravo VAV 2-24 Damper Output" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b23d-37c3-53d3-f23c91a70cca . _:0aa7c726-b23d-37c3-53d3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0263 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-24 Discharge Air Flow" ; ph:dis "Bravo VAV 2-24 Discharge Air Flow" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b23d-37c4-53d4-f23c91a70cca . _:0aa7c726-b23d-37c4-53d4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0264 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-24 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-24 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b23d-37c5-53d5-f23c91a70cca . _:0aa7c726-b23d-37c5-53d5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0265 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-24 Heating Valve" ; ph:dis "Bravo VAV 2-24 Heating Valve" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b23d-37c6-53d6-f23c91a70cca . _:0aa7c726-b23d-37c6-53d6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0266 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-24 Supply Air Temperature" ; ph:dis "Bravo VAV 2-24 Supply Air Temperature" ; phIoT:equipRef _:b-0261 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b23d-37c7-53d7-f23c91a70cca . _:0aa7c726-b23d-37c7-53d7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0267 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-24 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-24 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b23d-37c8-53d8-f23c91a70cca . _:0aa7c726-b23d-37c8-53d8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0268 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-24 Zone Temperature" ; ph:dis "Bravo VAV 2-24 Zone Temperature" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b23d-37c9-53d9-f23c91a70cca . _:0aa7c726-b23d-37c9-53d9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0269 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-25" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-25" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b24c-7a00-53da-f23c91a70cca . _:0aa7c726-b24c-7a00-53da-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 4.4 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 250 . _:b-026a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-25 Damper Output" ; ph:dis "Bravo VAV 2-25 Damper Output" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b24c-7a01-53db-f23c91a70cca . _:0aa7c726-b24c-7a01-53db-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-026b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-25 Discharge Air Flow" ; ph:dis "Bravo VAV 2-25 Discharge Air Flow" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b24c-7a02-53dc-f23c91a70cca . _:0aa7c726-b24c-7a02-53dc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-026c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-25 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-25 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b24c-7a03-53dd-f23c91a70cca . _:0aa7c726-b24c-7a03-53dd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-026d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-25 Heating Valve Output" ; ph:dis "Bravo VAV 2-25 Heating Valve Output" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b24c-7a04-53de-f23c91a70cca . _:0aa7c726-b24c-7a04-53de-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-026e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-25 Supply Air Temperature" ; ph:dis "Bravo VAV 2-25 Supply Air Temperature" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b24c-7a05-53df-f23c91a70cca . _:0aa7c726-b24c-7a05-53df-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-026f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-25 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-25 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b24c-7a06-53e0-f23c91a70cca . _:0aa7c726-b24c-7a06-53e0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0270 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-25 Zone Temperature" ; ph:dis "Bravo VAV 2-25 Zone Temperature" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b24c-7a07-53e1-f23c91a70cca . _:0aa7c726-b24c-7a07-53e1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0271 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-26" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-26" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b24c-7a08-53e2-f23c91a70cca . _:0aa7c726-b24c-7a08-53e2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 4.2 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 300 . _:b-0272 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-26 Damper Output" ; ph:dis "Bravo VAV 2-26 Damper Output" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b24c-7a09-53e3-f23c91a70cca . _:0aa7c726-b24c-7a09-53e3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0273 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-26 Discharge Air Flow" ; ph:dis "Bravo VAV 2-26 Discharge Air Flow" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b24c-7a0a-53e4-f23c91a70cca . _:0aa7c726-b24c-7a0a-53e4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0274 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-26 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-26 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b24c-7a0b-53e5-f23c91a70cca . _:0aa7c726-b24c-7a0b-53e5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0275 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-26 Heating Valve Output" ; ph:dis "Bravo VAV 2-26 Heating Valve Output" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b24c-7a0c-53e6-f23c91a70cca . _:0aa7c726-b24c-7a0c-53e6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0276 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-26 Supply Air Temperature" ; ph:dis "Bravo VAV 2-26 Supply Air Temperature" ; phIoT:equipRef _:b-0271 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b24c-7a0d-53e7-f23c91a70cca . _:0aa7c726-b24c-7a0d-53e7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0277 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-26 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-26 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b24c-7a0e-53e8-f23c91a70cca . _:0aa7c726-b24c-7a0e-53e8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0278 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-26 Zone Temperature" ; ph:dis "Bravo VAV 2-26 Zone Temperature" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b24c-7a0f-53e9-f23c91a70cca . _:0aa7c726-b24c-7a0f-53e9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0279 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-27" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-27" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b24c-7a10-53ea-f23c91a70cca . _:0aa7c726-b24c-7a10-53ea-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 18.6 ; _:designHotWaterFlow 2 ; _:designAirFlow 1125 . _:b-027a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-27 Damper Output" ; ph:dis "Bravo VAV 2-27 Damper Output" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b24c-7a11-53eb-f23c91a70cca . _:0aa7c726-b24c-7a11-53eb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-027b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-27 Discharge Air Flow" ; ph:dis "Bravo VAV 2-27 Discharge Air Flow" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b24c-7a12-53ec-f23c91a70cca . _:0aa7c726-b24c-7a12-53ec-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-027c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-27 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-27 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b25b-bc40-53ed-f23c91a70cca . _:0aa7c726-b25b-bc40-53ed-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-027d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-27 Heating Valve Output" ; ph:dis "Bravo VAV 2-27 Heating Valve Output" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b25b-bc41-53ee-f23c91a70cca . _:0aa7c726-b25b-bc41-53ee-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-027e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-27 Supply Air Temperature" ; ph:dis "Bravo VAV 2-27 Supply Air Temperature" ; phIoT:equipRef _:b-0279 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b25b-bc42-53ef-f23c91a70cca . _:0aa7c726-b25b-bc42-53ef-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-027f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-27 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-27 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b25b-bc43-53f0-f23c91a70cca . _:0aa7c726-b25b-bc43-53f0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0280 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-27 Zone Temperature" ; ph:dis "Bravo VAV 2-27 Zone Temperature" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b25b-bc44-53f1-f23c91a70cca . _:0aa7c726-b25b-bc44-53f1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0281 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-28" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-28" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b25b-bc45-53f2-f23c91a70cca . _:0aa7c726-b25b-bc45-53f2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-0282 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-28 Damper Output" ; ph:dis "Bravo VAV 2-28 Damper Output" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b25b-bc46-53f3-f23c91a70cca . _:0aa7c726-b25b-bc46-53f3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0283 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-28 Discharge Air Flow" ; ph:dis "Bravo VAV 2-28 Discharge Air Flow" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b25b-bc47-53f4-f23c91a70cca . _:0aa7c726-b25b-bc47-53f4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0284 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-28 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-28 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b25b-bc48-53f5-f23c91a70cca . _:0aa7c726-b25b-bc48-53f5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0285 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-28 Heating Valve Output" ; ph:dis "Bravo VAV 2-28 Heating Valve Output" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b25b-bc49-53f6-f23c91a70cca . _:0aa7c726-b25b-bc49-53f6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0286 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-28 Supply Air Temperature" ; ph:dis "Bravo VAV 2-28 Supply Air Temperature" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b25b-bc4a-53f7-f23c91a70cca . _:0aa7c726-b25b-bc4a-53f7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0287 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-28 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-28 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b25b-bc4b-53f8-f23c91a70cca . _:0aa7c726-b25b-bc4b-53f8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0288 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-28 Zone Temperature" ; ph:dis "Bravo VAV 2-28 Zone Temperature" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b25b-bc4c-53f9-f23c91a70cca . _:0aa7c726-b25b-bc4c-53f9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0289 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-29" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-29" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b25b-bc4d-53fa-f23c91a70cca . _:0aa7c726-b25b-bc4d-53fa-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-028a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-29 Damper Output" ; ph:dis "Bravo VAV 2-29 Damper Output" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b25b-bc4e-53fb-f23c91a70cca . _:0aa7c726-b25b-bc4e-53fb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-028b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-29 Discharge Air Flow" ; ph:dis "Bravo VAV 2-29 Discharge Air Flow" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b25b-bc4f-53fc-f23c91a70cca . _:0aa7c726-b25b-bc4f-53fc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-028c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-29 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-29 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b25b-bc50-53fd-f23c91a70cca . _:0aa7c726-b25b-bc50-53fd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-028d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-29 Heating Valve Output" ; ph:dis "Bravo VAV 2-29 Heating Valve Output" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b25b-bc51-53fe-f23c91a70cca . _:0aa7c726-b25b-bc51-53fe-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-028e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-29 Supply Air Temperature" ; ph:dis "Bravo VAV 2-29 Supply Air Temperature" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b25b-bc52-53ff-f23c91a70cca . _:0aa7c726-b25b-bc52-53ff-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-028f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-29 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-29 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b26a-fe80-5400-f23c91a70cca . _:0aa7c726-b26a-fe80-5400-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0290 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-29 Zone Temperature" ; ph:dis "Bravo VAV 2-29 Zone Temperature" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b26a-fe81-5401-f23c91a70cca . _:0aa7c726-b26a-fe81-5401-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0291 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-3" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-3" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b26a-fe82-5402-f23c91a70cca . _:0aa7c726-b26a-fe82-5402-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0292 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-3 Damper Output" ; ph:dis "Bravo VAV 2-3 Damper Output" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b26a-fe83-5403-f23c91a70cca . _:0aa7c726-b26a-fe83-5403-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0293 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-3 Discharge Air Flow" ; ph:dis "Bravo VAV 2-3 Discharge Air Flow" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b26a-fe84-5404-f23c91a70cca . _:0aa7c726-b26a-fe84-5404-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0294 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-3 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-3 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b26a-fe85-5405-f23c91a70cca . _:0aa7c726-b26a-fe85-5405-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0295 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-3 Heating Valve Output" ; ph:dis "Bravo VAV 2-3 Heating Valve Output" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b26a-fe86-5406-f23c91a70cca . _:0aa7c726-b26a-fe86-5406-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0296 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-3 Supply Air Temperature" ; ph:dis "Bravo VAV 2-3 Supply Air Temperature" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b26a-fe87-5407-f23c91a70cca . _:0aa7c726-b26a-fe87-5407-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0297 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-3 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-3 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b26a-fe88-5408-f23c91a70cca . _:0aa7c726-b26a-fe88-5408-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0298 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-3 Zone Temperature" ; ph:dis "Bravo VAV 2-3 Zone Temperature" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b26a-fe89-5409-f23c91a70cca . _:0aa7c726-b26a-fe89-5409-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0299 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-30" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-30" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b26a-fe8a-540a-f23c91a70cca . _:0aa7c726-b26a-fe8a-540a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-029a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-30 Damper Output" ; ph:dis "Bravo VAV 2-30 Damper Output" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b26a-fe8b-540b-f23c91a70cca . _:0aa7c726-b26a-fe8b-540b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-029b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-30 Discharge Air Flow" ; ph:dis "Bravo VAV 2-30 Discharge Air Flow" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b26a-fe8c-540c-f23c91a70cca . _:0aa7c726-b26a-fe8c-540c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-029c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-30 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-30 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2a8-0780-540d-f23c91a70cca . _:0aa7c726-b2a8-0780-540d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-029d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-30 Heating Valve Output" ; ph:dis "Bravo VAV 2-30 Heating Valve Output" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2a8-0781-540e-f23c91a70cca . _:0aa7c726-b2a8-0781-540e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-029e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-30 Supply Air Temperature" ; ph:dis "Bravo VAV 2-30 Supply Air Temperature" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2a8-0782-540f-f23c91a70cca . _:0aa7c726-b2a8-0782-540f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-029f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-30 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-30 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2a8-0783-5410-f23c91a70cca . _:0aa7c726-b2a8-0783-5410-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02a0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-30 Zone Temperature" ; ph:dis "Bravo VAV 2-30 Zone Temperature" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2a8-0784-5411-f23c91a70cca . _:0aa7c726-b2a8-0784-5411-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02a1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-31" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-31" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b2a8-0785-5412-f23c91a70cca . _:0aa7c726-b2a8-0785-5412-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 18.6 ; _:designHotWaterFlow 2 ; _:designAirFlow 650 . _:b-02a2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-31 Damper Output" ; ph:dis "Bravo VAV 2-31 Damper Output" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2a8-0786-5413-f23c91a70cca . _:0aa7c726-b2a8-0786-5413-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02a3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-31 Discharge Air Flow" ; ph:dis "Bravo VAV 2-31 Discharge Air Flow" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2a8-0787-5414-f23c91a70cca . _:0aa7c726-b2a8-0787-5414-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02a4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-31 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-31 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2a8-0788-5415-f23c91a70cca . _:0aa7c726-b2a8-0788-5415-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02a5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-31 Heating Valve Output" ; ph:dis "Bravo VAV 2-31 Heating Valve Output" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2a8-0789-5416-f23c91a70cca . _:0aa7c726-b2a8-0789-5416-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02a6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-31 Supply Air Temperature" ; ph:dis "Bravo VAV 2-31 Supply Air Temperature" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2a8-078a-5417-f23c91a70cca . _:0aa7c726-b2a8-078a-5417-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-02a7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-31 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-31 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2a8-078b-5418-f23c91a70cca . _:0aa7c726-b2a8-078b-5418-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-02a8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-31 Zone Temperature" ; ph:dis "Bravo VAV 2-31 Zone Temperature" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2a8-078c-5419-f23c91a70cca . _:0aa7c726-b2a8-078c-5419-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02a9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-32" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-32" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b2a8-078d-541a-f23c91a70cca . _:0aa7c726-b2a8-078d-541a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 28.6 ; _:designHotWaterFlow 3.5 ; _:designAirFlow 2150 . _:b-02aa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-32 Damper Output" ; ph:dis "Bravo VAV 2-32 Damper Output" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2a8-078e-541b-f23c91a70cca . _:0aa7c726-b2a8-078e-541b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02ab a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-32 Discharge Air Flow" ; ph:dis "Bravo VAV 2-32 Discharge Air Flow" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2a8-078f-541c-f23c91a70cca . _:0aa7c726-b2a8-078f-541c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02ac a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-32 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-32 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2b7-49c0-541d-f23c91a70cca . _:0aa7c726-b2b7-49c0-541d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02ad a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-32 Heating Valve Output" ; ph:dis "Bravo VAV 2-32 Heating Valve Output" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2b7-49c1-541e-f23c91a70cca . _:0aa7c726-b2b7-49c1-541e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-02ae a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-32 Supply Air Temperature" ; ph:dis "Bravo VAV 2-32 Supply Air Temperature" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2b7-49c2-541f-f23c91a70cca . _:0aa7c726-b2b7-49c2-541f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02af a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-32 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-32 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2b7-49c3-5420-f23c91a70cca . _:0aa7c726-b2b7-49c3-5420-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02b0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-32 Zone Temperature" ; ph:dis "Bravo VAV 2-32 Zone Temperature" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2b7-49c4-5421-f23c91a70cca . _:0aa7c726-b2b7-49c4-5421-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02b1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-33" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-33" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b2b7-49c5-5422-f23c91a70cca . _:0aa7c726-b2b7-49c5-5422-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 3.1 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 200 . _:b-02b2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-33 Damper Output" ; ph:dis "Bravo VAV 2-33 Damper Output" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2b7-49c6-5423-f23c91a70cca . _:0aa7c726-b2b7-49c6-5423-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02b3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-33 Discharge Air Flow" ; ph:dis "Bravo VAV 2-33 Discharge Air Flow" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2b7-49c7-5424-f23c91a70cca . _:0aa7c726-b2b7-49c7-5424-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02b4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-33 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-33 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2b7-49c8-5425-f23c91a70cca . _:0aa7c726-b2b7-49c8-5425-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02b5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-33 Heating Valve Output" ; ph:dis "Bravo VAV 2-33 Heating Valve Output" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2b7-49c9-5426-f23c91a70cca . _:0aa7c726-b2b7-49c9-5426-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02b6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-33 Supply Air Temperature" ; ph:dis "Bravo VAV 2-33 Supply Air Temperature" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2b7-49ca-5427-f23c91a70cca . _:0aa7c726-b2b7-49ca-5427-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02b7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-33 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-33 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2b7-49cb-5428-f23c91a70cca . _:0aa7c726-b2b7-49cb-5428-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02b8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-33 Zone Temperature" ; ph:dis "Bravo VAV 2-33 Zone Temperature" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2b7-49cc-5429-f23c91a70cca . _:0aa7c726-b2b7-49cc-5429-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02b9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-34" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-34" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b2b7-49cd-542a-f23c91a70cca . _:0aa7c726-b2b7-49cd-542a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 10.3 ; _:designHotWaterFlow 1 ; _:designAirFlow 575 . _:b-02ba a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-34 Damper Output" ; ph:dis "Bravo VAV 2-34 Damper Output" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2b7-49ce-542b-f23c91a70cca . _:0aa7c726-b2b7-49ce-542b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02bb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-34 Discharge Air Flow" ; ph:dis "Bravo VAV 2-34 Discharge Air Flow" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2b7-49cf-542c-f23c91a70cca . _:0aa7c726-b2b7-49cf-542c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-02bc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-34 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-34 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2b7-49d0-542d-f23c91a70cca . _:0aa7c726-b2b7-49d0-542d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-02bd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-34 Heating Valve Output" ; ph:dis "Bravo VAV 2-34 Heating Valve Output" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2b7-49d1-542e-f23c91a70cca . _:0aa7c726-b2b7-49d1-542e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02be a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-34 Supply Air Temperature" ; ph:dis "Bravo VAV 2-34 Supply Air Temperature" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2b7-49d2-542f-f23c91a70cca . _:0aa7c726-b2b7-49d2-542f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02bf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-34 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-34 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2c6-8c00-5430-f23c91a70cca . _:0aa7c726-b2c6-8c00-5430-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-02c0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-34 Zone Temperature" ; ph:dis "Bravo VAV 2-34 Zone Temperature" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2c6-8c01-5431-f23c91a70cca . _:0aa7c726-b2c6-8c01-5431-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02c1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-35" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-35" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b2c6-8c02-5432-f23c91a70cca . _:0aa7c726-b2c6-8c02-5432-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 3.1 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 250 . _:b-02c2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-35 Damper Output" ; ph:dis "Bravo VAV 2-35 Damper Output" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2c6-8c03-5433-f23c91a70cca . _:0aa7c726-b2c6-8c03-5433-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02c3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-35 Discharge Air Flow" ; ph:dis "Bravo VAV 2-35 Discharge Air Flow" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2c6-8c04-5434-f23c91a70cca . _:0aa7c726-b2c6-8c04-5434-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-02c4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-35 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-35 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2c6-8c05-5435-f23c91a70cca . _:0aa7c726-b2c6-8c05-5435-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02c5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-35 Heating Valve Output" ; ph:dis "Bravo VAV 2-35 Heating Valve Output" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2c6-8c06-5436-f23c91a70cca . _:0aa7c726-b2c6-8c06-5436-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02c6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-35 Supply Air Temperature" ; ph:dis "Bravo VAV 2-35 Supply Air Temperature" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2c6-8c07-5437-f23c91a70cca . _:0aa7c726-b2c6-8c07-5437-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02c7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-35 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-35 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2c6-8c08-5438-f23c91a70cca . _:0aa7c726-b2c6-8c08-5438-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02c8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-35 Zone Temperature" ; ph:dis "Bravo VAV 2-35 Zone Temperature" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2c6-8c09-5439-f23c91a70cca . _:0aa7c726-b2c6-8c09-5439-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02c9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-36" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-36" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b2c6-8c0a-543a-f23c91a70cca . _:0aa7c726-b2c6-8c0a-543a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-02ca a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-36 Damper Output" ; ph:dis "Bravo VAV 2-36 Damper Output" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2c6-8c0b-543b-f23c91a70cca . _:0aa7c726-b2c6-8c0b-543b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02cb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-36 Discharge Air Flow" ; ph:dis "Bravo VAV 2-36 Discharge Air Flow" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2c6-8c0c-543c-f23c91a70cca . _:0aa7c726-b2c6-8c0c-543c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-02cc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-36 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-36 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2c6-8c0d-543d-f23c91a70cca . _:0aa7c726-b2c6-8c0d-543d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02cd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-36 Heating Valve Output" ; ph:dis "Bravo VAV 2-36 Heating Valve Output" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2c6-8c0e-543e-f23c91a70cca . _:0aa7c726-b2c6-8c0e-543e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-02ce a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-36 Supply Air Temperature" ; ph:dis "Bravo VAV 2-36 Supply Air Temperature" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2c6-8c0f-543f-f23c91a70cca . _:0aa7c726-b2c6-8c0f-543f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02cf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-36 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-36 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2c6-8c10-5440-f23c91a70cca . _:0aa7c726-b2c6-8c10-5440-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02d0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-36 Zone Temperature" ; ph:dis "Bravo VAV 2-36 Zone Temperature" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2c6-8c11-5441-f23c91a70cca . _:0aa7c726-b2c6-8c11-5441-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02d1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-37" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-37" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b2c6-8c12-5442-f23c91a70cca . _:0aa7c726-b2c6-8c12-5442-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 10.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 500 . _:b-02d2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-37 Damper Output" ; ph:dis "Bravo VAV 2-37 Damper Output" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2c6-8c13-5443-f23c91a70cca . _:0aa7c726-b2c6-8c13-5443-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02d3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-37 Discharge Air Flow" ; ph:dis "Bravo VAV 2-37 Discharge Air Flow" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2d5-ce40-5444-f23c91a70cca . _:0aa7c726-b2d5-ce40-5444-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02d4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-37 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-37 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b2d5-ce41-5445-f23c91a70cca . _:0aa7c726-b2d5-ce41-5445-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02d5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-37 Heating Valve Output" ; ph:dis "Bravo VAV 2-37 Heating Valve Output" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b2d5-ce42-5446-f23c91a70cca . _:0aa7c726-b2d5-ce42-5446-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02d6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-37 Supply Air Temperature" ; ph:dis "Bravo VAV 2-37 Supply Air Temperature" ; phIoT:equipRef _:b-02d1 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2d5-ce43-5447-f23c91a70cca . _:0aa7c726-b2d5-ce43-5447-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02d7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-37 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-37 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2d5-ce44-5448-f23c91a70cca . _:0aa7c726-b2d5-ce44-5448-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02d8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-37 Zone Temperature" ; ph:dis "Bravo VAV 2-37 Zone Temperature" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b2d5-ce45-5449-f23c91a70cca . _:0aa7c726-b2d5-ce45-5449-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02d9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-38" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-38" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b2d5-ce46-544a-f23c91a70cca . _:0aa7c726-b2d5-ce46-544a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 4.9 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 250 . _:b-02da a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-38 Damper Output" ; ph:dis "Bravo VAV 2-38 Damper Output" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b303-9500-544b-f23c91a70cca . _:0aa7c726-b303-9500-544b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02db a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-38 Discharge Air Flow" ; ph:dis "Bravo VAV 2-38 Discharge Air Flow" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b303-9501-544c-f23c91a70cca . _:0aa7c726-b303-9501-544c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-02dc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-38 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-38 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b303-9502-544d-f23c91a70cca . _:0aa7c726-b303-9502-544d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02dd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-38 Heating Valve Output" ; ph:dis "Bravo VAV 2-38 Heating Valve Output" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b303-9503-544e-f23c91a70cca . _:0aa7c726-b303-9503-544e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02de a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-38 Supply Air Temperature" ; ph:dis "Bravo VAV 2-38 Supply Air Temperature" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b303-9504-544f-f23c91a70cca . _:0aa7c726-b303-9504-544f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02df a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-38 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-38 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b312-d740-5450-f23c91a70cca . _:0aa7c726-b312-d740-5450-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02e0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-38 Zone Temperature" ; ph:dis "Bravo VAV 2-38 Zone Temperature" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b312-d741-5451-f23c91a70cca . _:0aa7c726-b312-d741-5451-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02e1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-39" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-39" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b312-d742-5452-f23c91a70cca . _:0aa7c726-b312-d742-5452-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 9.5 ; _:designAirFlow 475 . _:b-02e2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-39 Damper Output" ; ph:dis "Bravo VAV 2-39 Damper Output" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b312-d743-5453-f23c91a70cca . _:0aa7c726-b312-d743-5453-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02e3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-39 Discharge Air Flow" ; ph:dis "Bravo VAV 2-39 Discharge Air Flow" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b312-d744-5454-f23c91a70cca . _:0aa7c726-b312-d744-5454-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-02e4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-39 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-39 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b312-d745-5455-f23c91a70cca . _:0aa7c726-b312-d745-5455-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-02e5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-39 Heating Valve Output" ; ph:dis "Bravo VAV 2-39 Heating Valve Output" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b312-d746-5456-f23c91a70cca . _:0aa7c726-b312-d746-5456-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02e6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-39 Supply Air Temperature" ; ph:dis "Bravo VAV 2-39 Supply Air Temperature" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b312-d747-5457-f23c91a70cca . _:0aa7c726-b312-d747-5457-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02e7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-39 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-39 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b312-d748-5458-f23c91a70cca . _:0aa7c726-b312-d748-5458-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02e8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-39 Zone Temperature" ; ph:dis "Bravo VAV 2-39 Zone Temperature" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b312-d749-5459-f23c91a70cca . _:0aa7c726-b312-d749-5459-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02e9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-4" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-4" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b312-d74a-545a-f23c91a70cca . _:0aa7c726-b312-d74a-545a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 2.9 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 150 . _:b-02ea a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-4 Damper Output" ; ph:dis "Bravo VAV 2-4 Damper Output" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b312-d74b-545b-f23c91a70cca . _:0aa7c726-b312-d74b-545b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02eb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-4 Discharge Air Flow" ; ph:dis "Bravo VAV 2-4 Discharge Air Flow" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b312-d74c-545c-f23c91a70cca . _:0aa7c726-b312-d74c-545c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02ec a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-4 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-4 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b312-d74d-545d-f23c91a70cca . _:0aa7c726-b312-d74d-545d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-02ed a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-4 Heating Valve Output" ; ph:dis "Bravo VAV 2-4 Heating Valve Output" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b312-d74e-545e-f23c91a70cca . _:0aa7c726-b312-d74e-545e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02ee a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-4 Supply Air Temperature" ; ph:dis "Bravo VAV 2-4 Supply Air Temperature" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b312-d74f-545f-f23c91a70cca . _:0aa7c726-b312-d74f-545f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02ef a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-4 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-4 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b312-d750-5460-f23c91a70cca . _:0aa7c726-b312-d750-5460-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02f0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-4 Zone Temperature" ; ph:dis "Bravo VAV 2-4 Zone Temperature" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b312-d751-5461-f23c91a70cca . _:0aa7c726-b312-d751-5461-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02f1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-40" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-40" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b312-d752-5462-f23c91a70cca . _:0aa7c726-b312-d752-5462-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-02f2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-40 Damper Output" ; ph:dis "Bravo VAV 2-40 Damper Output" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b312-d753-5463-f23c91a70cca . _:0aa7c726-b312-d753-5463-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02f3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-40 Discharge Air Flow" ; ph:dis "Bravo VAV 2-40 Discharge Air Flow" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b322-1980-5464-f23c91a70cca . _:0aa7c726-b322-1980-5464-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02f4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-40 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-40 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b322-1981-5465-f23c91a70cca . _:0aa7c726-b322-1981-5465-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02f5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-40 Heating Valve Output" ; ph:dis "Bravo VAV 2-40 Heating Valve Output" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b322-1982-5466-f23c91a70cca . _:0aa7c726-b322-1982-5466-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-02f6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-40 Supply Air Temperature" ; ph:dis "Bravo VAV 2-40 Supply Air Temperature" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b322-1983-5467-f23c91a70cca . _:0aa7c726-b322-1983-5467-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02f7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-40 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-40 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b322-1984-5468-f23c91a70cca . _:0aa7c726-b322-1984-5468-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02f8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-40 Zone Temperature" ; ph:dis "Bravo VAV 2-40 Zone Temperature" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b322-1985-5469-f23c91a70cca . _:0aa7c726-b322-1985-5469-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02f9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-41" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-41" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b322-1986-546a-f23c91a70cca . _:0aa7c726-b322-1986-546a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-02fa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-41 Damper Output" ; ph:dis "Bravo VAV 2-41 Damper Output" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b322-1987-546b-f23c91a70cca . _:0aa7c726-b322-1987-546b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.626-04:00"^^xsd:dateTime . _:b-02fb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-41 Discharge Air Flow" ; ph:dis "Bravo VAV 2-41 Discharge Air Flow" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b322-1988-546c-f23c91a70cca . _:0aa7c726-b322-1988-546c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02fc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-41 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-41 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b322-1989-546d-f23c91a70cca . _:0aa7c726-b322-1989-546d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02fd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-41 Heating Valve Output" ; ph:dis "Bravo VAV 2-41 Heating Valve Output" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b322-198a-546e-f23c91a70cca . _:0aa7c726-b322-198a-546e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02fe a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-41 Supply Air Temperature" ; ph:dis "Bravo VAV 2-41 Supply Air Temperature" ; phIoT:equipRef _:b-02f9 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b322-198b-546f-f23c91a70cca . _:0aa7c726-b322-198b-546f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02ff a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-41 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-41 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b322-198c-5470-f23c91a70cca . _:0aa7c726-b322-198c-5470-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0300 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-41 Zone Temperature" ; ph:dis "Bravo VAV 2-41 Zone Temperature" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b322-198d-5471-f23c91a70cca . _:0aa7c726-b322-198d-5471-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0301 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-42" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-42" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b322-198e-5472-f23c91a70cca . _:0aa7c726-b322-198e-5472-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0302 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-42 Damper Output" ; ph:dis "Bravo VAV 2-42 Damper Output" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b322-198f-5473-f23c91a70cca . _:0aa7c726-b322-198f-5473-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0303 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-42 Discharge Air Flow" ; ph:dis "Bravo VAV 2-42 Discharge Air Flow" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b322-1990-5474-f23c91a70cca . _:0aa7c726-b322-1990-5474-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0304 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-42 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-42 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b322-1991-5475-f23c91a70cca . _:0aa7c726-b322-1991-5475-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0305 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-42 Heating Valve Output" ; ph:dis "Bravo VAV 2-42 Heating Valve Output" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b331-5bc0-5476-f23c91a70cca . _:0aa7c726-b331-5bc0-5476-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0306 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-42 Supply Air Temperature" ; ph:dis "Bravo VAV 2-42 Supply Air Temperature" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b331-5bc1-5477-f23c91a70cca . _:0aa7c726-b331-5bc1-5477-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0307 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-42 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-42 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b331-5bc2-5478-f23c91a70cca . _:0aa7c726-b331-5bc2-5478-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0308 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-42 Zone Temperature" ; ph:dis "Bravo VAV 2-42 Zone Temperature" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b331-5bc3-5479-f23c91a70cca . _:0aa7c726-b331-5bc3-5479-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0309 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-43" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-43" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b331-5bc4-547a-f23c91a70cca . _:0aa7c726-b331-5bc4-547a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 141 ; _:designHotWaterPower 4.7 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-030a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-43 Damper Output" ; ph:dis "Bravo VAV 2-43 Damper Output" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b331-5bc5-547b-f23c91a70cca . _:0aa7c726-b331-5bc5-547b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-030b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-43 Discharge Air Flow" ; ph:dis "Bravo VAV 2-43 Discharge Air Flow" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b331-5bc6-547c-f23c91a70cca . _:0aa7c726-b331-5bc6-547c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-030c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-43 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-43 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b331-5bc7-547d-f23c91a70cca . _:0aa7c726-b331-5bc7-547d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-030d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-43 Heating Valve Output" ; ph:dis "Bravo VAV 2-43 Heating Valve Output" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b331-5bc8-547e-f23c91a70cca . _:0aa7c726-b331-5bc8-547e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-030e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-43 Supply Air Temperature" ; ph:dis "Bravo VAV 2-43 Supply Air Temperature" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b331-5bc9-547f-f23c91a70cca . _:0aa7c726-b331-5bc9-547f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-030f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-43 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-43 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b331-5bca-5480-f23c91a70cca . _:0aa7c726-b331-5bca-5480-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0310 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-43 Zone Temperature" ; ph:dis "Bravo VAV 2-43 Zone Temperature" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b331-5bcb-5481-f23c91a70cca . _:0aa7c726-b331-5bcb-5481-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0311 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-44" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-44" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b331-5bcc-5482-f23c91a70cca . _:0aa7c726-b331-5bcc-5482-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0312 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-44 Damper Output" ; ph:dis "Bravo VAV 2-44 Damper Output" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b331-5bcd-5483-f23c91a70cca . _:0aa7c726-b331-5bcd-5483-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0313 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-44 Discharge Air Flow" ; ph:dis "Bravo VAV 2-44 Discharge Air Flow" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b331-5bce-5484-f23c91a70cca . _:0aa7c726-b331-5bce-5484-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0314 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-44 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-44 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b331-5bcf-5485-f23c91a70cca . _:0aa7c726-b331-5bcf-5485-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0315 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-44 Heating Valve Output" ; ph:dis "Bravo VAV 2-44 Heating Valve Output" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b331-5bd0-5486-f23c91a70cca . _:0aa7c726-b331-5bd0-5486-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0316 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-44 Supply Air Temperature" ; ph:dis "Bravo VAV 2-44 Supply Air Temperature" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b36e-64c0-5487-f23c91a70cca . _:0aa7c726-b36e-64c0-5487-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0317 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-44 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-44 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b36e-64c1-5488-f23c91a70cca . _:0aa7c726-b36e-64c1-5488-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0318 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-44 Zone Temperature" ; ph:dis "Bravo VAV 2-44 Zone Temperature" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b36e-64c2-5489-f23c91a70cca . _:0aa7c726-b36e-64c2-5489-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0319 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-45" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-45" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b36e-64c3-548a-f23c91a70cca . _:0aa7c726-b36e-64c3-548a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 17.8 ; _:designHotWaterFlow 1.75 ; _:designAirFlow 600 . _:b-031a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-45 Damper Output" ; ph:dis "Bravo VAV 2-45 Damper Output" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b36e-64c4-548b-f23c91a70cca . _:0aa7c726-b36e-64c4-548b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-031b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-45 Discharge Air Flow" ; ph:dis "Bravo VAV 2-45 Discharge Air Flow" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b36e-64c5-548c-f23c91a70cca . _:0aa7c726-b36e-64c5-548c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-031c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-45 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-45 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b36e-64c6-548d-f23c91a70cca . _:0aa7c726-b36e-64c6-548d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-031d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-45 Heating Valve Output" ; ph:dis "Bravo VAV 2-45 Heating Valve Output" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b36e-64c7-548e-f23c91a70cca . _:0aa7c726-b36e-64c7-548e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-031e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-45 Supply Air Temperature" ; ph:dis "Bravo VAV 2-45 Supply Air Temperature" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b36e-64c8-548f-f23c91a70cca . _:0aa7c726-b36e-64c8-548f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-031f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-45 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-45 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b36e-64c9-5490-f23c91a70cca . _:0aa7c726-b36e-64c9-5490-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0320 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-45 Zone Temperature" ; ph:dis "Bravo VAV 2-45 Zone Temperature" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b36e-64ca-5491-f23c91a70cca . _:0aa7c726-b36e-64ca-5491-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0321 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-46" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-46" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b36e-64cb-5492-f23c91a70cca . _:0aa7c726-b36e-64cb-5492-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-0322 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-46 Damper Output" ; ph:dis "Bravo VAV 2-46 Damper Output" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b37d-a700-5493-f23c91a70cca . _:0aa7c726-b37d-a700-5493-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0323 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-46 Discharge Air Flow" ; ph:dis "Bravo VAV 2-46 Discharge Air Flow" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b37d-a701-5494-f23c91a70cca . _:0aa7c726-b37d-a701-5494-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0324 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-46 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-46 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b37d-a702-5495-f23c91a70cca . _:0aa7c726-b37d-a702-5495-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0325 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-46 Heating Valve Output" ; ph:dis "Bravo VAV 2-46 Heating Valve Output" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b37d-a703-5496-f23c91a70cca . _:0aa7c726-b37d-a703-5496-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0326 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-46 Supply Air Temperature" ; ph:dis "Bravo VAV 2-46 Supply Air Temperature" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b37d-a704-5497-f23c91a70cca . _:0aa7c726-b37d-a704-5497-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0327 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-46 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-46 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b37d-a705-5498-f23c91a70cca . _:0aa7c726-b37d-a705-5498-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0328 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-46 Zone Temperature" ; ph:dis "Bravo VAV 2-46 Zone Temperature" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b37d-a706-5499-f23c91a70cca . _:0aa7c726-b37d-a706-5499-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0329 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-47" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-47" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b37d-a707-549a-f23c91a70cca . _:0aa7c726-b37d-a707-549a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 25.9 ; _:designHotWaterFlow 2.5 ; _:designAirFlow 1400 . _:b-032a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-47 Damper Output" ; ph:dis "Bravo VAV 2-47 Damper Output" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b37d-a708-549b-f23c91a70cca . _:0aa7c726-b37d-a708-549b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-032b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-47 Discharge Air Flow" ; ph:dis "Bravo VAV 2-47 Discharge Air Flow" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b37d-a709-549c-f23c91a70cca . _:0aa7c726-b37d-a709-549c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-032c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-47 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-47 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b37d-a70a-549d-f23c91a70cca . _:0aa7c726-b37d-a70a-549d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-032d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-47 Heating Valve Output" ; ph:dis "Bravo VAV 2-47 Heating Valve Output" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b37d-a70b-549e-f23c91a70cca . _:0aa7c726-b37d-a70b-549e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-032e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-47 Supply Air Temperature" ; ph:dis "Bravo VAV 2-47 Supply Air Temperature" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b37d-a70c-549f-f23c91a70cca . _:0aa7c726-b37d-a70c-549f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-032f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-47 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-47 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b37d-a70d-54a0-f23c91a70cca . _:0aa7c726-b37d-a70d-54a0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0330 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-47 Zone Temperature" ; ph:dis "Bravo VAV 2-47 Zone Temperature" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b37d-a70e-54a1-f23c91a70cca . _:0aa7c726-b37d-a70e-54a1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0331 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-48" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-48" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b37d-a70f-54a2-f23c91a70cca . _:0aa7c726-b37d-a70f-54a2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-0332 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-48 Damper Output" ; ph:dis "Bravo VAV 2-48 Damper Output" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b37d-a710-54a3-f23c91a70cca . _:0aa7c726-b37d-a710-54a3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0333 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-48 Discharge Air Flow" ; ph:dis "Bravo VAV 2-48 Discharge Air Flow" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b37d-a711-54a4-f23c91a70cca . _:0aa7c726-b37d-a711-54a4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0334 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-48 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-48 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b37d-a712-54a5-f23c91a70cca . _:0aa7c726-b37d-a712-54a5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0335 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-48 Heating Valve Output" ; ph:dis "Bravo VAV 2-48 Heating Valve Output" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b38c-e940-54a6-f23c91a70cca . _:0aa7c726-b38c-e940-54a6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0336 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-48 Supply Air Temperature" ; ph:dis "Bravo VAV 2-48 Supply Air Temperature" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b38c-e941-54a7-f23c91a70cca . _:0aa7c726-b38c-e941-54a7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0337 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-48 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-48 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b38c-e942-54a8-f23c91a70cca . _:0aa7c726-b38c-e942-54a8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0338 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-48 Zone Temperature" ; ph:dis "Bravo VAV 2-48 Zone Temperature" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b38c-e943-54a9-f23c91a70cca . _:0aa7c726-b38c-e943-54a9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0339 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-49" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-49" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b38c-e944-54aa-f23c91a70cca . _:0aa7c726-b38c-e944-54aa-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-033a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-49 Damper Output" ; ph:dis "Bravo VAV 2-49 Damper Output" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b38c-e945-54ab-f23c91a70cca . _:0aa7c726-b38c-e945-54ab-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-033b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-49 Discharge Air Flow" ; ph:dis "Bravo VAV 2-49 Discharge Air Flow" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b38c-e946-54ac-f23c91a70cca . _:0aa7c726-b38c-e946-54ac-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-033c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-49 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-49 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b38c-e947-54ad-f23c91a70cca . _:0aa7c726-b38c-e947-54ad-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-033d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-49 Heating Valve Output" ; ph:dis "Bravo VAV 2-49 Heating Valve Output" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b38c-e948-54ae-f23c91a70cca . _:0aa7c726-b38c-e948-54ae-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-033e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-49 Supply Air Temperature" ; ph:dis "Bravo VAV 2-49 Supply Air Temperature" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b38c-e949-54af-f23c91a70cca . _:0aa7c726-b38c-e949-54af-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-033f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-49 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-49 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b38c-e94a-54b0-f23c91a70cca . _:0aa7c726-b38c-e94a-54b0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0340 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-49 Zone Temperature" ; ph:dis "Bravo VAV 2-49 Zone Temperature" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b38c-e94b-54b1-f23c91a70cca . _:0aa7c726-b38c-e94b-54b1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0341 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-5" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-5" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b38c-e94c-54b2-f23c91a70cca . _:0aa7c726-b38c-e94c-54b2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 3.1 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 200 . _:b-0342 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-5 Damper Output" ; ph:dis "Bravo VAV 2-5 Damper Output" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b38c-e94d-54b3-f23c91a70cca . _:0aa7c726-b38c-e94d-54b3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0343 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-5 Discharge Air Flow" ; ph:dis "Bravo VAV 2-5 Discharge Air Flow" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b38c-e94e-54b4-f23c91a70cca . _:0aa7c726-b38c-e94e-54b4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0344 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-5 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-5 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b38c-e94f-54b5-f23c91a70cca . _:0aa7c726-b38c-e94f-54b5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0345 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-5 Heating Valve Output" ; ph:dis "Bravo VAV 2-5 Heating Valve Output" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b38c-e950-54b6-f23c91a70cca . _:0aa7c726-b38c-e950-54b6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0346 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-5 Supply Air Temperature" ; ph:dis "Bravo VAV 2-5 Supply Air Temperature" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b38c-e951-54b7-f23c91a70cca . _:0aa7c726-b38c-e951-54b7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0347 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-5 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-5 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b38c-e952-54b8-f23c91a70cca . _:0aa7c726-b38c-e952-54b8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0348 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-5 Zone Temperature" ; ph:dis "Bravo VAV 2-5 Zone Temperature" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b39c-2b80-54b9-f23c91a70cca . _:0aa7c726-b39c-2b80-54b9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0349 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-50" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-50" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b39c-2b81-54ba-f23c91a70cca . _:0aa7c726-b39c-2b81-54ba-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-034a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-50 Damper Output" ; ph:dis "Bravo VAV 2-50 Damper Output" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b39c-2b82-54bb-f23c91a70cca . _:0aa7c726-b39c-2b82-54bb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-034b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-50 Discharge Air Flow" ; ph:dis "Bravo VAV 2-50 Discharge Air Flow" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b39c-2b83-54bc-f23c91a70cca . _:0aa7c726-b39c-2b83-54bc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-034c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-50 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-50 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b39c-2b84-54bd-f23c91a70cca . _:0aa7c726-b39c-2b84-54bd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-034d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-50 Heating Valve Output" ; ph:dis "Bravo VAV 2-50 Heating Valve Output" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b39c-2b85-54be-f23c91a70cca . _:0aa7c726-b39c-2b85-54be-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-034e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-50 Supply Air Temperature" ; ph:dis "Bravo VAV 2-50 Supply Air Temperature" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b39c-2b86-54bf-f23c91a70cca . _:0aa7c726-b39c-2b86-54bf-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-034f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-50 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-50 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b39c-2b87-54c0-f23c91a70cca . _:0aa7c726-b39c-2b87-54c0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0350 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-50 Zone Temperature" ; ph:dis "Bravo VAV 2-50 Zone Temperature" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b39c-2b88-54c1-f23c91a70cca . _:0aa7c726-b39c-2b88-54c1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0351 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-6" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-6" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b39c-2b89-54c2-f23c91a70cca . _:0aa7c726-b39c-2b89-54c2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 4.7 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 350 . _:b-0352 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-6 Damper Output" ; ph:dis "Bravo VAV 2-6 Damper Output" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b39c-2b8a-54c3-f23c91a70cca . _:0aa7c726-b39c-2b8a-54c3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0353 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-6 Discharge Air Flow" ; ph:dis "Bravo VAV 2-6 Discharge Air Flow" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b39c-2b8b-54c4-f23c91a70cca . _:0aa7c726-b39c-2b8b-54c4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0354 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-6 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-6 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b3d9-3480-54c5-f23c91a70cca . _:0aa7c726-b3d9-3480-54c5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0355 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-6 Heating Valve Output" ; ph:dis "Bravo VAV 2-6 Heating Valve Output" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b3d9-3481-54c6-f23c91a70cca . _:0aa7c726-b3d9-3481-54c6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0356 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-6 Supply Air Temperature" ; ph:dis "Bravo VAV 2-6 Supply Air Temperature" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3d9-3482-54c7-f23c91a70cca . _:0aa7c726-b3d9-3482-54c7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0357 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-6 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-6 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3d9-3483-54c8-f23c91a70cca . _:0aa7c726-b3d9-3483-54c8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0358 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-6 Zone Temperature" ; ph:dis "Bravo VAV 2-6 Zone Temperature" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3d9-3484-54c9-f23c91a70cca . _:0aa7c726-b3d9-3484-54c9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0359 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-7" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-7" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b3d9-3485-54ca-f23c91a70cca . _:0aa7c726-b3d9-3485-54ca-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 650 . _:b-035a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-7 Damper Output" ; ph:dis "Bravo VAV 2-7 Damper Output" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b3d9-3486-54cb-f23c91a70cca . _:0aa7c726-b3d9-3486-54cb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-035b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-7 Discharge Air Flow" ; ph:dis "Bravo VAV 2-7 Discharge Air Flow" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b3d9-3487-54cc-f23c91a70cca . _:0aa7c726-b3d9-3487-54cc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-035c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-7 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-7 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b3d9-3488-54cd-f23c91a70cca . _:0aa7c726-b3d9-3488-54cd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-035d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-7 Heating Valve Output" ; ph:dis "Bravo VAV 2-7 Heating Valve Output" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b3d9-3489-54ce-f23c91a70cca . _:0aa7c726-b3d9-3489-54ce-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-035e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-7 Supply Air Temperature" ; ph:dis "Bravo VAV 2-7 Supply Air Temperature" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3d9-348a-54cf-f23c91a70cca . _:0aa7c726-b3d9-348a-54cf-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-035f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-7 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-7 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3d9-348b-54d0-f23c91a70cca . _:0aa7c726-b3d9-348b-54d0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0360 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-7 Zone Temperature" ; ph:dis "Bravo VAV 2-7 Zone Temperature" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3d9-348c-54d1-f23c91a70cca . _:0aa7c726-b3d9-348c-54d1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0361 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-8" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-8" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b3d9-348d-54d2-f23c91a70cca . _:0aa7c726-b3d9-348d-54d2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 4.1 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0362 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-8 Damper Output" ; ph:dis "Bravo VAV 2-8 Damper Output" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b3d9-348e-54d3-f23c91a70cca . _:0aa7c726-b3d9-348e-54d3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0363 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-8 Discharge Air Flow" ; ph:dis "Bravo VAV 2-8 Discharge Air Flow" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b3d9-348f-54d4-f23c91a70cca . _:0aa7c726-b3d9-348f-54d4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0364 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-8 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-8 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b3d9-3490-54d5-f23c91a70cca . _:0aa7c726-b3d9-3490-54d5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0365 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-8 Heating Valve Output" ; ph:dis "Bravo VAV 2-8 Heating Valve Output" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b3e8-76c0-54d6-f23c91a70cca . _:0aa7c726-b3e8-76c0-54d6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0366 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-8 Supply Air Temperature" ; ph:dis "Bravo VAV 2-8 Supply Air Temperature" ; phIoT:equipRef _:b-0361 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3e8-76c1-54d7-f23c91a70cca . _:0aa7c726-b3e8-76c1-54d7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0367 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-8 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-8 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3e8-76c2-54d8-f23c91a70cca . _:0aa7c726-b3e8-76c2-54d8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0368 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-8 Zone Temperature" ; ph:dis "Bravo VAV 2-8 Zone Temperature" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3e8-76c3-54d9-f23c91a70cca . _:0aa7c726-b3e8-76c3-54d9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0369 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-9" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-9" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b3e8-76c4-54da-f23c91a70cca . _:0aa7c726-b3e8-76c4-54da-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-036a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-9 Damper Output" ; ph:dis "Bravo VAV 2-9 Damper Output" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b3e8-76c5-54db-f23c91a70cca . _:0aa7c726-b3e8-76c5-54db-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-036b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-9 Discharge Air Flow" ; ph:dis "Bravo VAV 2-9 Discharge Air Flow" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b3e8-76c6-54dc-f23c91a70cca . _:0aa7c726-b3e8-76c6-54dc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-036c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-9 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-9 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b3e8-76c7-54dd-f23c91a70cca . _:0aa7c726-b3e8-76c7-54dd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-036d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-9 Heating Valve Output" ; ph:dis "Bravo VAV 2-9 Heating Valve Output" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b3e8-76c8-54de-f23c91a70cca . _:0aa7c726-b3e8-76c8-54de-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-036e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-9 Supply Air Temperature" ; ph:dis "Bravo VAV 2-9 Supply Air Temperature" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3e8-76c9-54df-f23c91a70cca . _:0aa7c726-b3e8-76c9-54df-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-036f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-9 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-9 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3e8-76ca-54e0-f23c91a70cca . _:0aa7c726-b3e8-76ca-54e0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0370 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-9 Zone Temperature" ; ph:dis "Bravo VAV 2-9 Zone Temperature" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3e8-76cb-54e1-f23c91a70cca . _:0aa7c726-b3e8-76cb-54e1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0371 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-1" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-1" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b3e8-76cc-54e2-f23c91a70cca . _:0aa7c726-b3e8-76cc-54e2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 14.1 ; _:designHotWaterFlow 2.5 ; _:designAirFlow 1300 . _:b-0372 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-1 Air Damper Command" ; ph:dis "Bravo VAV 3-1 Air Damper Command" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b3e8-76cd-54e3-f23c91a70cca . _:0aa7c726-b3e8-76cd-54e3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0373 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-1 Discharge Air Flow" ; ph:dis "Bravo VAV 3-1 Discharge Air Flow" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b3e8-76ce-54e4-f23c91a70cca . _:0aa7c726-b3e8-76ce-54e4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0374 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-1 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-1 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b3e8-76cf-54e5-f23c91a70cca . _:0aa7c726-b3e8-76cf-54e5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0375 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-1 Heating Valve Output" ; ph:dis "Bravo VAV 3-1 Heating Valve Output" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b3e8-76d0-54e6-f23c91a70cca . _:0aa7c726-b3e8-76d0-54e6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0376 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-1 Supply Air Temperature" ; ph:dis "Bravo VAV 3-1 Supply Air Temperature" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3e8-76d1-54e7-f23c91a70cca . _:0aa7c726-b3e8-76d1-54e7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0377 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-1 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-1 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3e8-76d2-54e8-f23c91a70cca . _:0aa7c726-b3e8-76d2-54e8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0378 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-1 Zone Temperature" ; ph:dis "Bravo VAV 3-1 Zone Temperature" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3f7-b900-54e9-f23c91a70cca . _:0aa7c726-b3f7-b900-54e9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0379 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-10" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-10" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b3f7-b901-54ea-f23c91a70cca . _:0aa7c726-b3f7-b901-54ea-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 7.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-037a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-10 Damper Output" ; ph:dis "Bravo VAV 3-10 Damper Output" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b3f7-b902-54eb-f23c91a70cca . _:0aa7c726-b3f7-b902-54eb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-037b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-10 Discharge Air Flow" ; ph:dis "Bravo VAV 3-10 Discharge Air Flow" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b3f7-b903-54ec-f23c91a70cca . _:0aa7c726-b3f7-b903-54ec-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-037c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-10 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-10 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b3f7-b904-54ed-f23c91a70cca . _:0aa7c726-b3f7-b904-54ed-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-037d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-10 Heating Valve Output" ; ph:dis "Bravo VAV 3-10 Heating Valve Output" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b3f7-b905-54ee-f23c91a70cca . _:0aa7c726-b3f7-b905-54ee-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-037e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-10 Supply Air Temperature" ; ph:dis "Bravo VAV 3-10 Supply Air Temperature" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3f7-b906-54ef-f23c91a70cca . _:0aa7c726-b3f7-b906-54ef-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-037f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-10 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-10 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3f7-b907-54f0-f23c91a70cca . _:0aa7c726-b3f7-b907-54f0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0380 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-10 Zone Temperature" ; ph:dis "Bravo VAV 3-10 Zone Temperature" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3f7-b908-54f1-f23c91a70cca . _:0aa7c726-b3f7-b908-54f1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0381 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-11" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-11" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b3f7-b909-54f2-f23c91a70cca . _:0aa7c726-b3f7-b909-54f2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 22.7 ; _:designHotWaterFlow 2.25 ; _:designAirFlow 1100 . _:b-0382 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-11 Damper Output" ; ph:dis "Bravo VAV 3-11 Damper Output" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b3f7-b90a-54f3-f23c91a70cca . _:0aa7c726-b3f7-b90a-54f3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0383 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-11 Discharge Air Flow" ; ph:dis "Bravo VAV 3-11 Discharge Air Flow" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b3f7-b90b-54f4-f23c91a70cca . _:0aa7c726-b3f7-b90b-54f4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0384 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-11 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-11 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b3f7-b90c-54f5-f23c91a70cca . _:0aa7c726-b3f7-b90c-54f5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0385 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-11 Heating Valve Output" ; ph:dis "Bravo VAV 3-11 Heating Valve Output" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b3f7-b90d-54f6-f23c91a70cca . _:0aa7c726-b3f7-b90d-54f6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0386 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-11 Supply Air Temperature" ; ph:dis "Bravo VAV 3-11 Supply Air Temperature" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3f7-b90e-54f7-f23c91a70cca . _:0aa7c726-b3f7-b90e-54f7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0387 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-11 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-11 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3f7-b90f-54f8-f23c91a70cca . _:0aa7c726-b3f7-b90f-54f8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0388 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-11 Zone Temperature" ; ph:dis "Bravo VAV 3-11 Zone Temperature" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b3f7-b910-54f9-f23c91a70cca . _:0aa7c726-b3f7-b910-54f9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0389 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-12" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-12" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b3f7-b911-54fa-f23c91a70cca . _:0aa7c726-b3f7-b911-54fa-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 1000 . _:b-038a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-12 Damper Output" ; ph:dis "Bravo VAV 3-12 Damper Output" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b3f7-b912-54fb-f23c91a70cca . _:0aa7c726-b3f7-b912-54fb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-038b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-12 Discharge Air Flow" ; ph:dis "Bravo VAV 3-12 Discharge Air Flow" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b406-fb40-54fc-f23c91a70cca . _:0aa7c726-b406-fb40-54fc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-038c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-12 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-12 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b406-fb41-54fd-f23c91a70cca . _:0aa7c726-b406-fb41-54fd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-038d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-12 Heating Valve Output" ; ph:dis "Bravo VAV 3-12 Heating Valve Output" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b406-fb42-54fe-f23c91a70cca . _:0aa7c726-b406-fb42-54fe-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-038e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-12 Supply Air Temperature" ; ph:dis "Bravo VAV 3-12 Supply Air Temperature" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b406-fb43-54ff-f23c91a70cca . _:0aa7c726-b406-fb43-54ff-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-038f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-12 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-12 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b406-fb44-5500-f23c91a70cca . _:0aa7c726-b406-fb44-5500-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0390 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-12 Zone Temperature" ; ph:dis "Bravo VAV 3-12 Zone Temperature" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b434-c200-5501-f23c91a70cca . _:0aa7c726-b434-c200-5501-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0391 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-13" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-13" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b434-c201-5502-f23c91a70cca . _:0aa7c726-b434-c201-5502-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 5.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-0392 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-13 Damper Output" ; ph:dis "Bravo VAV 3-13 Damper Output" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b434-c202-5503-f23c91a70cca . _:0aa7c726-b434-c202-5503-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0393 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-13 Discharge Air Flow" ; ph:dis "Bravo VAV 3-13 Discharge Air Flow" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b434-c203-5504-f23c91a70cca . _:0aa7c726-b434-c203-5504-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0394 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-13 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-13 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b434-c204-5505-f23c91a70cca . _:0aa7c726-b434-c204-5505-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0395 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-13 Heating Valve Output" ; ph:dis "Bravo VAV 3-13 Heating Valve Output" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b434-c205-5506-f23c91a70cca . _:0aa7c726-b434-c205-5506-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0396 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-13 Supply Air Temperature" ; ph:dis "Bravo VAV 3-13 Supply Air Temperature" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b444-0440-5507-f23c91a70cca . _:0aa7c726-b444-0440-5507-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0397 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-13 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-13 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b444-0441-5508-f23c91a70cca . _:0aa7c726-b444-0441-5508-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0398 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-13 Zone Temperature" ; ph:dis "Bravo VAV 3-13 Zone Temperature" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b444-0442-5509-f23c91a70cca . _:0aa7c726-b444-0442-5509-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0399 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-14" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-14" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b444-0443-550a-f23c91a70cca . _:0aa7c726-b444-0443-550a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 5.4 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-039a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-14 Damper Output" ; ph:dis "Bravo VAV 3-14 Damper Output" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b444-0444-550b-f23c91a70cca . _:0aa7c726-b444-0444-550b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-039b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-14 Discharge Air Flow" ; ph:dis "Bravo VAV 3-14 Discharge Air Flow" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b444-0445-550c-f23c91a70cca . _:0aa7c726-b444-0445-550c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-039c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-14 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-14 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b444-0446-550d-f23c91a70cca . _:0aa7c726-b444-0446-550d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-039d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-14 Heating Valve Output" ; ph:dis "Bravo VAV 3-14 Heating Valve Output" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b444-0447-550e-f23c91a70cca . _:0aa7c726-b444-0447-550e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-039e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-14 Supply Air Temperature" ; ph:dis "Bravo VAV 3-14 Supply Air Temperature" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b444-0448-550f-f23c91a70cca . _:0aa7c726-b444-0448-550f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-039f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-14 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-14 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b444-0449-5510-f23c91a70cca . _:0aa7c726-b444-0449-5510-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03a0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-14 Zone Temperature" ; ph:dis "Bravo VAV 3-14 Zone Temperature" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b444-044a-5511-f23c91a70cca . _:0aa7c726-b444-044a-5511-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03a1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-15" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-15" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b444-044b-5512-f23c91a70cca . _:0aa7c726-b444-044b-5512-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 147 ; _:designHotWaterPower 2.7 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 250 . _:b-03a2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-15 Damper Output" ; ph:dis "Bravo VAV 3-15 Damper Output" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b444-044c-5513-f23c91a70cca . _:0aa7c726-b444-044c-5513-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03a3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-15 Discharge Air Flow" ; ph:dis "Bravo VAV 3-15 Discharge Air Flow" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b444-044d-5514-f23c91a70cca . _:0aa7c726-b444-044d-5514-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03a4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-15 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-15 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b444-044e-5515-f23c91a70cca . _:0aa7c726-b444-044e-5515-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-03a5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-15 Heating Valve Output" ; ph:dis "Bravo VAV 3-15 Heating Valve Output" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b444-044f-5516-f23c91a70cca . _:0aa7c726-b444-044f-5516-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-03a6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-15 Supply Air Temperature" ; ph:dis "Bravo VAV 3-15 Supply Air Temperature" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b444-0450-5517-f23c91a70cca . _:0aa7c726-b444-0450-5517-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-03a7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-15 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-15 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b444-0451-5518-f23c91a70cca . _:0aa7c726-b444-0451-5518-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-03a8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-15 Zone Temperature" ; ph:dis "Bravo VAV 3-15 Zone Temperature" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b444-0452-5519-f23c91a70cca . _:0aa7c726-b444-0452-5519-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03a9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-16" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-16" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b453-4680-551a-f23c91a70cca . _:0aa7c726-b453-4680-551a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 3.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-03aa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-16 Damper Output" ; ph:dis "Bravo VAV 3-16 Damper Output" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b453-4681-551b-f23c91a70cca . _:0aa7c726-b453-4681-551b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-03ab a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-16 Discharge Air Flow" ; ph:dis "Bravo VAV 3-16 Discharge Air Flow" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b453-4682-551c-f23c91a70cca . _:0aa7c726-b453-4682-551c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03ac a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-16 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-16 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b453-4683-551d-f23c91a70cca . _:0aa7c726-b453-4683-551d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-03ad a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-16 Heating Valve Output" ; ph:dis "Bravo VAV 3-16 Heating Valve Output" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b453-4684-551e-f23c91a70cca . _:0aa7c726-b453-4684-551e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03ae a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-16 Supply Air Temperature" ; ph:dis "Bravo VAV 3-16 Supply Air Temperature" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b453-4685-551f-f23c91a70cca . _:0aa7c726-b453-4685-551f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-03af a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-16 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-16 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b453-4686-5520-f23c91a70cca . _:0aa7c726-b453-4686-5520-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-03b0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-16 Zone Temperature" ; ph:dis "Bravo VAV 3-16 Zone Temperature" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b453-4687-5521-f23c91a70cca . _:0aa7c726-b453-4687-5521-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03b1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-17" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-17" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b453-4688-5522-f23c91a70cca . _:0aa7c726-b453-4688-5522-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 3.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-03b2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-17 Damper Output" ; ph:dis "Bravo VAV 3-17 Damper Output" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b453-4689-5523-f23c91a70cca . _:0aa7c726-b453-4689-5523-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-03b3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-17 Discharge Air Flow" ; ph:dis "Bravo VAV 3-17 Discharge Air Flow" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b453-468a-5524-f23c91a70cca . _:0aa7c726-b453-468a-5524-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-03b4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-17 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-17 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b453-468b-5525-f23c91a70cca . _:0aa7c726-b453-468b-5525-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03b5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-17 Heating Valve Output" ; ph:dis "Bravo VAV 3-17 Heating Valve Output" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b453-468c-5526-f23c91a70cca . _:0aa7c726-b453-468c-5526-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-03b6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-17 Supply Air Temperature" ; ph:dis "Bravo VAV 3-17 Supply Air Temperature" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b453-468d-5527-f23c91a70cca . _:0aa7c726-b453-468d-5527-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-03b7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-17 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-17 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b453-468e-5528-f23c91a70cca . _:0aa7c726-b453-468e-5528-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-03b8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-17 Zone Temperature" ; ph:dis "Bravo VAV 3-17 Zone Temperature" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b453-468f-5529-f23c91a70cca . _:0aa7c726-b453-468f-5529-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03b9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-18" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-18" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b453-4690-552a-f23c91a70cca . _:0aa7c726-b453-4690-552a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 12.4 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 500 . _:b-03ba a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-18 Damper Output" ; ph:dis "Bravo VAV 3-18 Damper Output" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b453-4691-552b-f23c91a70cca . _:0aa7c726-b453-4691-552b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03bb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-18 Discharge Air Flow" ; ph:dis "Bravo VAV 3-18 Discharge Air Flow" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b453-4692-552c-f23c91a70cca . _:0aa7c726-b453-4692-552c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03bc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-18 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-18 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b462-88c0-552d-f23c91a70cca . _:0aa7c726-b462-88c0-552d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-03bd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-18 Heating Valve Output" ; ph:dis "Bravo VAV 3-18 Heating Valve Output" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b462-88c1-552e-f23c91a70cca . _:0aa7c726-b462-88c1-552e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03be a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-18 Supply Air Temperature" ; ph:dis "Bravo VAV 3-18 Supply Air Temperature" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b462-88c2-552f-f23c91a70cca . _:0aa7c726-b462-88c2-552f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03bf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-18 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-18 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b462-88c3-5530-f23c91a70cca . _:0aa7c726-b462-88c3-5530-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03c0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-18 Zone Temperature" ; ph:dis "Bravo VAV 3-18 Zone Temperature" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b49f-91c0-5531-f23c91a70cca . _:0aa7c726-b49f-91c0-5531-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03c1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-19" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-19" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b49f-91c1-5532-f23c91a70cca . _:0aa7c726-b49f-91c1-5532-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 155 ; _:designHotWaterPower 2.1 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 150 . _:b-03c2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-19 Damper Output" ; ph:dis "Bravo VAV 3-19 Damper Output" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b49f-91c2-5533-f23c91a70cca . _:0aa7c726-b49f-91c2-5533-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-03c3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-19 Discharge Air Flow" ; ph:dis "Bravo VAV 3-19 Discharge Air Flow" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b49f-91c3-5534-f23c91a70cca . _:0aa7c726-b49f-91c3-5534-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03c4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-19 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-19 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b49f-91c4-5535-f23c91a70cca . _:0aa7c726-b49f-91c4-5535-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03c5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-19 Heating Valve Output" ; ph:dis "Bravo VAV 3-19 Heating Valve Output" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b49f-91c5-5536-f23c91a70cca . _:0aa7c726-b49f-91c5-5536-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-03c6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-19 Supply Air Temperature" ; ph:dis "Bravo VAV 3-19 Supply Air Temperature" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b49f-91c6-5537-f23c91a70cca . _:0aa7c726-b49f-91c6-5537-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03c7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-19 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-19 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b49f-91c7-5538-f23c91a70cca . _:0aa7c726-b49f-91c7-5538-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03c8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-19 Zone Temperature" ; ph:dis "Bravo VAV 3-19 Zone Temperature" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b49f-91c8-5539-f23c91a70cca . _:0aa7c726-b49f-91c8-5539-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03c9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-2" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-2" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b49f-91c9-553a-f23c91a70cca . _:0aa7c726-b49f-91c9-553a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.7 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 800 . _:b-03ca a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-2 Damper Output" ; ph:dis "Bravo VAV 3-2 Damper Output" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b4ae-d400-553b-f23c91a70cca . _:0aa7c726-b4ae-d400-553b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03cb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-2 Discharge Air Flow" ; ph:dis "Bravo VAV 3-2 Discharge Air Flow" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b4ae-d401-553c-f23c91a70cca . _:0aa7c726-b4ae-d401-553c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03cc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-2 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-2 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b4ae-d402-553d-f23c91a70cca . _:0aa7c726-b4ae-d402-553d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03cd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-2 Heating Valve Output" ; ph:dis "Bravo VAV 3-2 Heating Valve Output" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b4ae-d403-553e-f23c91a70cca . _:0aa7c726-b4ae-d403-553e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03ce a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-2 Supply Air Temperature" ; ph:dis "Bravo VAV 3-2 Supply Air Temperature" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4ae-d404-553f-f23c91a70cca . _:0aa7c726-b4ae-d404-553f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03cf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-2 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-2 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4ae-d405-5540-f23c91a70cca . _:0aa7c726-b4ae-d405-5540-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03d0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-2 Zone Temperature" ; ph:dis "Bravo VAV 3-2 Zone Temperature" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4ae-d406-5541-f23c91a70cca . _:0aa7c726-b4ae-d406-5541-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03d1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-20" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-20" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b4ae-d407-5542-f23c91a70cca . _:0aa7c726-b4ae-d407-5542-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 4.1 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-03d2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-20 Damper Output" ; ph:dis "Bravo VAV 3-20 Damper Output" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b4ae-d408-5543-f23c91a70cca . _:0aa7c726-b4ae-d408-5543-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-03d3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-20 Discharge Air Flow" ; ph:dis "Bravo VAV 3-20 Discharge Air Flow" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b4ae-d409-5544-f23c91a70cca . _:0aa7c726-b4ae-d409-5544-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03d4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-20 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-20 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b4ae-d40a-5545-f23c91a70cca . _:0aa7c726-b4ae-d40a-5545-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03d5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-20 Heating Valve Output" ; ph:dis "Bravo VAV 3-20 Heating Valve Output" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b4ae-d40b-5546-f23c91a70cca . _:0aa7c726-b4ae-d40b-5546-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03d6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-20 Supply Air Temperature" ; ph:dis "Bravo VAV 3-20 Supply Air Temperature" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4ae-d40c-5547-f23c91a70cca . _:0aa7c726-b4ae-d40c-5547-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-03d7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-20 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-20 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4ae-d40d-5548-f23c91a70cca . _:0aa7c726-b4ae-d40d-5548-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-03d8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-20 Zone Temperature" ; ph:dis "Bravo VAV 3-20 Zone Temperature" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4ae-d40e-5549-f23c91a70cca . _:0aa7c726-b4ae-d40e-5549-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03d9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-21" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-21" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b4ae-d40f-554a-f23c91a70cca . _:0aa7c726-b4ae-d40f-554a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6.5 ; _:designHotWaterFlow 1 ; _:designAirFlow 300 . _:b-03da a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-21 Damper Output" ; ph:dis "Bravo VAV 3-21 Damper Output" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b4ae-d410-554b-f23c91a70cca . _:0aa7c726-b4ae-d410-554b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-03db a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-21 Discharge Air Flow" ; ph:dis "Bravo VAV 3-21 Discharge Air Flow" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b4ae-d411-554c-f23c91a70cca . _:0aa7c726-b4ae-d411-554c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-03dc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-21 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-21 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b4ae-d412-554d-f23c91a70cca . _:0aa7c726-b4ae-d412-554d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03dd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-21 Heating Valve Output" ; ph:dis "Bravo VAV 3-21 Heating Valve Output" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b4be-1640-554e-f23c91a70cca . _:0aa7c726-b4be-1640-554e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-03de a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-21 Supply Air Temperature" ; ph:dis "Bravo VAV 3-21 Supply Air Temperature" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4be-1641-554f-f23c91a70cca . _:0aa7c726-b4be-1641-554f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03df a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-21 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-21 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4be-1642-5550-f23c91a70cca . _:0aa7c726-b4be-1642-5550-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03e0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-21 Zone Temperature" ; ph:dis "Bravo VAV 3-21 Zone Temperature" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4be-1643-5551-f23c91a70cca . _:0aa7c726-b4be-1643-5551-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03e1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-22" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-22" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b4be-1644-5552-f23c91a70cca . _:0aa7c726-b4be-1644-5552-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 29.2 ; _:designHotWaterFlow 3.5 ; _:designAirFlow 1250 . _:b-03e2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-22 Damper Output" ; ph:dis "Bravo VAV 3-22 Damper Output" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b4be-1645-5553-f23c91a70cca . _:0aa7c726-b4be-1645-5553-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03e3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-22 Discharge Air Flow" ; ph:dis "Bravo VAV 3-22 Discharge Air Flow" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b4be-1646-5554-f23c91a70cca . _:0aa7c726-b4be-1646-5554-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-03e4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-22 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-22 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b4be-1647-5555-f23c91a70cca . _:0aa7c726-b4be-1647-5555-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03e5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-22 Heating Valve Output" ; ph:dis "Bravo VAV 3-22 Heating Valve Output" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b4be-1648-5556-f23c91a70cca . _:0aa7c726-b4be-1648-5556-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03e6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-22 Supply Air Temperature" ; ph:dis "Bravo VAV 3-22 Supply Air Temperature" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4be-1649-5557-f23c91a70cca . _:0aa7c726-b4be-1649-5557-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-03e7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-22 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-22 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4be-164a-5558-f23c91a70cca . _:0aa7c726-b4be-164a-5558-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03e8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-22 Zone Temperature" ; ph:dis "Bravo VAV 3-22 Zone Temperature" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4be-164b-5559-f23c91a70cca . _:0aa7c726-b4be-164b-5559-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03e9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-23" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-23" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b4be-164c-555a-f23c91a70cca . _:0aa7c726-b4be-164c-555a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 2.2 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 200 . _:b-03ea a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-23 Damper Output" ; ph:dis "Bravo VAV 3-23 Damper Output" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b4be-164d-555b-f23c91a70cca . _:0aa7c726-b4be-164d-555b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime ; _:pointType "" . _:b-03eb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-23 Discharge Air Flow" ; ph:dis "Bravo VAV 3-23 Discharge Air Flow" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b4be-164e-555c-f23c91a70cca . _:0aa7c726-b4be-164e-555c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-03ec a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-23 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-23 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b4be-164f-555d-f23c91a70cca . _:0aa7c726-b4be-164f-555d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03ed a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-23 Heating Valve Output" ; ph:dis "Bravo VAV 3-23 Heating Valve Output" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b4be-1650-555e-f23c91a70cca . _:0aa7c726-b4be-1650-555e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03ee a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-23 Supply Air Temperature" ; ph:dis "Bravo VAV 3-23 Supply Air Temperature" ; phIoT:equipRef _:b-03e9 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4be-1651-555f-f23c91a70cca . _:0aa7c726-b4be-1651-555f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-03ef a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-23 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-23 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4cd-5880-5560-f23c91a70cca . _:0aa7c726-b4cd-5880-5560-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03f0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-23 Zone Temperature" ; ph:dis "Bravo VAV 3-23 Zone Temperature" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4cd-5881-5561-f23c91a70cca . _:0aa7c726-b4cd-5881-5561-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-03f1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-24" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-24" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b4cd-5882-5562-f23c91a70cca . _:0aa7c726-b4cd-5882-5562-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6.4 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-03f2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-24 Damper Output" ; ph:dis "Bravo VAV 3-24 Damper Output" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b4cd-5883-5563-f23c91a70cca . _:0aa7c726-b4cd-5883-5563-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03f3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-24 Discharge Air Flow" ; ph:dis "Bravo VAV 3-24 Discharge Air Flow" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b4cd-5884-5564-f23c91a70cca . _:0aa7c726-b4cd-5884-5564-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03f4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-24 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-24 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b4cd-5885-5565-f23c91a70cca . _:0aa7c726-b4cd-5885-5565-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03f5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-24 Heating Valve Output" ; ph:dis "Bravo VAV 3-24 Heating Valve Output" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b4cd-5886-5566-f23c91a70cca . _:0aa7c726-b4cd-5886-5566-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-03f6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-24 Supply Air Temperature" ; ph:dis "Bravo VAV 3-24 Supply Air Temperature" ; phIoT:equipRef _:b-03f1 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4cd-5887-5567-f23c91a70cca . _:0aa7c726-b4cd-5887-5567-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03f7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-24 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-24 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4cd-5888-5568-f23c91a70cca . _:0aa7c726-b4cd-5888-5568-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03f8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-24 Zone Temperature" ; ph:dis "Bravo VAV 3-24 Zone Temperature" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b4cd-5889-5569-f23c91a70cca . _:0aa7c726-b4cd-5889-5569-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-03f9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-25" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-25" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b4cd-588a-556a-f23c91a70cca . _:0aa7c726-b4cd-588a-556a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 16.6 ; _:designHotWaterFlow 2 ; _:designAirFlow 500 . _:b-03fa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-25 Damper Output" ; ph:dis "Bravo VAV 3-25 Damper Output" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b4cd-588b-556b-f23c91a70cca . _:0aa7c726-b4cd-588b-556b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-03fb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-25 Discharge Air Flow" ; ph:dis "Bravo VAV 3-25 Discharge Air Flow" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b4dc-9ac0-556c-f23c91a70cca . _:0aa7c726-b4dc-9ac0-556c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03fc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-25 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-25 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b538-2840-556d-f23c91a70cca . _:0aa7c726-b538-2840-556d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03fd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-25 Heating Valve Output" ; ph:dis "Bravo VAV 3-25 Heating Valve Output" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b538-2841-556e-f23c91a70cca . _:0aa7c726-b538-2841-556e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03fe a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-25 Supply Air Temperature" ; ph:dis "Bravo VAV 3-25 Supply Air Temperature" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b538-2842-556f-f23c91a70cca . _:0aa7c726-b538-2842-556f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03ff a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-25 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-25 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b538-2843-5570-f23c91a70cca . _:0aa7c726-b538-2843-5570-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0400 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-25 Zone Temperature" ; ph:dis "Bravo VAV 3-25 Zone Temperature" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b538-2844-5571-f23c91a70cca . _:0aa7c726-b538-2844-5571-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0401 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-26" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-26" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b538-2845-5572-f23c91a70cca . _:0aa7c726-b538-2845-5572-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 12.9 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 400 . _:b-0402 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-26 Damper Output" ; ph:dis "Bravo VAV 3-26 Damper Output" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b538-2846-5573-f23c91a70cca . _:0aa7c726-b538-2846-5573-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0403 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-26 Discharge Air Flow" ; ph:dis "Bravo VAV 3-26 Discharge Air Flow" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b538-2847-5574-f23c91a70cca . _:0aa7c726-b538-2847-5574-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0404 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-26 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-26 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b538-2848-5575-f23c91a70cca . _:0aa7c726-b538-2848-5575-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0405 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-26 Heating Valve Output" ; ph:dis "Bravo VAV 3-26 Heating Valve Output" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b538-2849-5576-f23c91a70cca . _:0aa7c726-b538-2849-5576-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0406 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-26 Supply Air Temperature" ; ph:dis "Bravo VAV 3-26 Supply Air Temperature" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b538-284a-5577-f23c91a70cca . _:0aa7c726-b538-284a-5577-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0407 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-26 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-26 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b547-6a80-5578-f23c91a70cca . _:0aa7c726-b547-6a80-5578-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0408 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-26 Zone Temperature" ; ph:dis "Bravo VAV 3-26 Zone Temperature" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b547-6a81-5579-f23c91a70cca . _:0aa7c726-b547-6a81-5579-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0409 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-27" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-27" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b547-6a82-557a-f23c91a70cca . _:0aa7c726-b547-6a82-557a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-040a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-27 Damper Output" ; ph:dis "Bravo VAV 3-27 Damper Output" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b547-6a83-557b-f23c91a70cca . _:0aa7c726-b547-6a83-557b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-040b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-27 Discharge Air Flow" ; ph:dis "Bravo VAV 3-27 Discharge Air Flow" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b547-6a84-557c-f23c91a70cca . _:0aa7c726-b547-6a84-557c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-040c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-27 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-27 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b547-6a85-557d-f23c91a70cca . _:0aa7c726-b547-6a85-557d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-040d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-27 Heating Valve Output" ; ph:dis "Bravo VAV 3-27 Heating Valve Output" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b547-6a86-557e-f23c91a70cca . _:0aa7c726-b547-6a86-557e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-040e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-27 Supply Air Temperature" ; ph:dis "Bravo VAV 3-27 Supply Air Temperature" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b547-6a87-557f-f23c91a70cca . _:0aa7c726-b547-6a87-557f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime ; _:pointType "" . _:b-040f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-27 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-27 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b547-6a88-5580-f23c91a70cca . _:0aa7c726-b547-6a88-5580-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0410 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-27 Zone Temperature" ; ph:dis "Bravo VAV 3-27 Zone Temperature" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b547-6a89-5581-f23c91a70cca . _:0aa7c726-b547-6a89-5581-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0411 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-28" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-28" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b547-6a8a-5582-f23c91a70cca . _:0aa7c726-b547-6a8a-5582-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 3 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 200 . _:b-0412 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-28 Damper Output" ; ph:dis "Bravo VAV 3-28 Damper Output" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b547-6a8b-5583-f23c91a70cca . _:0aa7c726-b547-6a8b-5583-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0413 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-28 Discharge Air Flow" ; ph:dis "Bravo VAV 3-28 Discharge Air Flow" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b547-6a8c-5584-f23c91a70cca . _:0aa7c726-b547-6a8c-5584-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0414 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-28 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-28 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b547-6a8d-5585-f23c91a70cca . _:0aa7c726-b547-6a8d-5585-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0415 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-28 Heating Valve Output" ; ph:dis "Bravo VAV 3-28 Heating Valve Output" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0aa7c726-b547-6a8e-5586-f23c91a70cca . _:0aa7c726-b547-6a8e-5586-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0416 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-28 Supply Air Temperature" ; ph:dis "Bravo VAV 3-28 Supply Air Temperature" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b556-acc0-5587-f23c91a70cca . _:0aa7c726-b556-acc0-5587-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0417 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-28 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-28 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b556-acc1-5588-f23c91a70cca . _:0aa7c726-b556-acc1-5588-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0418 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-28 Zone Temperature" ; ph:dis "Bravo VAV 3-28 Zone Temperature" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0aa7c726-b556-acc2-5589-f23c91a70cca . _:0aa7c726-b556-acc2-5589-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0419 a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-3" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-3" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b556-acc3-558a-f23c91a70cca . _:0aa7c726-b556-acc3-558a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 4.2 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 375 . _:b-041a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-3 Supply Air Flow" ; ph:dis "Bravo VAV 3-3 Supply Air Flow" ; phIoT:equipRef _:b-0419 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b556-acc4-558b-f23c91a70cca . _:0aa7c726-b556-acc4-558b-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-041b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-3 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-3 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-0419 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b556-acc5-558c-f23c91a70cca . _:0aa7c726-b556-acc5-558c-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-041c a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-4" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-4" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b556-acc6-558d-f23c91a70cca . _:0aa7c726-b556-acc6-558d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 155 ; _:designHotWaterPower 1.7 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 150 . _:b-041d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-4 Supply Air Flow" ; ph:dis "Bravo VAV 3-4 Supply Air Flow" ; phIoT:equipRef _:b-041c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b556-acc7-558e-f23c91a70cca . _:0aa7c726-b556-acc7-558e-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-041e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-4 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-4 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-041c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b556-acc8-558f-f23c91a70cca . _:0aa7c726-b556-acc8-558f-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-041f a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-5" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-5" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b556-acc9-5590-f23c91a70cca . _:0aa7c726-b556-acc9-5590-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 3.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0420 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-5 Supply Air Flow" ; ph:dis "Bravo VAV 3-5 Supply Air Flow" ; phIoT:equipRef _:b-041f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b556-acca-5591-f23c91a70cca . _:0aa7c726-b556-acca-5591-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0421 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-5 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-5 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-041f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b556-accb-5592-f23c91a70cca . _:0aa7c726-b556-accb-5592-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0422 a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-6" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-6" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b556-accc-5593-f23c91a70cca . _:0aa7c726-b556-accc-5593-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 6.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 600 . _:b-0423 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-6 Supply Air Flow" ; ph:dis "Bravo VAV 3-6 Supply Air Flow" ; phIoT:equipRef _:b-0422 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b556-accd-5594-f23c91a70cca . _:0aa7c726-b556-accd-5594-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0424 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-6 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-6 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-0422 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b556-acce-5595-f23c91a70cca . _:0aa7c726-b556-acce-5595-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0425 a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-7" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-7" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b556-accf-5596-f23c91a70cca . _:0aa7c726-b556-accf-5596-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 7.6 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 700 . _:b-0426 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-7 Supply Air Flow" ; ph:dis "Bravo VAV 3-7 Supply Air Flow" ; phIoT:equipRef _:b-0425 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b556-acd0-5597-f23c91a70cca . _:0aa7c726-b556-acd0-5597-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0427 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-7 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-7 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-0425 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b565-ef00-5598-f23c91a70cca . _:0aa7c726-b565-ef00-5598-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0428 a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-8" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-8" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b565-ef01-5599-f23c91a70cca . _:0aa7c726-b565-ef01-5599-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6.5 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0429 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-8 Supply Air Flow" ; ph:dis "Bravo VAV 3-8 Supply Air Flow" ; phIoT:equipRef _:b-0428 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b565-ef02-559a-f23c91a70cca . _:0aa7c726-b565-ef02-559a-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-042a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-8 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-8 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-0428 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b565-ef03-559b-f23c91a70cca . _:0aa7c726-b565-ef03-559b-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-042b a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-9" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-9" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0aa7c726-b565-ef04-559c-f23c91a70cca . _:0aa7c726-b565-ef04-559c-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 23 ; _:designHotWaterFlow 4 ; _:designAirFlow 2000 . _:b-042c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-9 Supply Air Flow" ; ph:dis "Bravo VAV 3-9 Supply Air Flow" ; phIoT:equipRef _:b-042b ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b565-ef05-559d-f23c91a70cca . _:0aa7c726-b565-ef05-559d-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-042d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-9 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-9 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-042b ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0aa7c726-b565-ef06-559e-f23c91a70cca . _:0aa7c726-b565-ef06-559e-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-042e a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo VAVs" ; ph:dis "Bravo VAVs" ; phIoT:siteRef _:b-0000 ; _:custom _:0aa7c726-b565-ef07-559f-f23c91a70cca . _:0aa7c726-b565-ef07-559f-f23c91a70cca rdfs:label "" . _:b-042f a phIoT:weatherStation ; ph:hasTag phIoT:weatherStation ; rdfs:label "Fort Wayne, IN" ; ph:dis "Fort Wayne, IN" ; ph:geoCity "Fort Wayne" ; ph:geoCoord "C(41.131,-85.129)"^^ph:coord ; ph:geoCountry "US" ; ph:geoState "IN" ; ph:tz "Indianapolis" . _:b-0430 a phIoT:his-point, phIoT:weather-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sensor, phScience:weather, phScience:weatherCond ; rdfs:label "Fort Wayne, IN Condition" ; ph:dis "Fort Wayne, IN Condition" ; ph:enum "unknown,clear,partlyCloudy,cloudy,showers,rain,thunderstorms,ice,flurries,snow" ; ph:kind "Str" ; ph:tz "Indianapolis" ; phIoT:weatherStationRef _:b-042f . _:b-0431 a phIoT:his-point, phIoT:weather-point ; ph:hasTag phScience:air, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor, phScience:weather ; rdfs:label "Fort Wayne, IN Humidity" ; ph:dis "Fort Wayne, IN Humidity" ; ph:kind "Number" ; ph:tz "Indianapolis" ; ph:unit "%RH" ; phIoT:weatherStationRef _:b-042f . _:b-0432 a phIoT:his-point, phIoT:weather-point ; ph:hasTag phScience:daytime, phIoT:his, phIoT:point, phIoT:sensor, phScience:weather ; rdfs:label "Fort Wayne, IN Sunrise" ; ph:dis "Fort Wayne, IN Sunrise" ; ph:kind "Bool" ; ph:tz "Indianapolis" ; phIoT:weatherStationRef _:b-042f . _:b-0433 a phIoT:his-point, phIoT:weather-point ; ph:hasTag phScience:air, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phScience:weather ; rdfs:label "Fort Wayne, IN Temp" ; ph:dis "Fort Wayne, IN Temp" ; ph:kind "Number" ; ph:tz "Indianapolis" ; ph:unit "\u00b0F" ; phIoT:weatherStationRef _:b-042f . _:b-0434 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Points Not Syncing" ; ph:dis "Points Not Syncing" ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0aa7c726-b565-ef08-55a0-f23c91a70cca . _:0aa7c726-b565-ef08-55a0-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime .